Danfoss-logo

Danfoss MCD 202 EtherNet-IP Module

Danfoss-MCD-202-EtherNet-IP-Module-product-image

Product Information

Specifications
The EtherNet/IP Module is designed for use with 24 V AC/V DC and 110/240 V AC control voltage. It is not suitable for use with the MCD 201/MCD 202 compact starters using 380/440 V AC control voltage. The module allows a Danfoss soft starter to connect to an Ethernet network for control and monitoring.

Introduction

Purpose of the Manual
This installation guide provides information for the installation of the EtherNet/IP option module for VLT® Compact Starter MCD 201/MCD 202 and VLT® Soft Starter MCD 500. The installation guide is intended for use by qualified personnel.

Users are assumed to be familiar with:

  • VLT® soft starters.
  • EtherNet/IP technology.
  • PC or PLC that is used as a master in the system.

Read the instructions before installation and ensure that the instructions for safe installation are observed.

  • VLT® is a registered trademark.
  • EtherNet/IP™ is a trademark of ODVA, Inc.

Additional Resources
Resources available for the soft starter and optional equipment:

  • The VLT® Compact Starter MCD 200 Operating Instructions provide the necessary information for getting the soft starter up and running.
  • The VLT® Soft Starter MCD 500 Operating Guide provides the necessary information for getting the soft starter up and running.

Supplementary publications and manuals are available from Danfoss. See drives.danfoss.com/knowledge-center/technical-documentation/ for listings.

Product Overview

Intended Use
This installation guide relates to EtherNet/IP Module for VLT® soft starters.
The EtherNet/IP interface is designed to communicate with any system complying with the CIP EtherNet/IP standard. EtherNet/IP provides users with the network tools to deploy standard Ethernet technology for manufacturing applications while enabling internet and enterprise connectivity.

EtherNet/IP Module is intended for use with:

  • VLT® Compact Starter MCD 201/MCD 202, 24 V AC/V DC and 110/240 V AC control voltage.
  • VLT® Soft Starter MCD 500, all models.

NOTICE

  • The EtherNet/IP Module is NOT suitable for use with the MCD 201/MCD 202 compact starters using 380/440 V AC control voltage.
  • The EtherNet/IP Module allows a Danfoss soft starter to connect to an Ethernet network and be controlled or monitored using an Ethernet communication model.
  • Separate modules are available for PROFINET, Modbus TCP, and EtherNet/IP networks.
  • The EtherNet/IP Module operates at the application layer. Lower levels are transparent to the user.
  • Familiarity with Ethernet protocols and networks is required to operate the EtherNet/IP Module successfully. If there are difficulties when using this device with third-party products, including PLCs, scanners, and commissioning tools, contact the relevant supplier.

Approvals and Certifications

Danfoss-MCD-202-EtherNet-IP-Module-image (1)

More approvals and certifications are available. For more information, contact a local Danfoss partner.

Disposal
Do not dispose of equipment containing electrical components together with domestic waste.
Collect it separately in accordance with local and currently valid legislation.

Symbols, Abbreviations, and Conventions

Abbreviation Definition
CIP™ Common industrial protocol
DHCP Dynamic host configuration protocol
EMC Electromagnetic compatibility
IP Internet protocol
LCP Local control panel
LED Light-emitting diode
PC Personal computer
PLC Programmable logic controller

Table 1.1 Symbols and Abbreviations

Conventions
Numbered lists indicate procedures.
Bullet lists indicate other information and description of illustrations.

Italicized text indicates:

  • Cross-reference.
  • Link.
  • Parameter name.
  • Parameter group name.
  • Parameter option.

Safety

The following symbols are used in this manual:

WARNING
Indicates a potentially hazardous situation that could result in death or serious injury.

CAUTION
Indicates a potentially hazardous situation that could result in minor or moderate injury. It can also be used to alert against unsafe practices.

NOTICE
Indicates important information, including situations that can result in damage to equipment or property.

Qualified Personnel
Correct and reliable transport, storage, installation, operation, and maintenance are required for the trouble-free and safe operation of the soft starter. Only qualified personnel are allowed to install or operate this equipment.
Qualified personnel are defined as trained staff, who are authorized to install, commission, and maintain equipment, systems, and circuits in accordance with pertinent laws and regulations. Also, the qualified personnel must be familiar with the instructions and safety measures described in this installation guide.

General Warnings

WARNING

ELECTRICAL SHOCK HAZARD
VLT® Soft Starter MCD 500 contains dangerous voltages when connected to mains voltage. Only a qualified electrician should carry out the electrical installation. Improper installation of the motor or the soft starter can cause death, serious injury, or equipment failure. Follow the guidelines in this manual and local electrical safety codes.

Models MCD5-0360C ~ MCD5-1600C:
Treat the busbar and heat sink as live parts whenever the unit has mains voltage connected (including when the soft starter is tripped or waiting for a command).

WARNING

PROPER GROUNDING

  • Disconnect the soft starter from mains voltage before carrying out repair work.
  • It is the responsibility of the person installing the soft starter to provide proper grounding and branch circuit protection according to local electrical safety codes.
  • Do not connect power factor correction capacitors to the output of the VLT® Soft Starter MCD 500. If static power factor correction is employed, it must be connected to the supply side of the soft starter.

WARNING

IMMEDIATE START
In auto-on mode, the motor can be controlled remotely (via remote inputs) while the soft starter is connected to mains.

MCD5-0021B ~ MCD5-961B:
Transportation, mechanical shock, or rough handling may cause the bypass contactor to latch into the On state.

To prevent the motor from starting immediately on first commissioning or operation after transportation:

  • Always ensure that the control supply is applied before the power.
  • Applying control supply before power ensures that the contactor state is initialized.

WARNING

UNINTENDED START
When the soft starter is connected to AC mains, DC supply, or load sharing, the motor can start at any time. Unintended start during programming, service, or repair work can result in death, serious injury, or property damage. The motor can start with an external switch, a fieldbus command, an input reference signal from the LCP or LOP, via remote operation using MCT 10 Set-up Software, or after a cleared fault condition.

To prevent unintended motor start:

  • Press [Off/Reset] on the LCP before programming parameters.
  • Disconnect the soft starter from the mains.
  • Completely wire and assemble the soft starter, motor, and any driven equipment before connecting the soft starter to AC mains, DC supply, or load sharing.

WARNING

SAFETY OF PERSONNEL
The soft starter is not a safety device and does not provide electrical isolation or disconnection from the supply.

  • If isolation is required, the soft starter must be installed with a main contactor.
  • Do not rely on the start and stop functions for safety of personnel. Faults occurring in the mains supply, the motor connection, or the electronics of the soft starter can cause unintended motor starts or stops.
  • If faults occur in the electronics of the soft starter, a stopped motor may start. A temporary fault in the supply mains or loss of motor connection can also cause a stopped motor to start.

To provide safety of personnel and equipment, control the isolation device through an external safety system.

NOTICE
Before changing any parameter settings, save the current parameter to a file using MCD PC Software or the Save User Set function.

NOTICE
Use the Autostart feature with caution. Read all the notes related to Autostart before operation.
The examples and diagrams in this manual are included solely for illustrative purposes. The information contained in this manual is subject to change at any time and without prior notice. Responsibility or liability is never accepted for direct, indirect, or consequential damage resulting from the use or application of this equipment.

Installation

Installation Procedure

CAUTION

EQUIPMENT DAMAGE
If mains and control voltage are applied when installing or removing options/accessories, it may damage the equipment.

To avoid damage:
Remove mains and control voltage from the soft starter before attaching or removing options/accessories.

Installing the EtherNet/IP option:

  1. Remove control power and mains supply from the soft starter.
  2. Fully pull out the top and bottom retaining clips on the module (A).
  3. Line up the module with the communication port slot (B).
  4. Push in the top and bottom retaining clips to secure the module to the soft starter (C).
  5. Connect Ethernet port 1 or port 2 on the module to the network.
  6. Apply control power to the soft starter.

Danfoss-MCD-202-EtherNet-IP-Module-image (2)

Remove the module from the soft starter:

  1. Remove control power and mains supply from the soft starter.
  2. Disconnect all external wiring from the module.
  3. Fully pull out the top and bottom retaining clips on the module (A).
  4. Pull the module away from the soft starter.

Danfoss-MCD-202-EtherNet-IP-Module-image (3)

Connection

Soft Starter Connection
The EtherNet/IP Module is powered from the soft starter.

VLT® Compact Starter MCD 201/MCD 202
For the EtherNet/IP Module to accept fieldbus commands, fit a link across terminals A1–N2 on the soft starter.

VLT® Soft Starter MCD 500
If the MCD 500 has to be operated in remote mode, input links are required across terminals 17 and 25 to terminal 18. In hand-on mode, links are not required.

NOTICE

FOR MCD 500 ONLY
Control via the fieldbus communication network is always enabled in local control mode and can be enabled or disabled in remote control mode (parameter 3-2 Comms in Remote). See the VLT® Soft Starter MCD 500 Operating Guide for parameter details.

EtherNet/IP Module Connections

MCD 201/202 MCD 500
Danfoss-MCD-202-EtherNet-IP-Module-image (4) Danfoss-MCD-202-EtherNet-IP-Module-image (5)
17
A1  18
N2
25
 2   2
 3  3
1 A1, N2: Stop input 1 (Auto-on mode) 17, 18: Stop input25, 18: Reset input
2 EtherNet/IP Module 2 EtherNet/IP Module
3 RJ45 Ethernet ports 3 RJ45 Ethernet ports

Table 4.1 Connection Diagrams

Network Connection

Ethernet Ports
The EtherNet/IP Module has 2 Ethernet ports. If only 1 connection is required, either port can be used.

Cables
Suitable cables for EtherNet/IP Module connection:

  • Category 5
  • Category 5e
  • Category 6
  • Category 6e

EMC Precautions
To minimize electromagnetic interference, Ethernet cables should be separated from motor and mains cables by 200 mm (7.9 in).
The Ethernet cable must cross the motor and mains cables at an angle of 90°.Danfoss-MCD-202-EtherNet-IP-Module-image (6)

1 3-phase supply
2 Ethernet cable

Illustration 4.1 Correct Running of Ethernet Cables

Network Establishment
The controller must establish communication directly with each device before the device can participate in the network.

Addressing
Each device in a network is addressed using a MAC address and an IP address and can be assigned a symbolic name associated with the MAC address.

  • The module receives a dynamic IP address when it is connected to the network or can be assigned a static IP address during configuration.
  • The symbolic name is optional and must be configured within the device.
  • The MAC address is fixed within the device and is printed on a label on the front of the module.

Danfoss-MCD-202-EtherNet-IP-Module-image (7)

Device Configuration

On-board Web Server
Ethernet attributes can be configured directly in the EtherNet/IP Module using the on-board web server.

NOTICE
The Error LED flashes whenever the module receives power but is not connected to a network. The Error LED flashes throughout the configuration process.

NOTICE
The default address for a new EtherNet/IP Module is 192.168.0.2. The default subnet mask is 255.255.255.0. The web server only accepts connections from within the same subnet domain. Use the Ethernet Device Configuration Tool to temporarily change the network address of the module to match the network address of the PC running the tool, if required.

To configure the device using the on-board web server:

  1. Attach the module to a soft starter.
  2. Connect Ethernet port 1 or port 2 on the module to the network.
  3. Apply control power to the soft starter.
  4. Start a browser on the PC and enter the device address, followed by /ipconfig. The default address for a new EtherNet/IP Module is 192.168.0.2.Danfoss-MCD-202-EtherNet-IP-Module-image (8)
  5. Edit the settings as required.
  6. Click Submit to save the new settings.
    • To store the settings permanently in the module, tick Set permanently.
  7. If prompted, enter username and password.
    • Username: Danfoss
    • Password: Danfoss

NOTICE
If an IP address is changed and its record is lost, use the Ethernet Device Configuration Tool to scan the network and identify the module.

NOTICE
If changing the subnet mask, the server is unable to communicate with the module after the new settings are saved.

Ethernet Device Configuration Tool
Download the Ethernet Device Configuration Tool from www.danfoss.com/drives.
Changes made via the Ethernet Device Configuration Tool cannot be stored permanently in the EtherNet/IP Module. To configure attributes permanently in the EtherNet/IP Module, use the on-board web server.

Configuring the device using the Ethernet Device Configuration Tool:

  1. Attach the module to a soft starter.
  2. Connect Ethernet port 1 or port 2 on the module to the Ethernet port of the PC.
  3. Apply control power to the soft starter.
  4. Start the Ethernet Device Configuration Tool.Danfoss-MCD-202-EtherNet-IP-Module-image (9)
  5. Click Search Devices.
    • The software searches for connected devices.Danfoss-MCD-202-EtherNet-IP-Module-image (19)
  6. To set a static IP address, click Configure and Danfoss-MCD-202-EtherNet-IP-Module-image (11)

Operation

The EtherNet/IP Module is designed for use in a system complying with the ODVA Common Industrial Protocol. For successful operation, the scanner must also support all functions and interfaces described in this manual.

Device Classification
The EtherNet/IP Module is an Adapter class device and must be managed by a Scanner class device over Ethernet.

Scanner Configuration

EDS File
Download the EDS file from drives.danfoss.com/services/pc-tools. The EDS file contains all required attributes of the EtherNet/IP Module.
Once the EDS file is loaded, define the individual EtherNet/IP Module. Input/output registers must be 240 bytes in size and type INT.Danfoss-MCD-202-EtherNet-IP-Module-image (12)

LEDs

Danfoss-MCD-202-EtherNet-IP-Module-image (13) LED name LED status Description
Power Off The module is not powered up.
On The module receives power.
Error Off The module is not powered up or does not have an IP address.
Flashing Connection timeout.
On Duplicate IP address.
Status Off The module is not powered up or does not have an IP address.
Flashing The module has obtained an IP address but has not established any network connections.
On Communication has been established.
Link x Off No network connection.
On Connected to a network.
TX/RX x Flashing Transmitting or receiving data.

Table 6.1 Feedback LEDs

Packet Structures

NOTICE
All references to registers refer to the registers within the module unless otherwise stated.

NOTICE
Some soft starters do not support all functions.

Ensuring Safe and Successful Control
Data written to the Ethernet Module remains in its registers until the data is overwritten or the module is reinitialized. The Ethernet Module does not transfer successive duplicate commands to the soft starter.

Control Commands (Write Only)

NOTICE
To operate reliably, only 1 bit in byte 0 may be set at a time. Set all other bits to 0.

NOTICE
If the soft starter is started via fieldbus communications but stopped via the LCP or a remote input, an identical start command cannot be used to restart the soft starter.
To operate safely and successfully in an environment where the soft starter may also be controlled via the LCP or the remote inputs (and fieldbus communications), a control command should be immediately followed by a status query to confirm that the command has been actioned.

Byte Bit Function
    0 0 0 = Stop command.
1 = Start command.
1 0 = Enable start or stop command.
1 = Quick stop (coast to stop) and disable start command.
2 0 = Enable start or stop command.
1 = Reset command and disable start command.
3–7 Reserved.
  1   0–1 0 = Use soft starter remote input to select motor set.
1 = Use primary motor when starting.1)
2 = Use secondary motor when starting.1)
3 = Reserved.
2–7 Reserved.

Table 7.1 Structures Used for Sending Control Commands to the Soft Starter

Ensure that the programmable input is not set to Motor set select before using this function.

Status Commands (Read Only)

NOTICE
Some soft starters do not support all functions.

Byte Bit Function Details
0 0 Trip 1 = Tripped.
1 Warning 1 = Warning.
2 Running 0 = Unknown, not ready, ready to start, or tripped.
1 = Starting, running, stopping, or jogging.
3 Reserved
4 Ready 0 = Start or stop command not acceptable.
1 = Start or stop command acceptable.
5 Control from net 1 = Always, except in program mode.
6 Local/Remote 0 = Local control.
1 = Remote control.
7 At reference 1 = Running (full voltage at the motor).
1 0–7 Status 0 = Unknown (menu open).
2 = Soft starter not ready (restart delay or thermal delay).
3 = Ready to start (including warning state).
4 = Starting or running.
5 = Soft stopping.
7 = Trip.
8 = Jog forward.
9 = Jog reverse.
2–3 0–15 Trip/warning code See trip codes in Table 7.4.
41) 0–7 Motor current (low byte) Current (A).
51) 0–7 Motor current (high byte)
6 0–7 Motor 1 temperature Motor 1 thermal model (%).
7 0–7 Motor 2 temperature Motor 2 thermal model (%).
 

8–9

0–5 Reserved
6–8 Product parameter list version
9–15 Product type code2)
10 0–7 Reserved
11 0–7 Reserved
123) 0–7 Changed parameter number 0 = No parameters have changed.
1~255 = Index number of the last parameter changed.
13 0–7 Parameters Total numbers of parameters available in the soft starter.
14–15 0–13 Changed parameter value3) Value of the last parameter that was changed, as indicated in byte 12.
14–15 Reserved
Byte Bit Function Details
         16       0–4       Soft starter state 0 = Reserved.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check).
6 = Tripped.
7 = Programming mode.
8 = Jog forward.
9 = Jog reverse.
5 Warning 1 = Warning.
6 Initialized 0 = Uninitialized.
1 = Initialized.
7 Local control 0 = Local control.
1 = Remote control.
  17 0 Parameters 0 = Parameters have changed since last parameter read.
1 = No parameters have changed.
1 Phase sequence 0 = Negative phase sequence.
1 = Positive phase sequence.
2–7 Trip code4) See trip codes in Table 7.4.
18–19 0–13 Current Average rms current across all 3 phases.
14–15 Reserved
20–21 0–13 Current (% motor FLC)
14–15 Reserved
22 0–7 Motor 1 thermal model (%)
23 0–7 Motor 2 thermal model (%)
 24–255) 0–11 Power
12–13 Power scale
14–15 Reserved
26 0–7 % power factor 100% = power factor of 1.
27 0–7 Reserved
28 0–7 Reserved
29 0–7 Reserved
30–31 0–13 Phase 1 current (rms)
14–15 Reserved
32–33 0–13 Phase 2 current (rms)
14–15 Reserved
34–35 0–13 Phase 3 current (rms)
14–15 Reserved
36 0–7 Reserved
37 0–7 Reserved
38 0–7 Reserved
39 0–7 Reserved
40 0–7 Reserved
41 0–7 Reserved
42 0–7 Parameter list minor revision
43 0–7 Parameter list major revision
   44 0–3 Digital input state For all inputs, 0 = open, 1 = closed.
0 = Start.
1 = Stop.
2 = Reset.
3 = Input A
4–7 Reserved
Byte Bit Function Details
45 0–7 Reserved

Table 7.2 Structures Used for Querying the Status of the Soft Starter

  1. For models MCD5-0053B and smaller, this value is 10 times greater than the value shown on the LCP.
  2. Product type code: 4=MCD 200, 5=MCD 500.
  3. Reading bytes 14–15 (changed parameter value) reset byte 12 (changed parameter number) and bit 0 of byte 17 (parameters have changed).
    Always read bytes 12 and 17 before reading bytes 14–15.
  4. Bits 2–7 of byte 17 report the soft starter’s trip or warning code. If the value of bits 0–4 of byte 16 is 6, the soft starter has tripped. If bit 5=1, a warning has activated and the soft starter continues operation.
  5. Power scale functions as follows:
    • 0 = Multiply power by 10 to get W.
    • 1 = Multiply power by 100 to get W.
    • 2 = Power is shown in kW.
    • 3 = Multiply power by 10 to get kW.

Soft Starter Internal Register Address
Internal registers within the soft starter have the functions listed in Table 7.3. These registers are not directly accessible via fieldbus.

Register Description Bits Details
0 Version 0–5 Binary protocol version number.
6–8 Product parameter list version.
9–15 Product type code.1)
1 Device details
22) Changed parameter number 0–7 0 = No parameters have changed.
1~255 = Index number of the last parameter changed.
8–15 Total number of parameters available in the soft starter.
32) Changed parameter value 0–13 Value of the last parameter that was changed, as indicated in register 2.
14–15 Reserved.
4 Soft starter state 0–4 0 = Reserved.
1 = Ready.
2 = Starting.
3 = Running.
4 = Stopping.
5 = Not ready (restart delay, restart temperature check).
6 = Tripped.
7 = Programming mode.
8 = Jog forward.
9 = Jog reverse.
5 1 = Warning.
6 0 = Warning.
1 = Initialized.
7 0 = Local control.
1 = Remote control.
8 0 = Parameters have changed.
1 = No parameters have changed.2)
9 0 = Negative phase sequence.
1 = Positive phase sequence.
10–15 See trip codes in Table 7.4.3)
5 Current 0–13 Average rms current across all 3 phases.4)
14–15 Reserved.
6 Current 0–9 Current (% motor FLC).
10–15 Reserved.
Register Description Bits Details
7 Motor temperature 0–7 Motor 1 thermal model (%).
8–15 Motor 2 thermal model (%).
85) Power 0–11 Power.
12–13 Power scale.
14–15 Reserved.
9 % Power factor 0–7 100% = power factor of 1.
8–15 Reserved.
10 Reserved 0–15
114) Current 0–13 Phase 1 current (rms).
14–15 Reserved.
124) Current 0–13 Phase 2 current (rms).
14–15 Reserved.
134) Current 0–13 Phase 3 current (rms).
14–15 Reserved.
14 Reserved
15 Reserved
16 Reserved
17 Parameter list version number 0–7 Parameter list minor revision.
8–15 Parameter list major revision.
18 Digital input state 0–15 For all inputs, 0 = open, 1 = closed (shorted).
0 = Start.
1 = Stop.
2 = Reset.
3 = Input A.
4–15 Reserved.
19–31 Reserved

Table 7.3 Functions of Internal Registers

  1. Product type code: 4=MCD 200, 5=MCD 500.
  2. Reading register 3 (changed parameter value) resets registers 2 (changed parameter number) and 4 (parameters have changed). Always read registers 2 and 4 before reading register 3.
  3. Bits 10–15 of register 4 report the soft starter’s trip or warning code. If the value of bits 0–4 is 6, the soft starter has tripped. If bit 5=1, a warning has activated and the soft starter continues operation.
  4. For models MCD5-0053B and smaller, this value is 10 times greater than the value shown on the LCP.
  5. Power scale functions as follows:
    • 0 = Multiply power by 10 to get W.
    • 1 = Multiply power by 100 to get W.
    • 2 = Power is shown in kW.
    • 3 = Multiply power by 10 to get kW.

Parameter Management (Read/Write)
Parameter values can be read from or written to the soft starter.
If output register 57 of the scanner is greater than 0, the EtherNet/IP interface writes all parameter registers to the soft starter.

Enter the required parameter values in the output registers of the scanner. The value of each parameter is stored in a separate register. Each register corresponds to 2 bytes.

  • Register 57 (bytes 114–115) corresponds to parameter 1-1 Motor Full Load Current.
  • The VLT® Soft Starter MCD 500 has 109 parameters. Register 162 (bytes 324–325) corresponds to parameter 16-13 Low Control Volts.

NOTICE
When writing parameter values, the EtherNet/IP Interface updates all parameter values in the soft starter. Always enter a valid value for every parameter.

NOTICE
The numbering of parameter options via fieldbus communications differs slightly from the numbering shown on the LCP. Numbering via the Ethernet Module starts at 0, so for parameter 2-1 Phase Sequence, the options are 1–3 on the LCP but 0–2 via the module.

Trip Codes

Code Trip type MCD 201 MCD 202 MCD 500
0 No trip
11 Input A trip
20 Motor overload
21 Heat sink overtemperature
23 L1 phase loss
24 L2 phase loss
25 L3 phase loss
26 Current imbalance
28 Instantaneous overcurrent
29 Undercurrent
50 Power loss
54 Phase sequence
55 Frequency
60 Unsupported option (function not available in inside delta)
61 FLC too high
62 Parameter out of range
70 Miscellaneous
75 Motor thermistor
101 Excess start time
102 Motor connection
104 Internal fault x (where x is the fault code detailed in Table 7.5)
113 Starter communication (between module and soft starter)
114 Network communication (between module and network)
115 L1-T1 short-circuited
116 L2-T2 short-circuited
117 L3-T3 short-circuited
1191) Time-overcurrent (bypass overload)
121 Battery/clock
122 Thermistor circuit

Table 7.4 Trip Code Reported in Bytes 2–3 and 17 of the Status Commands

For VLT® Soft Starter MCD 500, time-overcurrent protection is only available on internally bypassed models.

Internal Fault X

Internal fault Message on LCP
70–72 Current Read Err. Lx
73 ATTENTION! Remove Mains Volts
74–76 Motor connection Tx
77–79 Firing Fail Px
80–82 VZC Fail Px
83 Low Control Volts
84–98 Internal fault X. Contact the local supplier with the fault code (X).

Table 7.5 Internal Fault Code Associated with Trip Code 104

NOTICE
Only available on VLT® Soft Starters MCD 500. For parameter details, see the VLT® Soft Starter MCD 500 Operating Guide.

Network Design

The Ethernet Module supports star, line, and ring topologies.

Star Topology
In a star network, all controllers and devices connect to a central network switch.

Danfoss-MCD-202-EtherNet-IP-Module-image (14)

Line Topology
In a line network, the controller connects directly to 1 port of the first EtherNet/IP Module. The 2nd Ethernet port of the EtherNet/IP Module connects to another module, which in turn connects to another module until all devices are connected. Danfoss-MCD-202-EtherNet-IP-Module-image (16)

NOTICE
The EtherNet/IP Module has an integrated switch to allow data to pass through in line topology. The EtherNet/IP Module must be receiving control power from the soft starter for the switch to operate.

NOTICE
If the connection between 2 devices is interrupted, the controller cannot communicate with devices after the interruption point.

NOTICE
Each connection adds a delay to communication with the next module. The maximum number of devices in a line network is 32. Exceeding this number may reduce the reliability of the network.

Ring Topology
In a ring topology network, the controller connects to the 1st EtherNet/IP Module via a network switch. The 2nd Ethernet port of the EtherNet/IP Module connects to another module, which in turn connects to another module until all devices are connected. The final module connects back to the switch.Danfoss-MCD-202-EtherNet-IP-Module-image (17)

NOTICE
The network switch must support loss of line detection.

Combined Topologies
A single network can include both star and line components.

Danfoss-MCD-202-EtherNet-IP-Module-image (18)

Specifications

  • Enclosure
    • Dimensions, W x H x D [mm (in)] 40 x 166 x 90 (1.6 x 6.5 x 3.5)
    • Weight 250 g (8.8 Oz)
    • Protection IP20
  • Mounting
    • Spring-action plastic mounting clips 2
  • Connections
    • Soft starter 6-way pin assembly
    • Contacts Gold …ash
    • Networks RJ45
  • Settings
    • IP address Automatically assigned, configurable
    • Device name Automatically assigned, configurable
  • Network
    • Link speed 10 Mbps, 100 Mbps (auto-detect)
    • Full duplex
    • Auto crossover
  • Power
    • Consumption (steady state, maximum) 35 mA at 24 V DC
    • Reverse polarity protected
    • Galvanically isolated
  • Certification
    • RCM IEC 60947-4-2
    • CE IEC 60947-4-2
    • ODVA EtherNet/IP conformance tested

Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on order provided that such alterations can be made without sub sequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.

FAQ

Q: What should I do if I encounter difficulties using the EtherNet/IP Module with third-party products?
A: If you face challenges when using the device with third-party products such as PLCs, scanners, or commissioning tools, contact the relevant supplier for assistance.

Documents / Resources

Danfoss MCD 202 EtherNet-IP Module [pdf] Installation Guide
AN361182310204en-000301, MG17M202, MCD 202 EtherNet-IP Module, MCD 202, EtherNet-IP Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *