Intesis M-BUS to Modbus TCP Server Gateway
Produk inligting
Spesifikasies
- Product Name: M-BUS to Modbus TCP Server Gateway
- Gebruikershandleiding weergawe: 1.0.3
- Publikasiedatum: 2025-07-21
Description and Order Codes
INMBSMEBxxx0100 Protocol Translator Gateway
M-Bus to Modbus TCP server gateway
BESTEL KODE | WETTELIKE BESTELLINGSKODE |
INMBSMEB0200100 | IBMBSMEB0200100 |
INMBSMEB0500100 | IBMBSMEB0500100 |
KENNISGEWING
Die bestelkode kan wissel na gelang van die verkoper van die produk en die koper se ligging.
Gateway Kapasiteit
Element | INMBSMEB0200100 | INMBSMEB0500100 | Notas |
Type of Modbus client devices | ModBus TCP | Those supporting the Modbus protocol. Communication over TCP/IP. | |
Number of Modbus client devices | Up to five TCP connections | Number of Modbus client devices supported by the gateway. | |
Number of Modbus registers | 500 | 1250 | Maximum number of points that can be defined in the virtual Modbus server device inside the gateway. |
Type of M-Bus devices | M-Bus EIA-485 slave devices | Those supporting the M-Bus EN-1434-3 Standard. Communication over EIA-485. | |
Number of M-Bus slave devices | 20 | 50 | Number of M-Bus slave devices supported by the gateway. |
Number of M-Bus signals | 500 | 1250 | Number of M-Bus signals (readings in the meters) that can be read from the gateway. |
Algemene inligting
Bedoelde gebruik van die gebruikershandleiding
- Hierdie handleiding bevat die hoofkenmerke van hierdie Intesis-poort en die instruksies vir die toepaslike installasie, konfigurasie en werking daarvan.
- Any person who installs, configures, or operates this gateway or any associated equipment should be aware of this manual’s contents.
- Bewaar hierdie handleiding vir toekomstige verwysing tydens die installasie, konfigurasie en werking.
Algemene veiligheidsinligting
BELANGRIK
Follow these instructions carefully. Improper work may seriously harm your health and damage the gateway and/or any other equipment connected to it.
- Only technical personnel, following these instructions and the country legislation for installing electrical equipment, can install and manipulate this gateway.
- Installeer hierdie poort binnenshuis, in 'n beperkte toegang plek, vermy blootstelling aan direkte sonstraling, water, hoë relatiewe humiditeit, of stof.
- Preferably, mount this gateway on a DIN rail inside a grounded metallic cabinet, following the instructions in this manual.
- If mounting on a wall, firmly fix this gateway on a non-vibrating surface, following the instructions in this manual. Connect this gateway only to networks without routing to the outside plant.
- All communication ports are considered for indoor use and must only be connected to SELV circuits.
- Disconnect all systems from power before manipulating and connecting them to the gateway.
- Gebruik SELV-gegradeerde NEC klas 2 of beperkte kragbron (LPS) kragtoevoer.
MANDATORY GROUND CONNECTION - YOU MUST connect the gateway to the installation ground terminal. Always use the gateway’s dedicated connector.
- NEVER use the positive or negative gateway’s connectors to establish this connection. Not following this indication can cause ground loops and damage the gateway and/or any other equipment connected to it.
- If the power supply includes a ground connection, that terminal must be connected to ground.
- Use a circuit breaker between the gateway and the power supply. Rating: 250 V, 6 A.
- Verskaf die korrekte voltage to power the gateway. The admitted range is detailed in the technical specifications table.
- Respect the expected polarity of power and communication cables when connecting them to the gateway. Safety instructions in other languages can be found here.
Vermaningsboodskappe en simbole
VERSIGTIG
Instruksies wat gevolg moet word om 'n potensieel gevaarlike situasie te vermy wat, indien dit nie vermy word nie, tot geringe of matige besering kan lei.BELANGRIK
Instruksies wat gevolg moet word om 'n risiko van verminderde funksionaliteit en/of skade aan die toerusting te vermy of om 'n netwerksekuriteitsrisiko te vermy.LET WEL
Bykomende inligting wat die installering en / of werking kan vergemaklik.WENK
Nuttige raad en voorstelle.KENNISGEWING
Merkwaardige inligting.
verbyview
- This Intesis® gateway allows to integrate M-Bus devices into Modbus TCP systems easily.
- The aim of this integration is to make M-Bus devices accessible from a Modbus control system or device to get the same behavior as if the M-Bus device was part of the Modbus installation.
- For this, the Intesis gateway acts as a Modbus TCP server device in its Modbus interface, allowing it to read/write points from the Modbus client device(s). From the M-Bus point of view, the gateway acts as an M-Bus level converter and Master device (EN-1434-3). The gateway performs the readings of the M-Bus slave device(s) by automatic continuous polling or on demand (to reduce battery consumption).
- The gateway configuration is carried out through the Intesis MAPS configuration tool.
BELANGRIK
This document assumes that the user is familiar with Modbus and M-Bus technologies and their technical terms.
Binne die Pakket
ITEMS INGESLUIT
- Intesis INMBSMEBxxx0100 Protocol Translator Gateway
- Installasie gids
Gateway Main Features
- Embedded level converter. Direct connection to M-Bus meters with no extra hardware required.
- Scan function: detect M-Bus meters and their available registers automatically.
- Import/Export of M-Bus meter templates. Reduce commissioning time when adding multiple meters of the same type.
- Baud rate configurable within the M-Bus allowed range (300 to 9600 bps. The devices are normally configured at 2400 bps).
- Specific parameters and timeouts are available to maximize compatibility with any possible peculiarity between different meter manufacturers.
- Availability of variables for communication errors, both at meter and general level, helping you to know if the communication with one or more meters has failed.
- DIN rail and wall mounting case.
- Flexible configuration using the Intesis MAPS configuration tool.
Gateway General Functionality
- This gateway acts as a server on its Modbus side and as a master on its M-Bus interface, thus allowing the integration of M-Bus devices into a Modbus system.
- The gateway is continuously polling the devices (together or individually), storing in its memory the current status of every signal you want to track, and serving this data to the installation when requested. This continuous polling can be activated/deactivated through a Modbus signal. It is also possible to configure the gateway to make a single polling of the meters (refresh of readings) at startup.
- Primary or secondary addressing is allowed for M-Bus devices. When a signal status changes, the gateway sends a write telegram to the installation, waits for the response, and performs the corresponding action.
- This action can be: force a polling of a specific M-Bus device or force a polling of all M-Bus devices. This can also be forced from the Modbus side at any time by writing a 1 in the corresponding binary point specially enabled for this purpose.
Other M-Bus information accessible from Modbus, using specific points of the gateway, is:
- Bus activity: Indicates if meters are currently being polled or polling is on standby.
- M-Bus status of every meter: This is sent by the own meter with every poll and indicates the internal status, which is manufacturer specific in every case.
A lack of response from a signal activates a communication error, allowing you to know which signal from which M-Bus device is not correctly working. There is also a general communication error available that will be active whenever the communication with one or more M-Bus meters has failed.
Hardeware
Montering
- BELANGRIK
Voordat u dit monteer, maak asseblief seker dat die gekose installasieplek die poort van direkte sonstraling, water, hoë relatiewe humiditeit of stof bewaar. - LET WEL
Mount the gateway on a wall or over a DIN rail. We recommend the DIN rail mounting option, preferably inside a grounded metallic industrial cabinet. - BELANGRIK
Maak seker dat die poort voldoende spelings het vir alle verbindings wanneer dit gemonteer is. Sien Afmetings (bladsy 13).
DIN RAIL BEVESTIGING
- Fit the gateway’s top-side clip in the upper edge of the DIN rail.
- Press the low side of the gateway gently to lock it in the DIN rail.
- Make sure the gateway is firmly fixed.
LET WEL
For some DIN rails, to complete step 2, you may need a small screwdriver or similar to pull the bottom clip down.
MUURMONTERING
BELANGRIK
For reasons of security, the maximum height for wall mounting is two meters (6.5 feet).
- Press the rear panel clips outwards until you hear a click.
- Use the clip holes to screw the gateway to the wall.
LET WEL
Use M3 screws, 25mm (1″) length. - Make sure the gateway is firmly fixed.
Verbinding
- VERSIGTIG
Disconnect all systems from power before manipulating and connecting them to the gateway. - BELANGRIK
Keep communication cables away from power and ground wires. - LET WEL
Mount the gateway in the desired place before wiring it.
Gateway Connectors
- Kragtoevoer: 24 VDC, Max.: 220 mA, 5.2 W
- Port A: M-Bus port, for M-Bus bus connection.
- Ethernet-poort: For Modbus TCP connection.
Port A connectors | M-Bus wires |
A1 | + |
A2 | – |
LET WEL
You can also use the Ethernet Port to connect the gateway to the PC for configuration purposes.
WIRING THE CONNECTORS
BELANGRIK
For all connectors, use solid or stranded wires (twisted or with ferrule).
Cross-section/gauge per terminal:
- Een kern: 0.2 .. 2.5 mm2 / 24 .. 11 AWG
- Twee kerne: 0.2 .. 1.5 mm2 / 24 .. 15 AWG
- Drie kerne: Nie toegelaat nie
LET WEL
To know more about each port’s specifications, see Technical Specifications (page 12).
Common Connections
Connecting the Gateway to the Power Supply
The power supply connector is a green pluggable terminal block (3 poles) labeled as 24Vdc.
BELANGRIK
- Use a SELV-rated NEC class 2 or limited power source (LPS) power supply.
- Connect the gateway’s ground terminal to the installation grounding.
- 'n Verkeerde verbinding kan aardlusse veroorsaak wat die Intesis-poort en/of enige ander stelseltoerusting kan beskadig.
Pas die voltage within the admitted range and of enough power:
24 VDC, Max.: 220 mA, 5.2 W
BELANGRIK
Respect the polarity labeled on the power connector for the positive and negative wires.
Connection Procedure for M-Bus
- The gateway connects directly to the M-Bus system without requiring any external RS-232 or EIA-485 to M-Bus level converter.
- Connect the M-Bus bus to connectors A1 (+) and A2 (-) of the gateway’s Port A. Respect the polarity.
- Remember that the gateway provides 36 VDC M-Bus voltage to the bus, acting also as an M-Bus level converter.
- If no response from the M-Bus device(s) to the frames sent by the gateway is received, check that they are operative and reachable from the network connection used by the gateway.
Connection Procedure for Modbus TCP
LET WEL
Remember to check the Common Connections (page 10).
Connect the Modbus TCP Ethernet cable to the gateway’s Ethernet Port.
- BELANGRIK
Gebruik 'n reguit Ethernet UTP/FTP CAT5 of hoër kabel. - BELANGRIK
When commissioning the gateway for the first time, DHCP will be enabled for 30 seconds. After that time, the default IP address 192.168.100.246 will be set. - LET WEL
Die verstekpoort is 502. - BELANGRIK
As daar deur die LAN van die gebou gekommunikeer word, kontak die netwerkadministrateur en maak seker dat verkeer op die gebruikte poort deur alle LAN-paaie toegelaat word.
Tegniese spesifikasies
Behuising | Plastic, type PC (UL 94 V-0). Color: Light Grey. RAL 7035Net dimensions (HxWxD): 93 x 53 x 58 mm / 3.6 x 2.1 x 2.3″ |
Montering | WallDIN rail (recommended mounting) EN60715 TH35 |
Terminale bedrading For power supply and low-voltageseine |
For distances longer than 3.05 meters (10 feet), use Class 2 cables. |
Krag |
|
Ethernet | 1 x Ethernet 10/100 Mbps RJ45 |
Poort A | 1 x M-Bus port: pluggable terminal block (two poles) M-Bus power consumption:
Voltage-gradering: 36 VDC |
LED aanwysers |
|
Operasioneel temperatuur | Celsius: 0 .. 60°C / Fahrenheit: 32 .. 140°F |
Operasioneel humiditeit | 5 tot 95%, geen kondensasie |
Beskerming | IP20 (IEC60529) |
Afmetings
Netto afmetings (HxBxD)
- Millimeter: 93 x 53 x 58 mm
- Duim: 3.6 x 2.1 x 2.3 duim
BELANGRIK
Ensure the gateway has sufficient clearance for all connections when mounted.
M-Bus System
Algemene beskrywing
The M-Bus (“Meter-Bus”) is a European standard for remote reading of heat meters, and it is also usable for all other types of consumption meters, as well as for various sensors and actuators.
M-Bus standards are:
- EN 13757-2 (physical and link layer – Wired M-Bus)
- EN 13757-3 (application layer)
Many manufacturers of energy meters, pulse counters, water meters, electricity meters, etc., add an M-Bus interface to their devices, enabling them to be interconnected and remotely monitored through a 2-wire bus based on the M-Bus standards. There are many manufacturers of these measurement devices incorporating the M-Bus interface, and also some other manufacturers of specific M-Bus communication devices such as bus repeaters, EIA-232/EIA-485 to M-Bus level converters, etc.
M-Bus Interface
- The gateway connects directly to the M-Bus system. No external level converter is required.
- Connection to the M-Bus is made via the EIA-485 connection. Notice that the gateway also powers the bus, so no extra hardware is required to connect to M-Bus compatible meters or devices.
M-Bus Signals
The gateway supports several meter magnitudes and units typically used on energy, electricity, water, and other meters. This information is required to add the desired signals when integrating meters manually, as this process is done through the Intesis MAPS configuration tool by setting the meters up and then adding the signals each meter uses and assigning them accordingly in the Signals tab (page 20).
KENNISGEWING
- The type of signals available from each meter may differ depending on the manufacturer and model, so please refer to the device’s technical documentation to determine the signals available for a given meter when adding meters manually.
- However, Intesis MAPS also offers a much quicker and simpler alternative method for meter detection in the form of a scanning function. This scan detects all meters available on the bus and their signals and imports each signal with the units and details each meter provides. These signals can then be matched with the corresponding Modbus registers in the Signals tab for integration with the BMS.
Modbus System
Algemene beskrywing
- The Modbus protocol is an application-layer messaging protocol developed by Modicon in 1979. It is used to establish client-server communication between intelligent devices over different types of buses or networks. The Intesis gateway supports Modbus TCP.
- Modbus is a request/reply protocol and offers services specified by function codes. Modbus function codes are elements of Modbus request/reply PDUs (Protocol Data Units).
ModBus Interface
The Intesis gateway acts as a server device in its Modbus interface; the interface for this model is the Ethernet port. To access the points and resources of the gateway from a Modbus client device, you must specify the Modbus register addresses configured inside the gateway as those configured inside the gateway corresponding to the signals of the field device protocol.
Ondersteunde funksies
Tabel 1. Modbus-funksies
# | Funksie | Lees/Skryf |
01 | Lees Coils | R |
02 | Lees Diskrete Insette | R |
03 | Lees Hoeweregisters | R |
04 | Lees Invoerregisters | R |
05 | Skryf Enkelspoel | W |
06 | Skryf Enkelregister | W |
15 | Skryf veelvuldige spoele | W |
16 | Skryf veelvuldige registers | W |
- Indien peilingsrekords gebruik word om meer as een register te lees of te skryf, moet die reeks adresse wat aangevra word, geldige adresse bevat; indien nie, sal die Intesis-poort die ooreenstemmende Modbus-foutkode terugstuur.
- All registers are of 2 bytes (16 bits)1, even if they are associated with signals of bit type on the other protocol’s side. Its content is expressed in MSB .. LSB.2
- Modbus-foutkodes word ten volle ondersteun. Hulle word gestuur wanneer 'n ongeldige Modbus-aksie of adres vereis word.
ModBus TCP
- Modbus TCP-kommunikasie word basies gekenmerk deur die inbedding van die Modbus RTU-protokol in TCP/IP-rame, wat vinniger kommunikasie en 'n langer afstand tussen kliënt- en bedienertoestelle moontlik maak in vergelyking met RTU-kommunikasie oor 'n reekslyn. Nog 'n voordeel is om algemene TCP/IP-infrastruktuur in geboue te gebruik en oor WAN of die internet te stuur. Dit laat ook die naasbestaan van een of meer kliënte en, natuurlik, een of meer bedienertoestelle in 'n gegewe netwerk toe, almal met mekaar verbind deur 'n TCP/IP-gebaseerde netwerk.
- Gebruik die konfigurasienutsding om die IP-instellings van die poort (DHCP-status, eie IP, netmasker en verstekpoort) en die TCP-poort op te stel.
- Default value. The measurement-related registers can be configured to be 4 or 8 bytes (32 or 64 bits) in Intesis MAPS if required.
- MSB: most significant bit; LSB: least significant bit
Adreskaart
The Modbus address map is fully configurable; any point in the gateway can be freely configured with the desired Modbus register address.
Modbus Server Interface Points Definisie
- The Modbus registers are fully configurable through the Intesis MAPS configuration tool; any point in the gateway can be freely configured with the desired Modbus register address.
- Elke punt wat in die poort gedefinieer word, het die volgende Modbus-kenmerke wat daarmee geassosieer word:
Kenmerk | Beskrywing |
#Buitjies |
|
Data Kodering Formaat |
|
Funksie Kode |
|
Byte bestelling |
|
Registreer Adres | Die Modbus-registeradres binne die bedienertoestel vir die punt. |
Bietjie in die register | Bit inside the Modbus register (optional). The Intesis gateway allows bit decoding from generic 16 bits input/holding Modbus registers.Some devices use the bit coding into 16 bits input/holding Modbus registers to encode digital values. These registers are generally accessible using Modbus function codes 03 and 04 (read holding/input registers). |
Lees/Skryf |
|
Setup Process with the Configuration Tool
Voorvereistes
Vir hierdie integrasie benodig jy:
- Die items wat deur HMS Networks gelewer word:
- The Intesis INMBSMEBxxx0100 Protocol Translator Gateway.
- Skakel om die konfigurasie-instrument af te laai.
- Produkdokumentasie.
- The respective M-Bus devices connected to the Port A of the gateway.
- A computer to run the Intesis MAPS configuration tool. Requirements:
- Windows® 7 or higher.
- Hard disk free space: 1 GB.
- RAM: 4GB.
- An Ethernet cable.
Intesis MAPS Configuration and Monitoring Tool
Inleiding
- Intesis MAPS is a software tool for the configuration and monitoring of the Intesis gateways. It has been designed and developed in-house, ensuring an up-to-date tool to get all the potential of our gateways. It is compatible with Windows® 7 and higher.
- The installation procedure and the main functions are explained in the Intesis MAPS user manual. Please also check the Intesis MAPS user manual for specific information about the different parameters and how to configure them.
Create a New Project from a Template
- Open Intesis MAPS.
- Click Create New Project in the Start menu on the left.
You can create a project from scratch using a template. To find the appropriate template, filter the search by:- Clicking on the protocol logos.
- Typing the order code in the Order Code field.|
LET WEL - The order code is printed on the silver label placed on the gateway’s right side.
- Looking for the Project Name on the list: IN-MBSTCP-MBUS.
- Select the desired template.
- Click Next or double-click the template on the list.
LET WEL
Templates are just a starting point for your integration. Depending on the type of integration, you may have to modify some parameters.
BELANGRIK
Don’t forget to save your project on your computer before exiting Intesis MAPS. To do so, go to Project → Save or Save As. Later on, you can load the project to Intesis MAPS and continue with the configuration.
Hoofkieslys verbyview
Die volgende afdelings bied 'n oorview of the five tabs that compose the Intesis MAPS main menu. Through these options, you will establish a connection between the gateway and the computer, set up your project through the Configuration and Signals tabs, send it to the gateway, and monitor that everything works fine using the Diagnostic tab.
WENK
Tooltip: Hover the cursor over a field, and a message will appear indicating the purpose of the parameter.
Verbinding Tab
Click the Connection button in the menu bar to configure the gateway connection parameters.
Konfigurasie-oortjie
Select the Configuration tab to configure the connection parameters. This window contains three subsets of information: General (gateway general parameters), Modbus server (Modbus interface configuration), and M-Bus (M-Bus interface parameters).
Seine Tab
All available objects, object instances, their corresponding Modbus register, and other main parameters are listed in the Signals tab. More information on each parameter and how to configure it can be found in the Intesis MAPS user manual.
Ontvang/stuur-oortjie
Stuur:
Once you have finished setting the parameters, you have to send the configuration to the gateway:
Volg hierdie stappe:
- Klik op die Stuur-knoppie.
- If the gateway is still factory-set, you will be prompted to save the project on your PC. Once saved, the configuration is automatically sent to the gateway.
- If you have already saved the project, the configuration is automatically sent to the gateway.
- Koppel weer met die poort na die stuur van die file.
KENNISGEWING
Die poort sal outomaties herlaai sodra die nuwe konfigurasie gelaai is. Hierdie proses kan 'n paar sekondes neem.
Ontvang:
- Gebruik hierdie funksie om die konfigurasie van 'n poort te kry, bvample, wanneer jy 'n paar parameters van 'n poort wat reeds in 'n installasie gemonteer is, moet verander.
- Sodra die konfigurasie voltooi en gestuur is, is die poort reeds in werking. Desondanks moet u seker maak dat alles reg werk deur die Diagnostiese-oortjie in te voer.
Diagnostiese oortjie
BELANGRIK
Verbinding met die poort is nodig om die diagnostiese gereedskap te gebruik.
Figuur 6. Diagnostiese oortjie-venster. Vind die ToolBox tussen die boonste oortjiesbalk en die konsole view. Onder dit, van links na regs: Console vieweh, Protokol viewers (een bo die ander), en die Seine viewer
Hierdie afdeling het twee hoofdele:
Gereedskapkas
Gebruik die gereedskap-afdeling om:
- Gaan die huidige hardewarestatus van die poort na.
- Stoor kommunikasie logs in 'n zip file vir diagnostiese doeleindes.
- Kry inligting oor die poort.
- Stel die poort terug.
Viewers
Intesis MAPS bied verskeie viewers:
- 'n Generiese konsole viewer vir algemene inligting oor kommunikasie en die poortstatus.
- A viewvir beide protokolle om hul huidige status na te gaan.
- A seine viewer to simulate the BMS behavior or check the system’s current values.
The layout of these viewers can be modified: - Using the Select Diagnostics View opsie van die View spyskaart:
LET WEL
Layouts 3 and 4 offer two different tabbed options:
- Fixed console to the left and tabbed browser for the other viewers
- Full tabbed browser
- Clicking and dragging the border of a viewer. To do so, place the cursor over
the edge of a viewer. On the vertical edges, the cursor changes to to adjust the width, and on the horizontal edges, the cursor changes to
to adjust the height.
Mouser Electronics
Gemagtigde verspreider
Klik om View Pryse, voorraad, aflewering en lewensiklusinligting:
HMS Networks: INMBSMEB0200100 INMBSMEB0500100
Kopiereg © 2025 Intesis
Disclaimer
- Die inligting in hierdie dokument is slegs vir inligtingsdoeleindes. Stel HMS Networks in kennis van enige onakkuraathede of weglatings in hierdie dokument. HMS Networks ontken alle verantwoordelikheid of aanspreeklikheid vir enige foute wat in hierdie dokument voorkom.
- HMS Networks behou die reg voor om sy produkte aan te pas in ooreenstemming met sy beleid van deurlopende produkontwikkeling. Die inligting in hierdie dokument word dus nie as 'n verbintenis van HMS Networks beskou nie en kan sonder kennisgewing verander word. HMS Networks verbind nie daartoe om die inligting in hierdie dokument by te werk of op datum te hou nie.
- Die data, bvampDie illustrasies en illustrasies in hierdie dokument is ingesluit vir illustratiewe doeleindes en is slegs bedoel om die begrip van die funksionaliteit en hantering van die produk te verbeter. In view vanweë die wye verskeidenheid moontlike toepassings van die produk, en vanweë die vele veranderlikes en vereistes wat verband hou met 'n spesifieke implementering, kan HMS Networks nie verantwoordelikheid of aanspreeklikheid aanvaar vir die werklike gebruik op grond van die data nie, bv.amples of illustrasies wat in hierdie dokument ingesluit is, asook vir enige skade wat tydens die installering van die produk opgedoen word. Diegene wat verantwoordelik is vir die gebruik van die produk, moet voldoende kennis opdoen om te verseker dat die produk korrek in hul spesifieke toepassings gebruik word en dat die toepassing voldoen aan alle prestasie- en veiligheidsvereistes, insluitend alle toepaslike wette, regulasies, kodes en standaarde. Verder aanvaar HMS Networks onder geen omstandighede aanspreeklikheid of verantwoordelikheid vir enige probleme wat mag ontstaan as gevolg van die gebruik van ongedokumenteerde funksies of funksionele newe -effekte wat buite die gedokumenteerde omvang van die produk voorkom nie. Die gevolge wat veroorsaak word deur direkte of indirekte gebruik van sulke aspekte van die produk, is ongedefinieerd en kan byvoorbeeld probleme met verenigbaarheid en stabiliteit insluit.
Gereelde vrae
How many Modbus client devices are supported by the gateway?
The gateway supports up to 500 Modbus client devices.
What is the maximum number of M-Bus signals that can be read from the gateway?
The gateway can read up to 50 M-Bus signals from connected meters.
Dokumente / Hulpbronne
![]() |
Intesis M-BUS to Modbus TCP Server Gateway [pdfGebruikershandleiding v1, Version 1.0.3, M-BUS to Modbus TCP Server Gateway, M-BUS, Modbus TCP Server Gateway, TCP Server Gateway, Server Gateway, Gateway |