Intesis M-BUS to Modbus TCP Server Gateway
Produktinformasjon
Spesifikasjoner
- Product Name: M-BUS to Modbus TCP Server Gateway
- Brukerhåndbok versjon: 1.0.3
- Publiseringsdato: 2025-07-21
Description and Order Codes
INMBSMEBxxx0100 Protocol Translator Gateway
M-Bus to Modbus TCP server gateway
BESTILL KODE | LEGACY BESTILLINGSKODE |
INMBSMEB0200100 | IBMBSMEB0200100 |
INMBSMEB0500100 | IBMBSMEB0500100 |
MERKNAD
Ordrekoden kan variere avhengig av produktselgeren og kjøperens beliggenhet.
Gateway kapasitet
Element | INMBSMEB0200100 | INMBSMEB0500100 | Notater |
Type of Modbus client devices | ModBus TCP | Those supporting the Modbus protocol. Communication over TCP/IP. | |
Number of Modbus client devices | Up to five TCP connections | Number of Modbus client devices supported by the gateway. | |
Number of Modbus registers | 500 | 1250 | Maximum number of points that can be defined in the virtual Modbus server device inside the gateway. |
Type of M-Bus devices | M-Bus EIA-485 slave devices | Those supporting the M-Bus EN-1434-3 Standard. Communication over EIA-485. | |
Number of M-Bus slave devices | 20 | 50 | Number of M-Bus slave devices supported by the gateway. |
Number of M-Bus signals | 500 | 1250 | Number of M-Bus signals (readings in the meters) that can be read from the gateway. |
Generell informasjon
Tiltenkt bruk av brukerhåndboken
- Denne håndboken inneholder hovedfunksjonene til denne Intesis-gatewayen og instruksjonene for riktig installasjon, konfigurasjon og drift.
- Any person who installs, configures, or operates this gateway or any associated equipment should be aware of this manual’s contents.
- Ta vare på denne håndboken for fremtidig referanse under installasjon, konfigurasjon og drift.
Generell sikkerhetsinformasjon
VIKTIG
Follow these instructions carefully. Improper work may seriously harm your health and damage the gateway and/or any other equipment connected to it.
- Only technical personnel, following these instructions and the country legislation for installing electrical equipment, can install and manipulate this gateway.
- Installer denne gatewayen innendørs, på et sted med begrenset tilgang, og unngå eksponering for direkte solstråling, vann, høy relativ fuktighet eller støv.
- Preferably, mount this gateway on a DIN rail inside a grounded metallic cabinet, following the instructions in this manual.
- If mounting on a wall, firmly fix this gateway on a non-vibrating surface, following the instructions in this manual. Connect this gateway only to networks without routing to the outside plant.
- All communication ports are considered for indoor use and must only be connected to SELV circuits.
- Disconnect all systems from power before manipulating and connecting them to the gateway.
- Bruk SELV-klassifisert NEC klasse 2 eller strømforsyning med begrenset strømkilde (LPS).
MANDATORY GROUND CONNECTION - YOU MUST connect the gateway to the installation ground terminal. Always use the gateway’s dedicated connector.
- NEVER use the positive or negative gateway’s connectors to establish this connection. Not following this indication can cause ground loops and damage the gateway and/or any other equipment connected to it.
- If the power supply includes a ground connection, that terminal must be connected to ground.
- Use a circuit breaker between the gateway and the power supply. Rating: 250 V, 6 A.
- Angi riktig voltage to power the gateway. The admitted range is detailed in the technical specifications table.
- Respect the expected polarity of power and communication cables when connecting them to the gateway. Safety instructions in other languages can be found here.
Formaningsmeldinger og symboler
FORSIKTIGHET
Instruksjoner som må følges for å unngå en potensielt farlig situasjon som, hvis den ikke unngås, kan føre til mindre eller moderate skader.VIKTIG
Instruksjoner som må følges for å unngå risiko for redusert funksjonalitet og/eller skade på utstyret eller for å unngå nettverkssikkerhetsrisiko.NOTE
Tilleggsinformasjon som kan lette installasjon og / eller drift.TUPP
Nyttige råd og forslag.MERKNAD
Bemerkelsesverdig informasjon.
Overview
- This Intesis® gateway allows to integrate M-Bus devices into Modbus TCP systems easily.
- The aim of this integration is to make M-Bus devices accessible from a Modbus control system or device to get the same behavior as if the M-Bus device was part of the Modbus installation.
- For this, the Intesis gateway acts as a Modbus TCP server device in its Modbus interface, allowing it to read/write points from the Modbus client device(s). From the M-Bus point of view, the gateway acts as an M-Bus level converter and Master device (EN-1434-3). The gateway performs the readings of the M-Bus slave device(s) by automatic continuous polling or on demand (to reduce battery consumption).
- The gateway configuration is carried out through the Intesis MAPS configuration tool.
VIKTIG
This document assumes that the user is familiar with Modbus and M-Bus technologies and their technical terms.
Inne i pakken
VARER INKLUDERT
- Intesis INMBSMEBxxx0100 Protocol Translator Gateway
- Installasjonsveiledning
Gateway Main Features
- Embedded level converter. Direct connection to M-Bus meters with no extra hardware required.
- Scan function: detect M-Bus meters and their available registers automatically.
- Import/Export of M-Bus meter templates. Reduce commissioning time when adding multiple meters of the same type.
- Baud rate configurable within the M-Bus allowed range (300 to 9600 bps. The devices are normally configured at 2400 bps).
- Specific parameters and timeouts are available to maximize compatibility with any possible peculiarity between different meter manufacturers.
- Availability of variables for communication errors, both at meter and general level, helping you to know if the communication with one or more meters has failed.
- DIN rail and wall mounting case.
- Flexible configuration using the Intesis MAPS configuration tool.
Gateway General Functionality
- This gateway acts as a server on its Modbus side and as a master on its M-Bus interface, thus allowing the integration of M-Bus devices into a Modbus system.
- The gateway is continuously polling the devices (together or individually), storing in its memory the current status of every signal you want to track, and serving this data to the installation when requested. This continuous polling can be activated/deactivated through a Modbus signal. It is also possible to configure the gateway to make a single polling of the meters (refresh of readings) at startup.
- Primary or secondary addressing is allowed for M-Bus devices. When a signal status changes, the gateway sends a write telegram to the installation, waits for the response, and performs the corresponding action.
- This action can be: force a polling of a specific M-Bus device or force a polling of all M-Bus devices. This can also be forced from the Modbus side at any time by writing a 1 in the corresponding binary point specially enabled for this purpose.
Other M-Bus information accessible from Modbus, using specific points of the gateway, is:
- Bus activity: Indicates if meters are currently being polled or polling is on standby.
- M-Bus status of every meter: This is sent by the own meter with every poll and indicates the internal status, which is manufacturer specific in every case.
A lack of response from a signal activates a communication error, allowing you to know which signal from which M-Bus device is not correctly working. There is also a general communication error available that will be active whenever the communication with one or more M-Bus meters has failed.
Maskinvare
Montering
- VIKTIG
Før montering, sørg for at det valgte installasjonsstedet beskytter porten mot direkte solstråling, vann, høy relativ fuktighet eller støv. - NOTE
Mount the gateway on a wall or over a DIN rail. We recommend the DIN rail mounting option, preferably inside a grounded metallic industrial cabinet. - VIKTIG
Sørg for at gatewayen har tilstrekkelige klaringer for alle tilkoblinger når den er montert. Se Dimensjoner (side 13).
DIN-SKINNEMONTERING
- Fit the gateway’s top-side clip in the upper edge of the DIN rail.
- Press the low side of the gateway gently to lock it in the DIN rail.
- Make sure the gateway is firmly fixed.
NOTE
For some DIN rails, to complete step 2, you may need a small screwdriver or similar to pull the bottom clip down.
VEGGMONTERING
VIKTIG
For reasons of security, the maximum height for wall mounting is two meters (6.5 feet).
- Press the rear panel clips outwards until you hear a click.
- Use the clip holes to screw the gateway to the wall.
NOTE
Use M3 screws, 25mm (1″) length. - Make sure the gateway is firmly fixed.
Forbindelse
- FORSIKTIGHET
Disconnect all systems from power before manipulating and connecting them to the gateway. - VIKTIG
Keep communication cables away from power and ground wires. - NOTE
Mount the gateway in the desired place before wiring it.
Gateway Connectors
- Strømforsyning: 24 VDC, Max.: 220 mA, 5.2 W
- Havn A: M-Bus port, for M-Bus bus connection.
- Ethernet-port: For Modbus TCP connection.
Port A connectors | M-Bus wires |
A1 | + |
A2 | – |
NOTE
You can also use the Ethernet Port to connect the gateway to the PC for configuration purposes.
WIRING THE CONNECTORS
VIKTIG
For all connectors, use solid or stranded wires (twisted or with ferrule).
Cross-section/gauge per terminal:
- Én kjerne: 0.2 .. 2.5 mm2 / 24 .. 11 AWG
- To kjerner: 0.2 .. 1.5 mm2 / 24 .. 15 AWG
- Tre kjerner: Ikke tillatt
NOTE
To know more about each port’s specifications, see Technical Specifications (page 12).
Common Connections
Connecting the Gateway to the Power Supply
The power supply connector is a green pluggable terminal block (3 poles) labeled as 24Vdc.
VIKTIG
- Use a SELV-rated NEC class 2 or limited power source (LPS) power supply.
- Connect the gateway’s ground terminal to the installation grounding.
- En feil tilkobling kan forårsake jordsløyfer som kan skade Intesis-gatewayen og/eller annet systemutstyr.
Påfør voltage within the admitted range and of enough power:
24 VDC, Max.: 220 mA, 5.2 W
VIKTIG
Respect the polarity labeled on the power connector for the positive and negative wires.
Connection Procedure for M-Bus
- The gateway connects directly to the M-Bus system without requiring any external RS-232 or EIA-485 to M-Bus level converter.
- Connect the M-Bus bus to connectors A1 (+) and A2 (-) of the gateway’s Port A. Respect the polarity.
- Remember that the gateway provides 36 VDC M-Bus voltage to the bus, acting also as an M-Bus level converter.
- If no response from the M-Bus device(s) to the frames sent by the gateway is received, check that they are operative and reachable from the network connection used by the gateway.
Connection Procedure for Modbus TCP
NOTE
Remember to check the Common Connections (page 10).
Connect the Modbus TCP Ethernet cable to the gateway’s Ethernet Port.
- VIKTIG
Bruk en rett Ethernet UTP/FTP CAT5 eller høyere kabel. - VIKTIG
When commissioning the gateway for the first time, DHCP will be enabled for 30 seconds. After that time, the default IP address 192.168.100.246 will be set. - NOTE
Standardporten er 502. - VIKTIG
Hvis du kommuniserer gjennom bygningens LAN, kontakt nettverksadministratoren og sørg for at trafikk på den brukte porten er tillatt gjennom alle LAN-baner.
Tekniske spesifikasjoner
Bolig | Plastic, type PC (UL 94 V-0). Color: Light Grey. RAL 7035Net dimensions (HxWxD): 93 x 53 x 58 mm / 3.6 x 2.1 x 2.3″ |
Montering | WallDIN rail (recommended mounting) EN60715 TH35 |
Terminal ledninger For power supply and low-voltagesignaler |
For distances longer than 3.05 meters (10 feet), use Class 2 cables. |
Makt |
|
Ethernet | 1 x Ethernet 10/100 Mbps RJ45 |
Port A | 1 x M-Bus port: pluggable terminal block (two poles) M-Bus power consumption:
Voltage-vurdering: 36 VDC |
LED-indikatorer |
|
Operasjonell temperatur | Celsius: 0 .. 60°C / Fahrenheit: 32 .. 140°F |
Operasjonell fuktighet | 5 til 95%, ingen kondens |
Beskyttelse | IP20 (IEC60529) |
Dimensjoner
Netto dimensjoner (HxBxD)
- Millimeter: 93 x 53 x 58 mm
- Tommer: 3.6 x 2.1 x 2.3"
VIKTIG
Ensure the gateway has sufficient clearance for all connections when mounted.
M-Bus System
Generell beskrivelse
The M-Bus (“Meter-Bus”) is a European standard for remote reading of heat meters, and it is also usable for all other types of consumption meters, as well as for various sensors and actuators.
M-Bus standards are:
- EN 13757-2 (physical and link layer – Wired M-Bus)
- EN 13757-3 (application layer)
Many manufacturers of energy meters, pulse counters, water meters, electricity meters, etc., add an M-Bus interface to their devices, enabling them to be interconnected and remotely monitored through a 2-wire bus based on the M-Bus standards. There are many manufacturers of these measurement devices incorporating the M-Bus interface, and also some other manufacturers of specific M-Bus communication devices such as bus repeaters, EIA-232/EIA-485 to M-Bus level converters, etc.
M-Bus Interface
- The gateway connects directly to the M-Bus system. No external level converter is required.
- Connection to the M-Bus is made via the EIA-485 connection. Notice that the gateway also powers the bus, so no extra hardware is required to connect to M-Bus compatible meters or devices.
M-Bus Signals
The gateway supports several meter magnitudes and units typically used on energy, electricity, water, and other meters. This information is required to add the desired signals when integrating meters manually, as this process is done through the Intesis MAPS configuration tool by setting the meters up and then adding the signals each meter uses and assigning them accordingly in the Signals tab (page 20).
MERKNAD
- The type of signals available from each meter may differ depending on the manufacturer and model, so please refer to the device’s technical documentation to determine the signals available for a given meter when adding meters manually.
- However, Intesis MAPS also offers a much quicker and simpler alternative method for meter detection in the form of a scanning function. This scan detects all meters available on the bus and their signals and imports each signal with the units and details each meter provides. These signals can then be matched with the corresponding Modbus registers in the Signals tab for integration with the BMS.
Modbus System
Generell beskrivelse
- The Modbus protocol is an application-layer messaging protocol developed by Modicon in 1979. It is used to establish client-server communication between intelligent devices over different types of buses or networks. The Intesis gateway supports Modbus TCP.
- Modbus is a request/reply protocol and offers services specified by function codes. Modbus function codes are elements of Modbus request/reply PDUs (Protocol Data Units).
ModBus Interface
The Intesis gateway acts as a server device in its Modbus interface; the interface for this model is the Ethernet port. To access the points and resources of the gateway from a Modbus client device, you must specify the Modbus register addresses configured inside the gateway as those configured inside the gateway corresponding to the signals of the field device protocol.
Funksjoner som støttes
Tabell 1. Modbus-funksjoner
# | Funksjon | Les/skriv |
01 | Les Coils | R |
02 | Les diskrete innganger | R |
03 | Les beholdningsregistre | R |
04 | Les inngangsregistre | R |
05 | Skriv Single Coil | W |
06 | Skriv enkeltregister | W |
15 | Skriv flere spoler | W |
16 | Skriv flere registre | W |
- Hvis avstemningsposter brukes til å lese eller skrive mer enn ett register, må utvalget av adresser inneholde gyldige adresser; hvis ikke, vil Intesis-gatewayen returnere den tilsvarende Modbus-feilkoden.
- All registers are of 2 bytes (16 bits)1, even if they are associated with signals of bit type on the other protocol’s side. Its content is expressed in MSB .. LSB.2
- Modbus-feilkoder støttes fullt ut. De sendes når det kreves en ugyldig Modbus-handling eller adresse.
ModBus TCP
- Modbus TCP-kommunikasjon kjennetegnes i hovedsak av innbygging av Modbus RTU-protokollen i TCP/IP-rammer, som tillater raskere kommunikasjon og lengre avstand mellom klient- og serverenheter sammenlignet med RTU-kommunikasjon over en seriell linje. En annen fordel er bruk av vanlig TCP/IP-infrastruktur i bygninger og overføring over WAN eller internett. Den tillater også sameksistens av én eller flere klienter og, selvfølgelig, én eller flere serverenheter i et gitt nettverk, alle sammenkoblet gjennom et TCP/IP-basert nettverk.
- Bruk konfigurasjonsverktøyet til å konfigurere IP-innstillingene til gatewayen (DHCP-status, egen IP, nettmaske og standard gateway) og TCP-porten.
- Default value. The measurement-related registers can be configured to be 4 or 8 bytes (32 or 64 bits) in Intesis MAPS if required.
- MSB: most significant bit; LSB: least significant bit
Adressekart
The Modbus address map is fully configurable; any point in the gateway can be freely configured with the desired Modbus register address.
Modbus Server Interface Points Definisjon
- The Modbus registers are fully configurable through the Intesis MAPS configuration tool; any point in the gateway can be freely configured with the desired Modbus register address.
- Hvert punkt definert i gatewayen har følgende Modbus-funksjoner knyttet til seg:
Trekk | Beskrivelse |
#biter |
|
Data Koding Format |
|
Funksjon Kode |
|
Byte -ordre |
|
Register Adresse | Modbus-registeradressen inne i serverenheten for punktet. |
Litt inne i registeret | Bit inside the Modbus register (optional). The Intesis gateway allows bit decoding from generic 16 bits input/holding Modbus registers.Some devices use the bit coding into 16 bits input/holding Modbus registers to encode digital values. These registers are generally accessible using Modbus function codes 03 and 04 (read holding/input registers). |
Les/skriv |
|
Setup Process with the Configuration Tool
Forutsetninger
For denne integrasjonen trenger du:
- Varene levert av HMS Networks:
- The Intesis INMBSMEBxxx0100 Protocol Translator Gateway.
- Link for å laste ned konfigurasjonsverktøyet.
- Produktdokumentasjon.
- The respective M-Bus devices connected to the Port A of the gateway.
- A computer to run the Intesis MAPS configuration tool. Requirements:
- Windows® 7 or higher.
- Hard disk free space: 1 GB.
- RAM: 4GB.
- An Ethernet cable.
Intesis MAPS Configuration and Monitoring Tool
Introduksjon
- Intesis MAPS is a software tool for the configuration and monitoring of the Intesis gateways. It has been designed and developed in-house, ensuring an up-to-date tool to get all the potential of our gateways. It is compatible with Windows® 7 and higher.
- The installation procedure and the main functions are explained in the Intesis MAPS user manual. Please also check the Intesis MAPS user manual for specific information about the different parameters and how to configure them.
Create a New Project from a Template
- Open Intesis MAPS.
- Click Create New Project in the Start menu on the left.
You can create a project from scratch using a template. To find the appropriate template, filter the search by:- Clicking on the protocol logos.
- Typing the order code in the Order Code field.|
NOTE - The order code is printed on the silver label placed on the gateway’s right side.
- Looking for the Project Name on the list: IN-MBSTCP-MBUS.
- Select the desired template.
- Click Next or double-click the template on the list.
NOTE
Templates are just a starting point for your integration. Depending on the type of integration, you may have to modify some parameters.
VIKTIG
Don’t forget to save your project on your computer before exiting Intesis MAPS. To do so, go to Project → Save or Save As. Later on, you can load the project to Intesis MAPS and continue with the configuration.
Hovedmeny overview
Følgende avsnitt gir en overview of the five tabs that compose the Intesis MAPS main menu. Through these options, you will establish a connection between the gateway and the computer, set up your project through the Configuration and Signals tabs, send it to the gateway, and monitor that everything works fine using the Diagnostic tab.
TUPP
Tooltip: Hover the cursor over a field, and a message will appear indicating the purpose of the parameter.
Tilkobling Tab
Click the Connection button in the menu bar to configure the gateway connection parameters.
Konfigurasjonsfanen
Select the Configuration tab to configure the connection parameters. This window contains three subsets of information: General (gateway general parameters), Modbus server (Modbus interface configuration), and M-Bus (M-Bus interface parameters).
Signaler Tab
All available objects, object instances, their corresponding Modbus register, and other main parameters are listed in the Signals tab. More information on each parameter and how to configure it can be found in the Intesis MAPS user manual.
Motta/send-fanen
Sende:
Once you have finished setting the parameters, you have to send the configuration to the gateway:
Følg disse trinnene:
- Klikk på Send-knappen.
- If the gateway is still factory-set, you will be prompted to save the project on your PC. Once saved, the configuration is automatically sent to the gateway.
- If you have already saved the project, the configuration is automatically sent to the gateway.
- Koble til igjen med gatewayen etter at du har sendt file.
MERKNAD
Gatewayen starter automatisk på nytt når den nye konfigurasjonen er lastet inn. Denne prosessen kan ta noen sekunder.
Motta:
- Bruk denne funksjonen for å få konfigurasjonen av en gateway, f.eksample, når du trenger å endre noen parametere for en gateway som allerede er montert i en installasjon.
- Når konfigurasjonen er fullført og sendt, er gatewayen allerede operativ. Likevel bør du sjekke at alt fungerer som det skal ved å gå inn i Diagnostikk-fanen.
Diagnostikkfane
VIKTIG
Tilkobling med gatewayen er nødvendig for å bruke diagnoseverktøyene.
Figur 6. Vinduet Diagnostikk. Finn verktøykassen mellom den øvre fanelinjen og konsollen view. Under den, fra venstre til høyre: Konsoll vieweh, protokoll viewers (den ene over den andre), og signalene viewer
Denne delen har to hoveddeler:
Verktøykasse
Bruk verktøydelen til å:
- Sjekk gjeldende maskinvarestatus for gatewayen.
- Lagre kommunikasjonslogger til en ZIP file for diagnostiske formål.
- Få informasjon om gatewayen.
- Tilbakestill gatewayen.
Viewers
Intesis MAPS gir flere viewers:
- En generisk konsoll viewer for generell informasjon om kommunikasjon og gatewaystatus.
- A viewer for begge protokollene for å sjekke gjeldende status.
- A signaliserer viewer to simulate the BMS behavior or check the system’s current values.
The layout of these viewers can be modified: - Using the Select Diagnostics View alternativ fra View Meny:
NOTE
Layouts 3 and 4 offer two different tabbed options:
- Fixed console to the left and tabbed browser for the other viewers
- Full tabbed browser
- Clicking and dragging the border of a viewer. To do so, place the cursor over
the edge of a viewer. On the vertical edges, the cursor changes to to adjust the width, and on the horizontal edges, the cursor changes to
to adjust the height.
Mouser elektronikk
Autorisert distributør
Klikk for å View Priser, inventar, levering og livssyklusinformasjon:
HMS Networks: INMBSMEB0200100 INMBSMEB0500100
Copyright © 2025 Intesis
Ansvarsfraskrivelse
- Informasjonen i dette dokumentet er kun til informasjonsformål. Vennligst informer HMS Networks om unøyaktigheter eller mangler i dette dokumentet. HMS Networks fraskriver seg ethvert ansvar eller ansvar for eventuelle feil som kan vises i dette dokumentet.
- HMS Networks forbeholder seg retten til å endre sine produkter i tråd med retningslinjene for kontinuerlig produktutvikling. Informasjonen i dette dokumentet skal derfor ikke tolkes som en forpliktelse fra HMS Networks side og kan endres uten varsel. HMS Networks forplikter seg ikke til å oppdatere eller holde informasjonen i dette dokumentet oppdatert.
- Dataene, eksampLes og illustrasjoner som finnes i dette dokumentet er inkludert for illustrasjonsformål og er bare ment å bidra til å forbedre forståelsen av funksjonaliteten og håndteringen av produktet. I view av det brede utvalget av mulige applikasjoner av produktet, og på grunn av de mange variablene og kravene knyttet til en bestemt implementering, kan HMS Networks ikke påta seg ansvar eller ansvar for faktisk bruk basert på dataene, f.amples eller illustrasjoner som er inkludert i dette dokumentet eller for skader som oppstår under installasjon av produktet. De som er ansvarlige for bruken av produktet må tilegne seg tilstrekkelig kunnskap for å sikre at produktet brukes riktig i den spesifikke applikasjonen, og at applikasjonen oppfyller alle ytelses- og sikkerhetskrav, inkludert gjeldende lover, forskrifter, koder og standarder. Videre påtar HMS Networks seg under ingen omstendigheter ansvar eller ansvar for eventuelle problemer som måtte oppstå som følge av bruk av udokumenterte funksjoner eller funksjonelle bivirkninger som finnes utenfor produktets dokumenterte omfang. Virkningene forårsaket av direkte eller indirekte bruk av slike aspekter ved produktet er udefinerte og kan omfatte f.eks. Kompatibilitetsproblemer og stabilitetsproblemer.
FAQ
How many Modbus client devices are supported by the gateway?
The gateway supports up to 500 Modbus client devices.
What is the maximum number of M-Bus signals that can be read from the gateway?
The gateway can read up to 50 M-Bus signals from connected meters.