Intesis M-BUS to Modbus TCP Server Gateway
Productinformatie
Specificaties
- Product Name: M-BUS to Modbus TCP Server Gateway
- Gebruikershandleiding Versie: 1.0.3 "
- Publicatiedatum: 2025-07-21
Description and Order Codes
INMBSMEBxxx0100 Protocol Translator Gateway
M-Bus to Modbus TCP server gateway
BESTELCODE | OUDE BESTELCODE |
INMBSMEB0200100 | IBMBSMEB0200100 |
INMBSMEB0500100 | IBMBSMEB0500100 |
KENNISGEVING
The order code may vary depending on the product seller and the buyer’s location.
Gateway-capaciteit
Element | INMBSMEB0200100 | INMBSMEB0500100 | Notities |
Type of Modbus client devices | Modbus TCP | Those supporting the Modbus protocol. Communication over TCP/IP. | |
Number of Modbus client devices | Up to five TCP connections | Number of Modbus client devices supported by the gateway. | |
Number of Modbus registers | 500 | 1250 | Maximum number of points that can be defined in the virtual Modbus server device inside the gateway. |
Type of M-Bus devices | M-Bus EIA-485 slave devices | Those supporting the M-Bus EN-1434-3 Standard. Communication over EIA-485. | |
Number of M-Bus slave devices | 20 | 50 | Number of M-Bus slave devices supported by the gateway. |
Number of M-Bus signals | 500 | 1250 | Number of M-Bus signals (readings in the meters) that can be read from the gateway. |
Algemene informatie
Beoogd gebruik van de gebruikershandleiding
- Deze handleiding bevat de belangrijkste kenmerken van deze Intesis-gateway en de instructies voor de juiste installatie, configuratie en bediening ervan.
- Any person who installs, configures, or operates this gateway or any associated equipment should be aware of this manual’s contents.
- Bewaar deze handleiding voor toekomstig gebruik tijdens de installatie, configuratie en bediening.
Algemene veiligheidsinformatie
BELANGRIJK
Follow these instructions carefully. Improper work may seriously harm your health and damage the gateway and/or any other equipment connected to it.
- Only technical personnel, following these instructions and the country legislation for installing electrical equipment, can install and manipulate this gateway.
- Installeer deze gateway binnenshuis, op een locatie met beperkte toegang, en vermijd blootstelling aan directe zonnestraling, water, hoge relatieve vochtigheid of stof.
- Preferably, mount this gateway on a DIN rail inside a grounded metallic cabinet, following the instructions in this manual.
- If mounting on a wall, firmly fix this gateway on a non-vibrating surface, following the instructions in this manual. Connect this gateway only to networks without routing to the outside plant.
- All communication ports are considered for indoor use and must only be connected to SELV circuits.
- Disconnect all systems from power before manipulating and connecting them to the gateway.
- Gebruik een SELV-gecertificeerde NEC klasse 2-voeding of een beperkte stroombron (LPS).
MANDATORY GROUND CONNECTION - YOU MUST connect the gateway to the installation ground terminal. Always use the gateway’s dedicated connector.
- NEVER use the positive or negative gateway’s connectors to establish this connection. Not following this indication can cause ground loops and damage the gateway and/or any other equipment connected to it.
- If the power supply includes a ground connection, that terminal must be connected to ground.
- Use a circuit breaker between the gateway and the power supply. Rating: 250 V, 6 A.
- Geef de juiste voltage to power the gateway. The admitted range is detailed in the technical specifications table.
- Respect the expected polarity of power and communication cables when connecting them to the gateway. Safety instructions in other languages can be found here.
Waarschuwingsberichten en symbolen
VOORZICHTIGHEID
Instructie die moet worden gevolgd om een potentieel gevaarlijke situatie te voorkomen die, als deze niet wordt vermeden, kan leiden tot licht of matig letsel.BELANGRIJK
Instructie die moet worden gevolgd om het risico van verminderde functionaliteit en/of schade aan de apparatuur te voorkomen of om een netwerkveiligheidsrisico te voorkomen.OPMERKING
Aanvullende informatie die de installatie en/of bediening kan vergemakkelijken.TIP
Handige tips en suggesties.KENNISGEVING
Opmerkelijke informatie.
Overview
- This Intesis® gateway allows to integrate M-Bus devices into Modbus TCP systems easily.
- The aim of this integration is to make M-Bus devices accessible from a Modbus control system or device to get the same behavior as if the M-Bus device was part of the Modbus installation.
- For this, the Intesis gateway acts as a Modbus TCP server device in its Modbus interface, allowing it to read/write points from the Modbus client device(s). From the M-Bus point of view, the gateway acts as an M-Bus level converter and Master device (EN-1434-3). The gateway performs the readings of the M-Bus slave device(s) by automatic continuous polling or on demand (to reduce battery consumption).
- The gateway configuration is carried out through the Intesis MAPS configuration tool.
BELANGRIJK
This document assumes that the user is familiar with Modbus and M-Bus technologies and their technical terms.
Binnenin het pakket
INBEGREPEN ARTIKELEN
- Intesis INMBSMEBxxx0100 Protocol Translator Gateway
- Installatiehandleiding
Gateway Main Features
- Embedded level converter. Direct connection to M-Bus meters with no extra hardware required.
- Scan function: detect M-Bus meters and their available registers automatically.
- Import/Export of M-Bus meter templates. Reduce commissioning time when adding multiple meters of the same type.
- Baud rate configurable within the M-Bus allowed range (300 to 9600 bps. The devices are normally configured at 2400 bps).
- Specific parameters and timeouts are available to maximize compatibility with any possible peculiarity between different meter manufacturers.
- Availability of variables for communication errors, both at meter and general level, helping you to know if the communication with one or more meters has failed.
- DIN rail and wall mounting case.
- Flexible configuration using the Intesis MAPS configuration tool.
Gateway General Functionality
- This gateway acts as a server on its Modbus side and as a master on its M-Bus interface, thus allowing the integration of M-Bus devices into a Modbus system.
- The gateway is continuously polling the devices (together or individually), storing in its memory the current status of every signal you want to track, and serving this data to the installation when requested. This continuous polling can be activated/deactivated through a Modbus signal. It is also possible to configure the gateway to make a single polling of the meters (refresh of readings) at startup.
- Primary or secondary addressing is allowed for M-Bus devices. When a signal status changes, the gateway sends a write telegram to the installation, waits for the response, and performs the corresponding action.
- This action can be: force a polling of a specific M-Bus device or force a polling of all M-Bus devices. This can also be forced from the Modbus side at any time by writing a 1 in the corresponding binary point specially enabled for this purpose.
Other M-Bus information accessible from Modbus, using specific points of the gateway, is:
- Bus activity: Indicates if meters are currently being polled or polling is on standby.
- M-Bus status of every meter: This is sent by the own meter with every poll and indicates the internal status, which is manufacturer specific in every case.
A lack of response from a signal activates a communication error, allowing you to know which signal from which M-Bus device is not correctly working. There is also a general communication error available that will be active whenever the communication with one or more M-Bus meters has failed.
Hardware
Montage
- BELANGRIJK
Zorg er vóór de montage voor dat de gekozen installatieplaats de gateway beschermt tegen directe zonnestraling, water, hoge relatieve vochtigheid of stof. - OPMERKING
Mount the gateway on a wall or over a DIN rail. We recommend the DIN rail mounting option, preferably inside a grounded metallic industrial cabinet. - BELANGRIJK
Zorg ervoor dat de gateway na montage voldoende ruimte heeft voor alle aansluitingen. Zie Afmetingen (pagina 13).
DIN-RAILMONTAGE
- Fit the gateway’s top-side clip in the upper edge of the DIN rail.
- Press the low side of the gateway gently to lock it in the DIN rail.
- Make sure the gateway is firmly fixed.
OPMERKING
For some DIN rails, to complete step 2, you may need a small screwdriver or similar to pull the bottom clip down.
MUURMONTAGE
BELANGRIJK
For reasons of security, the maximum height for wall mounting is two meters (6.5 feet).
- Press the rear panel clips outwards until you hear a click.
- Use the clip holes to screw the gateway to the wall.
OPMERKING
Use M3 screws, 25mm (1″) length. - Make sure the gateway is firmly fixed.
Verbinding
- VOORZICHTIGHEID
Disconnect all systems from power before manipulating and connecting them to the gateway. - BELANGRIJK
Keep communication cables away from power and ground wires. - OPMERKING
Mount the gateway in the desired place before wiring it.
Gateway Connectors
- Stroomvoorziening: 24 VDC, Max.: 220 mA, 5.2 W
- Haven A: M-Bus port, for M-Bus bus connection.
- Ethernet-poort: For Modbus TCP connection.
Port A connectors | M-Bus wires |
A1 | + |
A2 | – |
OPMERKING
You can also use the Ethernet Port to connect the gateway to the PC for configuration purposes.
WIRING THE CONNECTORS
BELANGRIJK
For all connectors, use solid or stranded wires (twisted or with ferrule).
Cross-section/gauge per terminal:
- One core: 0.2 .. 2.5 mm2 / 24 .. 11 AWG
- Two cores: 0.2 .. 1.5 mm2 / 24 .. 15 AWG
- Three cores: Niet toegestaan
OPMERKING
To know more about each port’s specifications, see Technical Specifications (page 12).
Common Connections
Connecting the Gateway to the Power Supply
The power supply connector is a green pluggable terminal block (3 poles) labeled as 24Vdc.
BELANGRIJK
- Use a SELV-rated NEC class 2 or limited power source (LPS) power supply.
- Connect the gateway’s ground terminal to the installation grounding.
- Een verkeerde aansluiting kan aardlussen veroorzaken die de Intesis-gateway en/of andere systeemapparatuur kunnen beschadigen.
Pas de vol toetage within the admitted range and of enough power:
24 VDC, Max.: 220 mA, 5.2 W
BELANGRIJK
Respect the polarity labeled on the power connector for the positive and negative wires.
Connection Procedure for M-Bus
- The gateway connects directly to the M-Bus system without requiring any external RS-232 or EIA-485 to M-Bus level converter.
- Connect the M-Bus bus to connectors A1 (+) and A2 (-) of the gateway’s Port A. Respect the polarity.
- Remember that the gateway provides 36 VDC M-Bus voltage to the bus, acting also as an M-Bus level converter.
- If no response from the M-Bus device(s) to the frames sent by the gateway is received, check that they are operative and reachable from the network connection used by the gateway.
Connection Procedure for Modbus TCP
OPMERKING
Remember to check the Common Connections (page 10).
Connect the Modbus TCP Ethernet cable to the gateway’s Ethernet Port.
- BELANGRIJK
Gebruik een rechte Ethernet UTP/FTP CAT5- of hogere kabel. - BELANGRIJK
When commissioning the gateway for the first time, DHCP will be enabled for 30 seconds. After that time, the default IP address 192.168.100.246 will be set. - OPMERKING
De standaardpoort is 502. - BELANGRIJK
Als u communiceert via het LAN van het gebouw, neem dan contact op met de netwerkbeheerder en zorg ervoor dat verkeer op de gebruikte poort via alle LAN-paden wordt toegestaan.
Technische specificaties
Huisvesting | Plastic, type PC (UL 94 V-0). Color: Light Grey. RAL 7035Net dimensions (HxWxD): 93 x 53 x 58 mm / 3.6 x 2.1 x 2.3″ |
Montage | WallDIN rail (recommended mounting) EN60715 TH35 |
Terminal bedrading For power supply and low-voltagesignalen |
For distances longer than 3.05 meters (10 feet), use Class 2 cables. |
Stroom |
|
Ethernet | 1x Ethernet 10/100 Mbit/s RJ45 |
Poort A | 1x M-Bus port: pluggable terminal block (two poles) M-Bus power consumption:
Deeltage beoordeling: 36 V DC |
LED-indicatoren |
|
Operationeel temperatuur | Celsius: 0 .. 60°C / Fahrenheit: 32 .. 140°F |
Operationeel vochtigheid | 5 tot 95%, geen condensatie |
Bescherming | IP20 (IEC60529) |
Afmetingen
Netto afmetingen (HxBxD)
- millimeter: 93x53x58mm
- Duim: 3.6 x 2.1 x 2.3 inch
BELANGRIJK
Ensure the gateway has sufficient clearance for all connections when mounted.
M-Bus System
Algemene beschrijving
The M-Bus (“Meter-Bus”) is a European standard for remote reading of heat meters, and it is also usable for all other types of consumption meters, as well as for various sensors and actuators.
M-Bus standards are:
- EN 13757-2 (physical and link layer – Wired M-Bus)
- EN 13757-3 (application layer)
Many manufacturers of energy meters, pulse counters, water meters, electricity meters, etc., add an M-Bus interface to their devices, enabling them to be interconnected and remotely monitored through a 2-wire bus based on the M-Bus standards. There are many manufacturers of these measurement devices incorporating the M-Bus interface, and also some other manufacturers of specific M-Bus communication devices such as bus repeaters, EIA-232/EIA-485 to M-Bus level converters, etc.
M-Bus Interface
- The gateway connects directly to the M-Bus system. No external level converter is required.
- Connection to the M-Bus is made via the EIA-485 connection. Notice that the gateway also powers the bus, so no extra hardware is required to connect to M-Bus compatible meters or devices.
M-Bus Signals
The gateway supports several meter magnitudes and units typically used on energy, electricity, water, and other meters. This information is required to add the desired signals when integrating meters manually, as this process is done through the Intesis MAPS configuration tool by setting the meters up and then adding the signals each meter uses and assigning them accordingly in the Signals tab (page 20).
KENNISGEVING
- The type of signals available from each meter may differ depending on the manufacturer and model, so please refer to the device’s technical documentation to determine the signals available for a given meter when adding meters manually.
- However, Intesis MAPS also offers a much quicker and simpler alternative method for meter detection in the form of a scanning function. This scan detects all meters available on the bus and their signals and imports each signal with the units and details each meter provides. These signals can then be matched with the corresponding Modbus registers in the Signals tab for integration with the BMS.
Modbus System
Algemene beschrijving
- The Modbus protocol is an application-layer messaging protocol developed by Modicon in 1979. It is used to establish client-server communication between intelligent devices over different types of buses or networks. The Intesis gateway supports Modbus TCP.
- Modbus is a request/reply protocol and offers services specified by function codes. Modbus function codes are elements of Modbus request/reply PDUs (Protocol Data Units).
ModBus Interface
The Intesis gateway acts as a server device in its Modbus interface; the interface for this model is the Ethernet port. To access the points and resources of the gateway from a Modbus client device, you must specify the Modbus register addresses configured inside the gateway as those configured inside the gateway corresponding to the signals of the field device protocol.
Ondersteunde functies
Tabel 1. Modbus-functies
# | Functie | Lezen/Schrijven |
01 | Lees spoelen | R |
02 | Lees discrete ingangen | R |
03 | Lees Holdingregisters | R |
04 | Lees invoerregisters | R |
05 | Schrijf enkele spoel | W |
06 | Schrijf enkel register | W |
15 | Schrijf meerdere spoelen | W |
16 | Schrijf meerdere registers | W |
- Als pollrecords worden gebruikt om meer dan één register te lezen of te schrijven, moet het aangevraagde adresbereik geldige adressen bevatten; Als dit niet het geval is, retourneert de Intesis-gateway de bijbehorende Modbus-foutcode.
- All registers are of 2 bytes (16 bits)1, even if they are associated with signals of bit type on the other protocol’s side. Its content is expressed in MSB .. LSB.2
- Modbus-foutcodes worden volledig ondersteund. Ze worden verzonden wanneer een ongeldige Modbus-actie of -adres vereist is.
Modbus TCP
- Modbus TCP-communicatie wordt in principe gekenmerkt door de inbedding van het Modbus RTU-protocol in TCP/IP-frames, waardoor snellere communicatie en een langere afstand tussen client- en serverapparaten mogelijk zijn in vergelijking met RTU-communicatie via een seriële lijn. Een ander voordeel is het gebruik van de gemeenschappelijke TCP/IP-infrastructuur in gebouwen en het verzenden via WAN of internet. Het maakt ook het naast elkaar bestaan mogelijk van een of meer clients en uiteraard een of meer serverapparaten in een bepaald netwerk, allemaal met elkaar verbonden via een op TCP/IP gebaseerd netwerk.
- Gebruik de configuratietool om de IP-instellingen van de gateway (DHCP-status, eigen IP, netmasker en standaardgateway) en de TCP-poort te configureren.
- Default value. The measurement-related registers can be configured to be 4 or 8 bytes (32 or 64 bits) in Intesis MAPS if required.
- MSB: most significant bit; LSB: least significant bit
Adreskaart
The Modbus address map is fully configurable; any point in the gateway can be freely configured with the desired Modbus register address.
Definitie van Modbus-serverinterfacepunten
- The Modbus registers are fully configurable through the Intesis MAPS configuration tool; any point in the gateway can be freely configured with the desired Modbus register address.
- Aan elk punt dat in de gateway is gedefinieerd, zijn de volgende Modbus-functies gekoppeld:
Functie | Beschrijving |
#Bits |
|
Gegevens Coderen Formaat |
|
Functie Code |
|
Bytevolgorde |
|
Register Adres | Het Modbus-registeradres in het serverapparaat voor het punt. |
Beetje binnen het register | Bit inside the Modbus register (optional). The Intesis gateway allows bit decoding from generic 16 bits input/holding Modbus registers.Some devices use the bit coding into 16 bits input/holding Modbus registers to encode digital values. These registers are generally accessible using Modbus function codes 03 and 04 (read holding/input registers). |
Lezen/Schrijven |
|
Setup Process with the Configuration Tool
Vereisten
Voor deze integratie heb je nodig:
- De door HMS Networks geleverde artikelen:
- The Intesis INMBSMEBxxx0100 Protocol Translator Gateway.
- Link om de configuratietool te downloaden.
- Productdocumentatie.
- The respective M-Bus devices connected to the Port A of the gateway.
- A computer to run the Intesis MAPS configuration tool. Requirements:
- Windows® 7 or higher.
- Hard disk free space: 1 GB.
- RAM: 4GB.
- An Ethernet cable.
Intesis MAPS Configuration and Monitoring Tool
Invoering
- Intesis MAPS is a software tool for the configuration and monitoring of the Intesis gateways. It has been designed and developed in-house, ensuring an up-to-date tool to get all the potential of our gateways. It is compatible with Windows® 7 and higher.
- The installation procedure and the main functions are explained in the Intesis MAPS user manual. Please also check the Intesis MAPS user manual for specific information about the different parameters and how to configure them.
Create a New Project from a Template
- Open Intesis MAPS.
- Click Create New Project in the Start menu on the left.
You can create a project from scratch using a template. To find the appropriate template, filter the search by:- Clicking on the protocol logos.
- Typing the order code in the Order Code field.|
OPMERKING - The order code is printed on the silver label placed on the gateway’s right side.
- Looking for the Project Name on the list: IN-MBSTCP-MBUS.
- Select the desired template.
- Click Next or double-click the template on the list.
OPMERKING
Templates are just a starting point for your integration. Depending on the type of integration, you may have to modify some parameters.
BELANGRIJK
Don’t forget to save your project on your computer before exiting Intesis MAPS. To do so, go to Project → Save or Save As. Later on, you can load the project to Intesis MAPS and continue with the configuration.
Hoofdmenu voorbijview
De volgende paragrafen geven een overview of the five tabs that compose the Intesis MAPS main menu. Through these options, you will establish a connection between the gateway and the computer, set up your project through the Configuration and Signals tabs, send it to the gateway, and monitor that everything works fine using the Diagnostic tab.
TIP
Tooltip: Hover the cursor over a field, and a message will appear indicating the purpose of the parameter.
Verbindingstab
Click the Connection button in the menu bar to configure the gateway connection parameters.
Configuratietabblad
Select the Configuration tab to configure the connection parameters. This window contains three subsets of information: General (gateway general parameters), Modbus server (Modbus interface configuration), and M-Bus (M-Bus interface parameters).
Tabblad Signalen
All available objects, object instances, their corresponding Modbus register, and other main parameters are listed in the Signals tab. More information on each parameter and how to configure it can be found in the Intesis MAPS user manual.
Tabblad Ontvangen/Verzenden
Versturen:
Once you have finished setting the parameters, you have to send the configuration to the gateway:
Volg deze stappen:
- Klik op de knop Verzenden.
- If the gateway is still factory-set, you will be prompted to save the project on your PC. Once saved, the configuration is automatically sent to the gateway.
- If you have already saved the project, the configuration is automatically sent to the gateway.
- Maak opnieuw verbinding met de gateway nadat u het file.
KENNISGEVING
De gateway zal automatisch opnieuw opstarten zodra de nieuwe configuratie is geladen. Dit proces kan enkele seconden duren.
Ontvangen:
- Gebruik deze functie om bijvoorbeeld de configuratie van een gateway op te halenample, wanneer u enkele parameters moet wijzigen van een gateway die al in een installatie is geïnstalleerd.
- Zodra de configuratie is voltooid en verzonden, is de gateway al operationeel. Toch moet u controleren of alles correct werkt door naar het tabblad Diagnostiek te gaan.
Diagnostisch tabblad
BELANGRIJK
Om de diagnosetools te kunnen gebruiken, is verbinding met de gateway vereist.
Figuur 6. Venster met het tabblad Diagnostiek. Zoek de ToolBox tussen de bovenste tabbladenbalk en de console view. Daaronder, van links naar rechts: Console vieweh, Protocol viewers (de een boven de ander) en de signalen viewer
Dit gedeelte bestaat uit twee hoofdonderdelen:
Gereedschapskist
Gebruik het gedeelte Hulpmiddelen om:
- Controleer de huidige hardwarestatus van de gateway.
- Bewaar communicatielogboeken in een ZIP file voor diagnostische doeleinden.
- Krijg informatie over de gateway.
- Reset de gateway.
Viewers
Intesis MAPS biedt er verschillende viewers:
- Een generieke console viewer voor algemene informatie over communicatie en de gatewaystatus.
- A viewer voor beide protocollen om hun huidige status te controleren.
- Een signalen viewer to simulate the BMS behavior or check the system’s current values.
The layout of these viewers can be modified: - Using the Select Diagnostics View optie van de View menu:
OPMERKING
Layouts 3 and 4 offer two different tabbed options:
- Fixed console to the left and tabbed browser for the other viewers
- Full tabbed browser
- Clicking and dragging the border of a viewer. To do so, place the cursor over
the edge of a viewer. On the vertical edges, the cursor changes to to adjust the width, and on the horizontal edges, the cursor changes to
to adjust the height.
Mouser-elektronica
Geautoriseerde distributeur
Klik om View Informatie over prijzen, voorraad, levering en levenscyclus:
HMS Networks: INMBSMEB0200100 INMBSMEB0500100
Copyright © 2025 Intesis
Vrijwaring
- De informatie in dit document is alleen voor informatieve doeleinden. Informeer HMS Networks over eventuele onjuistheden of weglatingen in dit document. HMS Networks wijst elke verantwoordelijkheid of aansprakelijkheid af voor eventuele fouten in dit document.
- HMS Networks behoudt zich het recht voor om haar producten aan te passen in lijn met haar beleid van continue productontwikkeling. De informatie in dit document mag daarom niet worden opgevat als een verplichting van de kant van HMS Networks en kan zonder voorafgaande kennisgeving worden gewijzigd. HMS Networks verplicht zich niet om de informatie in dit document bij te werken of actueel te houden.
- De gegevens, bijv.ampDe bestanden en illustraties in dit document zijn ter illustratie opgenomen en zijn alleen bedoeld om het begrip van de functionaliteit en het gebruik van het product te helpen verbeteren. In view van het brede scala aan mogelijke toepassingen van het product, en vanwege de vele variabelen en vereisten die aan een bepaalde implementatie zijn verbonden, kan HMS Networks geen verantwoordelijkheid of aansprakelijkheid aanvaarden voor het daadwerkelijke gebruik op basis van de gegevens, exampbestanden of illustraties in dit document, noch voor eventuele schade opgelopen tijdens de installatie van het product. Degenen die verantwoordelijk zijn voor het gebruik van het product moeten voldoende kennis verwerven om ervoor te zorgen dat het product correct wordt gebruikt in hun specifieke toepassing en dat de toepassing voldoet aan alle prestatie- en veiligheidseisen, inclusief alle toepasselijke wetten, voorschriften, codes en normen. Verder aanvaardt HMS Networks onder geen enkele omstandigheid aansprakelijkheid of verantwoordelijkheid voor eventuele problemen die kunnen voortvloeien uit het gebruik van niet-gedocumenteerde functies of functionele bijwerkingen die buiten de gedocumenteerde reikwijdte van het product voorkomen. De effecten veroorzaakt door direct of indirect gebruik van dergelijke aspecten van het product zijn niet gedefinieerd en kunnen bijvoorbeeld compatibiliteitsproblemen en stabiliteitsproblemen omvatten.
Veelgestelde vragen
How many Modbus client devices are supported by the gateway?
The gateway supports up to 500 Modbus client devices.
What is the maximum number of M-Bus signals that can be read from the gateway?
The gateway can read up to 50 M-Bus signals from connected meters.
Documenten / Bronnen
![]() |
Intesis M-BUS to Modbus TCP Server Gateway [pdf] Gebruikershandleiding v1, Version 1.0.3, M-BUS to Modbus TCP Server Gateway, M-BUS, Modbus TCP Server Gateway, TCP Server Gateway, Server Gateway, Gateway |