Intesis-M-LOGO

Intesis M-BUS to Modbus TCP Server Gateway

Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-PRODUCT-IMAGE

Informasi Produk

Spesifikasi

  • Product Name: M-BUS to Modbus TCP Server Gateway
  • Versi Manual Pengguna: 1.0.3
  • Tanggal Publikasi: 2025-07-21

Description and Order Codes

INMBSMEBxxx0100 Protocol Translator Gateway
M-Bus to Modbus TCP server gateway

KODE PEMESANAN KODE ORDER LEGACY
INMBSMEB0200100 IBMBSMEB0200100
INMBSMEB0500100 IBMBSMEB0500100

MELIHAT
Kode pesanan dapat bervariasi tergantung pada penjual produk dan lokasi pembeli.

Kapasitas Gerbang

Elemen INMBSMEB0200100 INMBSMEB0500100 Catatan
Type of Modbus client devices ModBus TCP Those supporting the Modbus protocol. Communication over TCP/IP.
Number of Modbus client devices Up to five TCP connections Number of Modbus client devices supported by the gateway.
Number of Modbus registers 500 1250 Maximum number of points that can be defined in the virtual Modbus server device inside the gateway.
Type of M-Bus devices M-Bus EIA-485 slave devices Those supporting the M-Bus EN-1434-3 Standard. Communication over EIA-485.
Number of M-Bus slave devices 20 50 Number of M-Bus slave devices supported by the gateway.
Number of M-Bus signals 500 1250 Number of M-Bus signals (readings in the meters) that can be read from the gateway.

Informasi Umum

Tujuan Penggunaan Panduan Pengguna

  • Manual ini berisi fitur-fitur utama gateway Intesis ini dan petunjuk untuk pemasangan, konfigurasi, dan pengoperasiannya yang sesuai.
  • Any person who installs, configures, or operates this gateway or any associated equipment should be aware of this manual’s contents.
  • Simpan panduan ini untuk referensi di masa mendatang selama penginstalan, konfigurasi, dan pengoperasian.

Informasi Keselamatan Umum

PENTING
Follow these instructions carefully. Improper work may seriously harm your health and damage the gateway and/or any other equipment connected to it.

  • Only technical personnel, following these instructions and the country legislation for installing electrical equipment, can install and manipulate this gateway.
  • Pasang gateway ini di dalam ruangan, di lokasi dengan akses terbatas, hindari paparan radiasi matahari langsung, air, kelembapan relatif tinggi, atau debu.
  • Preferably, mount this gateway on a DIN rail inside a grounded metallic cabinet, following the instructions in this manual.
  • If mounting on a wall, firmly fix this gateway on a non-vibrating surface, following the instructions in this manual. Connect this gateway only to networks without routing to the outside plant.
  • All communication ports are considered for indoor use and must only be connected to SELV circuits.
  • Disconnect all systems from power before manipulating and connecting them to the gateway.
  • Gunakan NEC kelas 2 dengan peringkat SELV atau catu daya sumber daya terbatas (LPS).
    MANDATORY GROUND CONNECTION
  • YOU MUST connect the gateway to the installation ground terminal. Always use the gateway’s dedicated connector.
  • NEVER use the positive or negative gateway’s connectors to establish this connection. Not following this indication can cause ground loops and damage the gateway and/or any other equipment connected to it.
  • If the power supply includes a ground connection, that terminal must be connected to ground.
  • Use a circuit breaker between the gateway and the power supply. Rating: 250 V, 6 A.
  • Menyediakan vol yang benartage to power the gateway. The admitted range is detailed in the technical specifications table.
  • Respect the expected polarity of power and communication cables when connecting them to the gateway. Safety instructions in other languages can be found here.

Pesan dan Simbol Peringatan

  • Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (1)PERINGATAN
    Instruksi yang harus diikuti untuk menghindari situasi yang berpotensi berbahaya yang, jika tidak dihindari, dapat mengakibatkan cedera ringan atau sedang.
  • Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (2)PENTING
    Instruksi yang harus diikuti untuk menghindari risiko berkurangnya fungsionalitas dan/atau kerusakan peralatan atau untuk menghindari risiko keamanan jaringan.
  • Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (3)CATATAN
    Informasi tambahan yang dapat memfasilitasi pemasangan dan/atau pengoperasian.
  • Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (4)TIP
    Saran dan masukan yang bermanfaat.
  • Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (5)MELIHAT
    Informasi Luar Biasa.

Lebihview

  • This Intesis® gateway allows to integrate M-Bus devices into Modbus TCP systems easily.
  • The aim of this integration is to make M-Bus devices accessible from a Modbus control system or device to get the same behavior as if the M-Bus device was part of the Modbus installation.
  • For this, the Intesis gateway acts as a Modbus TCP server device in its Modbus interface, allowing it to read/write points from the Modbus client device(s). From the M-Bus point of view, the gateway acts as an M-Bus level converter and Master device (EN-1434-3). The gateway performs the readings of the M-Bus slave device(s) by automatic continuous polling or on demand (to reduce battery consumption).
  • The gateway configuration is carried out through the Intesis MAPS configuration tool.

Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (6) PENTING
This document assumes that the user is familiar with Modbus and M-Bus technologies and their technical terms.

Di Dalam Paket

BARANG YANG TERMASUK

  • Intesis INMBSMEBxxx0100 Protocol Translator Gateway
  • Panduan instalasi

Gateway Main Features

  • Embedded level converter. Direct connection to M-Bus meters with no extra hardware required.
  • Scan function: detect M-Bus meters and their available registers automatically.
  • Import/Export of M-Bus meter templates. Reduce commissioning time when adding multiple meters of the same type.
  • Baud rate configurable within the M-Bus allowed range (300 to 9600 bps. The devices are normally configured at 2400 bps).
  • Specific parameters and timeouts are available to maximize compatibility with any possible peculiarity between different meter manufacturers.
  • Availability of variables for communication errors, both at meter and general level, helping you to know if the communication with one or more meters has failed.
  • DIN rail and wall mounting case.
  • Flexible configuration using the Intesis MAPS configuration tool.

Gateway General Functionality

  • This gateway acts as a server on its Modbus side and as a master on its M-Bus interface, thus allowing the integration of M-Bus devices into a Modbus system.
  • The gateway is continuously polling the devices (together or individually), storing in its memory the current status of every signal you want to track, and serving this data to the installation when requested. This continuous polling can be activated/deactivated through a Modbus signal. It is also possible to configure the gateway to make a single polling of the meters (refresh of readings) at startup.
  • Primary or secondary addressing is allowed for M-Bus devices. When a signal status changes, the gateway sends a write telegram to the installation, waits for the response, and performs the corresponding action.
  • This action can be: force a polling of a specific M-Bus device or force a polling of all M-Bus devices. This can also be forced from the Modbus side at any time by writing a 1 in the corresponding binary point specially enabled for this purpose.

Other M-Bus information accessible from Modbus, using specific points of the gateway, is:

  • Bus activity: Indicates if meters are currently being polled or polling is on standby.
  • M-Bus status of every meter: This is sent by the own meter with every poll and indicates the internal status, which is manufacturer specific in every case.

A lack of response from a signal activates a communication error, allowing you to know which signal from which M-Bus device is not correctly working. There is also a general communication error available that will be active whenever the communication with one or more M-Bus meters has failed.

Perangkat keras

Pemasangan

  • PENTING
    Sebelum memasang, pastikan tempat pemasangan yang dipilih melindungi pintu gerbang dari radiasi matahari langsung, air, kelembapan relatif tinggi, atau debu.
  • CATATAN
    Mount the gateway on a wall or over a DIN rail. We recommend the DIN rail mounting option, preferably inside a grounded metallic industrial cabinet.
  • PENTING
    Pastikan gateway memiliki jarak yang cukup untuk semua koneksi saat dipasang. Lihat Dimensi (halaman 13).

PEMASANGAN DIN RAIL

  1. Fit the gateway’s top-side clip in the upper edge of the DIN rail.
  2. Press the low side of the gateway gently to lock it in the DIN rail.
  3. Make sure the gateway is firmly fixed.

CATATAN
For some DIN rails, to complete step 2, you may need a small screwdriver or similar to pull the bottom clip down.Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (7)

PEMASANGAN DINDING

PENTING
For reasons of security, the maximum height for wall mounting is two meters (6.5 feet).

  1. Press the rear panel clips outwards until you hear a click.
  2. Use the clip holes to screw the gateway to the wall.
    CATATAN
    Use M3 screws, 25mm (1″) length.
  3. Make sure the gateway is firmly fixed.Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (8)

Koneksi

  • PERINGATAN
    Disconnect all systems from power before manipulating and connecting them to the gateway.
  • PENTING
    Keep communication cables away from power and ground wires.
  • CATATAN
    Mount the gateway in the desired place before wiring it.

Gateway ConnectorsIntesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (9)

  1. Catu daya: 24 VDC, Max.: 220 mA, 5.2 W
  2. Pelabuhan A: M-Bus port, for M-Bus bus connection.
  3. Pelabuhan Ethernet: For Modbus TCP connection.
Port A connectors M-Bus wires
A1 +
A2

CATATAN
You can also use the Ethernet Port to connect the gateway to the PC for configuration purposes.

WIRING THE CONNECTORS

PENTING
For all connectors, use solid or stranded wires (twisted or with ferrule).

Cross-section/gauge per terminal:

  • Satu inti: 0.2 .. 2.5 mm2 / 24 .. 11 AWG
  • Dua inti: 0.2 .. 1.5 mm2 / 24 .. 15 AWG
  • Tiga inti: Tidak diizinkan

CATATAN
To know more about each port’s specifications, see Technical Specifications (page 12).

Common Connections

Connecting the Gateway to the Power SupplyIntesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (10)

The power supply connector is a green pluggable terminal block (3 poles) labeled as 24Vdc.

PENTING

  • Use a SELV-rated NEC class 2 or limited power source (LPS) power supply.
  • Connect the gateway’s ground terminal to the installation grounding.
  • Koneksi yang salah dapat menyebabkan loop bumi yang dapat merusak gateway Intesis dan/atau peralatan sistem lainnya.

Terapkan volumetage within the admitted range and of enough power:
24 VDC, Max.: 220 mA, 5.2 W

PENTING
Respect the polarity labeled on the power connector for the positive and negative wires.

Connection Procedure for M-Bus

  • The gateway connects directly to the M-Bus system without requiring any external RS-232 or EIA-485 to M-Bus level converter.
  • Connect the M-Bus bus to connectors A1 (+) and A2 (-) of the gateway’s Port A. Respect the polarity.
  • Remember that the gateway provides 36 VDC M-Bus voltage to the bus, acting also as an M-Bus level converter.
  • If no response from the M-Bus device(s) to the frames sent by the gateway is received, check that they are operative and reachable from the network connection used by the gateway.

Connection Procedure for Modbus TCP

CATATAN
Remember to check the Common Connections (page 10).

Connect the Modbus TCP Ethernet cable to the gateway’s Ethernet Port.

  • PENTING
    Gunakan kabel Ethernet UTP/FTP CAT5 lurus atau lebih tinggi.
  • PENTING
    When commissioning the gateway for the first time, DHCP will be enabled for 30 seconds. After that time, the default IP address 192.168.100.246 will be set.
  • CATATAN
    Port default adalah 502.
  • PENTING
    Jika berkomunikasi melalui LAN gedung, hubungi administrator jaringan dan pastikan lalu lintas pada port yang digunakan diperbolehkan melalui semua jalur LAN.

Spesifikasi Teknis

 Perumahan Plastic, type PC (UL 94 V-0). Color: Light Grey. RAL 7035Net dimensions (HxWxD): 93 x 53 x 58 mm / 3.6 x 2.1 x 2.3″
 Pemasangan WallDIN rail (recommended mounting) EN60715 TH35
   Terminal pemasangan kabel For power supply and low-voltagesinyal
  • Per terminal: solid wires or stranded wires (twisted or with ferrule) Wire cross-section/gauge:
  • Satu inti: 0.2 mm2 ..2.5mm2 (24 .. 11 AWG)
  • Dua inti: 0.2 mm2 ..1.5mm2 (24 .. 15 AWG) Three cores: Not permitted

For distances longer than 3.05 meters (10 feet), use Class 2 cables.

  Kekuatan
  • 1 x Green pluggable terminal block (3 poles)
  •  24 VDC, Max.: 220 mA, 5.2 W
  • Recommended: 24 VDC, 220 mA
Eternet 1xEthernet 10/100 Mbps RJ45
     Pelabuhan A 1 lembar M-Bus port: pluggable terminal block (two poles) M-Bus power consumption:
  • Normal operating level: 90 mA (50 M-Bus unit loads + 20%)
  • Deteksi tabrakan: 25mA
  • Overload level: 215mA

Jil.tagperingkat: Tegangan 36 VDC

 Indikator LED
  • 2 x indikator LED Onboard
  • Tautan / Kecepatan Ethernet
Operasional suhu Celsius: 0 .. 60°C / Fahrenheit: 32 .. 140°F
Operasional kelembaban 5 hingga 95%, tanpa kondensasi
Perlindungan IP20 (IEC60529)

Ukuran

Dimensi bersih (T x L x D)

  • Milimeter: Ukuran 93x53x58 mm
  • Inci: 3.6x2.1x2.3 inci

Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (11) PENTING
Ensure the gateway has sufficient clearance for all connections when mounted.

M-Bus System

Deskripsi Umum
The M-Bus (“Meter-Bus”) is a European standard for remote reading of heat meters, and it is also usable for all other types of consumption meters, as well as for various sensors and actuators.

M-Bus standards are:

  • EN 13757-2 (physical and link layer – Wired M-Bus)
  • EN 13757-3 (application layer)

Many manufacturers of energy meters, pulse counters, water meters, electricity meters, etc., add an M-Bus interface to their devices, enabling them to be interconnected and remotely monitored through a 2-wire bus based on the M-Bus standards. There are many manufacturers of these measurement devices incorporating the M-Bus interface, and also some other manufacturers of specific M-Bus communication devices such as bus repeaters, EIA-232/EIA-485 to M-Bus level converters, etc.

M-Bus Interface

  • The gateway connects directly to the M-Bus system. No external level converter is required.
  • Connection to the M-Bus is made via the EIA-485 connection. Notice that the gateway also powers the bus, so no extra hardware is required to connect to M-Bus compatible meters or devices.

M-Bus Signals
The gateway supports several meter magnitudes and units typically used on energy, electricity, water, and other meters. This information is required to add the desired signals when integrating meters manually, as this process is done through the Intesis MAPS configuration tool by setting the meters up and then adding the signals each meter uses and assigning them accordingly in the Signals tab (page 20).

MELIHAT

  • The type of signals available from each meter may differ depending on the manufacturer and model, so please refer to the device’s technical documentation to determine the signals available for a given meter when adding meters manually.
  • However, Intesis MAPS also offers a much quicker and simpler alternative method for meter detection in the form of a scanning function. This scan detects all meters available on the bus and their signals and imports each signal with the units and details each meter provides. These signals can then be matched with the corresponding Modbus registers in the Signals tab for integration with the BMS.

Modbus System

Deskripsi Umum

  • The Modbus protocol is an application-layer messaging protocol developed by Modicon in 1979. It is used to establish client-server communication between intelligent devices over different types of buses or networks. The Intesis gateway supports Modbus TCP.
  • Modbus is a request/reply protocol and offers services specified by function codes. Modbus function codes are elements of Modbus request/reply PDUs (Protocol Data Units).

ModBus Interface
The Intesis gateway acts as a server device in its Modbus interface; the interface for this model is the Ethernet port. To access the points and resources of the gateway from a Modbus client device, you must specify the Modbus register addresses configured inside the gateway as those configured inside the gateway corresponding to the signals of the field device protocol.

Fungsi yang Didukung

Tabel 1. Fungsi Modbus

# Fungsi Baca/Tulis
01 Baca Gulungan R
02 Baca Input Diskrit R
03 Baca Holding Register R
04 Membaca Register Input R
05 Tulis Kumparan Tunggal W
06 Tulis Register Tunggal W
15 Tulis Beberapa Kumparan W
16 Tulis Beberapa Register W
  • Jika catatan polling digunakan untuk membaca atau menulis lebih dari satu register, rentang alamat yang diminta harus berisi alamat yang valid; jika tidak, gateway Intesis akan mengembalikan kode kesalahan Modbus yang sesuai.
  • All registers are of 2 bytes (16 bits)1, even if they are associated with signals of bit type on the other protocol’s side. Its content is expressed in MSB .. LSB.2
  • Kode kesalahan Modbus didukung sepenuhnya. Mereka dikirim setiap kali diperlukan tindakan atau alamat Modbus yang tidak valid.

ModBus TCP

  • Komunikasi Modbus TCP pada dasarnya ditandai dengan penyematan protokol Modbus RTU ke dalam bingkai TCP/IP, yang memungkinkan komunikasi lebih cepat dan jarak yang lebih jauh antara perangkat klien dan server dibandingkan dengan komunikasi RTU melalui jalur serial. Manfaat lainnya adalah menggunakan infrastruktur TCP/IP umum di gedung dan mentransmisikan melalui WAN atau internet. Ini juga memungkinkan koeksistensi satu atau lebih klien dan, tentu saja, satu atau lebih perangkat server dalam jaringan tertentu, semuanya saling terhubung melalui jaringan berbasis TCP/IP.
  • Gunakan alat konfigurasi untuk mengonfigurasi pengaturan IP gateway (status DHCP, IP sendiri, netmask, dan gateway default) dan port TCP.
  1. Default value. The measurement-related registers can be configured to be 4 or 8 bytes (32 or 64 bits) in Intesis MAPS if required.
  2. MSB: most significant bit; LSB: least significant bit

Peta Alamat
The Modbus address map is fully configurable; any point in the gateway can be freely configured with the desired Modbus register address.

Definisi Poin Antarmuka Server Modbus

  • The Modbus registers are fully configurable through the Intesis MAPS configuration tool; any point in the gateway can be freely configured with the desired Modbus register address.
  • Setiap titik yang ditentukan di gateway memiliki fitur Modbus berikut yang terkait dengannya:
Fitur Keterangan
#Bit
  • 1-sedikit
  • 16-sedikit
  • 32-sedikit
Data Pengkodean Format
  • 16/32 unsigned
  • 16/32-bit signed (one’s complement – C1)
  • 16/32-bit signed (two’s complement – C2)
  • 16/32-bit Float
  • 16/32-bit Bitfields
  • Error comm.
Fungsi Kode
  • 1 – Read coils.
  • 2 – Read discrete inputs.
  • 3 – Read holding registers.
  • 4 – Read input registers.
  • 5 – Write a single coil.
  • 6 – Write a single register.
  • 15 – Write multiple coils.
  • 16 – Write multiple registers.
Urutan Byte
  • Endian Besar
  • Endian Kecil
  • Kata Terbalik Big Endian
  • Word Inverted Little Endian
Daftar Alamat Alamat register Modbus di dalam perangkat server untuk titik tersebut.
Sedikit di dalam register Bit inside the Modbus register (optional). The Intesis gateway allows bit decoding from generic 16 bits input/holding Modbus registers.Some devices use the bit coding into 16 bits input/holding Modbus registers to encode digital values. These registers are generally accessible using Modbus function codes 03 and 04 (read holding/input registers).
Baca/Tulis
  • 0: Baca
  • 1: Pemicu
  • 2: Read/Write

Setup Process with the Configuration Tool

Prasyarat
Untuk integrasi ini, Anda memerlukan:

  • Barang yang dikirim oleh HMS Networks:
    • The Intesis INMBSMEBxxx0100 Protocol Translator Gateway.
    • Tautan untuk mengunduh alat konfigurasi.
    • Dokumentasi produk.
  • The respective M-Bus devices connected to the Port A of the gateway.
  • A computer to run the Intesis MAPS configuration tool. Requirements:
    • Windows® 7 or higher.
    • Hard disk free space: 1 GB.
    • RAM: 4GB.
  • An Ethernet cable.

Intesis MAPS Configuration and Monitoring Tool

Perkenalan

  • Intesis MAPS is a software tool for the configuration and monitoring of the Intesis gateways. It has been designed and developed in-house, ensuring an up-to-date tool to get all the potential of our gateways. It is compatible with Windows® 7 and higher.
  • The installation procedure and the main functions are explained in the Intesis MAPS user manual. Please also check the Intesis MAPS user manual for specific information about the different parameters and how to configure them.

Create a New Project from a Template

  1. Open Intesis MAPS.
  2. Click Create New Project in the Start menu on the left.
    You can create a project from scratch using a template. To find the appropriate template, filter the search by:
    • Clicking on the protocol logos.
    • Typing the order code in the Order Code field.|
      CATATAN
    • The order code is printed on the silver label placed on the gateway’s right side.
    • Looking for the Project Name on the list: IN-MBSTCP-MBUS.Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (12)
  3. Select the desired template.
  4. Click Next or double-click the template on the list.

CATATAN
Templates are just a starting point for your integration. Depending on the type of integration, you may have to modify some parameters.

PENTING
Don’t forget to save your project on your computer before exiting Intesis MAPS. To do so, go to Project → Save or Save As. Later on, you can load the project to Intesis MAPS and continue with the configuration.

Menu Utama SelesaiviewIntesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (13)

Bagian berikut memberikan overview of the five tabs that compose the Intesis MAPS main menu. Through these options, you will establish a connection between the gateway and the computer, set up your project through the Configuration and Signals tabs, send it to the gateway, and monitor that everything works fine using the Diagnostic tab.

TIP

Tooltip: Hover the cursor over a field, and a message will appear indicating the purpose of the parameter.Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (14)

Tab Koneksi
Click the Connection button in the menu bar to configure the gateway connection parameters.Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (15)

Tab Konfigurasi
Select the Configuration tab to configure the connection parameters. This window contains three subsets of information: General (gateway general parameters), Modbus server (Modbus interface configuration), and M-Bus (M-Bus interface parameters).
Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (16)

Tab Sinyal
All available objects, object instances, their corresponding Modbus register, and other main parameters are listed in the Signals tab. More information on each parameter and how to configure it can be found in the Intesis MAPS user manual.
Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (17)

Tab Terima/Kirim

Mengirim:
Once you have finished setting the parameters, you have to send the configuration to the gateway:

Ikuti langkah-langkah berikut:

  1. Klik tombol Kirim.
    • If the gateway is still factory-set, you will be prompted to save the project on your PC. Once saved, the configuration is automatically sent to the gateway.
    • If you have already saved the project, the configuration is automatically sent to the gateway.
  2. Hubungkan kembali dengan gateway setelah mengirim file.Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (18)

MELIHAT
Gateway akan reboot secara otomatis setelah konfigurasi baru dimuat. Proses ini mungkin memakan waktu beberapa detik.

Menerima:

  • Gunakan fungsi ini untuk mendapatkan konfigurasi gateway, misalnyaample, ketika Anda perlu mengubah beberapa parameter gateway yang sudah dipasang di instalasi.
  • Setelah konfigurasi selesai dan dikirim, gateway sudah beroperasi. Meski begitu, Anda harus memeriksa apakah semuanya berfungsi dengan benar dengan masuk ke tab Diagnostik.

Tab Diagnostik

PENTING
Koneksi dengan gateway diperlukan untuk menggunakan alat diagnostik.

Gambar 6. Jendela tab diagnostik. Temukan Kotak Alat di antara bilah tab atas dan Konsol view. Di bawahnya, dari kiri ke kanan: Konsol vieweh, Protokol viewers (satu di atas yang lain), dan Sinyal viewerIntesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (19)

Bagian ini memiliki dua bagian utama:

Kotak AlatIntesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (20)

Gunakan bagian alat untuk:

  • Periksa status perangkat keras gateway saat ini.
  • Simpan log komunikasi ke ZIP file untuk tujuan diagnostik.
  • Dapatkan informasi tentang gateway.
  • Setel ulang gerbang.

Vieworang asing
Intesis MAPS menyediakan beberapa viewpengguna:

  • Konsol generik viewer untuk informasi umum tentang komunikasi dan status gateway.
  • A viewer bagi kedua protokol untuk memeriksa statusnya saat ini.
  • Sebuah sinyal viewer to simulate the BMS behavior or check the system’s current values.
    The layout of these viewers can be modified:
  • Using the Select Diagnostics View pilihan dari View Tidak bisa:Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (21)

CATATAN
Layouts 3 and 4 offer two different tabbed options:

  • Fixed console to the left and tabbed browser for the other vieworang asing
  • Full tabbed browser
  • Clicking and dragging the border of a viewer. To do so, place the cursor over Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (22)the edge of a viewer. On the vertical edges, the cursor changes to to adjust the width, and on the horizontal edges, the cursor changes to  Intesis-M-BUS-to-Modbus-TCP-Server-Gateway-IMAGE (22) to adjust the height.

Elektronik Mouser

Distributor resmi
Klik untuk View Informasi Harga, Inventaris, Pengiriman & Siklus Hidup:

HMS Networks: INMBSMEB0200100  INMBSMEB0500100

Hak Cipta © 2025 Intesis

Penafian

  • Informasi dalam dokumen ini hanya untuk tujuan informasi. Harap informasikan kepada HMS Networks jika ada ketidakakuratan atau kelalaian yang ditemukan dalam dokumen ini. HMS Networks melepaskan tanggung jawab atau kewajiban apa pun atas kesalahan apa pun yang mungkin muncul dalam dokumen ini.
  • HMS Networks berhak untuk memodifikasi produknya sesuai dengan kebijakan pengembangan produk yang berkelanjutan. Oleh karena itu, informasi dalam dokumen ini tidak boleh ditafsirkan sebagai komitmen dari pihak HMS Networks dan dapat berubah tanpa pemberitahuan. HMS Networks tidak membuat komitmen untuk memperbarui atau menjaga informasi terkini dalam dokumen ini.
  • Data, misalampfile dan ilustrasi yang ditemukan dalam dokumen ini disertakan untuk tujuan ilustrasi dan hanya dimaksudkan untuk membantu meningkatkan pemahaman tentang fungsionalitas dan penanganan produk. Di dalam view dari berbagai kemungkinan aplikasi produk, dan karena banyak variabel dan persyaratan yang terkait dengan implementasi tertentu, HMS Networks tidak dapat memikul tanggung jawab atau kewajiban untuk penggunaan aktual berdasarkan data, mis.ample atau ilustrasi yang disertakan dalam dokumen ini atau untuk kerusakan apa pun yang terjadi selama pemasangan produk. Mereka yang bertanggung jawab atas penggunaan produk harus memperoleh pengetahuan yang cukup untuk memastikan bahwa produk tersebut digunakan dengan benar dalam aplikasi khusus mereka dan bahwa aplikasi tersebut memenuhi semua persyaratan kinerja dan keselamatan termasuk undang-undang, peraturan, kode, dan standar yang berlaku. Lebih lanjut, HMS Networks dalam keadaan apa pun tidak akan bertanggung jawab atau bertanggung jawab atas masalah apa pun yang mungkin timbul sebagai akibat dari penggunaan fitur tidak berdokumen atau efek samping fungsional yang ditemukan di luar cakupan produk yang didokumentasikan. Efek yang disebabkan oleh penggunaan langsung atau tidak langsung dari aspek produk tersebut tidak terdefinisi dan mungkin termasuk misalnya masalah kompatibilitas dan masalah stabilitas.

Tanya Jawab Umum

How many Modbus client devices are supported by the gateway?

The gateway supports up to 500 Modbus client devices.

What is the maximum number of M-Bus signals that can be read from the gateway?

The gateway can read up to 50 M-Bus signals from connected meters.

Dokumen / Sumber Daya

Intesis M-BUS to Modbus TCP Server Gateway [Bahasa Indonesia:] Panduan Pengguna
v1, Version 1.0.3, M-BUS to Modbus TCP Server Gateway, M-BUS, Modbus TCP Server Gateway, TCP Server Gateway, Server Gateway, Gateway

Referensi