Danfoss MCE101C Load Controller User Guide
DESCRIPTION
The MCE101C Load Controller is used to limit the power output from systems in which prime-mover inputs to the work stage are loaded by power outputs from the work stage. By limiting the output, the Controller keeps the prime-mover input near setpoint.
In a typical application, the MCE101C supplies a dithered voltage to a proportional solenoid valve that regulates servo pressure on a manually-controlled servo positioned hydrostatic transmission used to modulate a trencher’s ground speed. As heavy trenching loads, such as rocks or compacted earth, are encountered, the Load Controllerquickly responds to engine droop. By automatically reducing the commanded ground speed, engine stoppage is avoided and engine wear (caused by running at non-optimal speed) is reduced
The solenoid valve works in conjuction with the charge supply orifice in the manual displacement control to reduce servo pressure as engine speed reduces. The reduced servo pressure results in lower pump displacement and, therefore, slower ground speed. The servo positioned hydrostatic pumps must have sufficient spring centering moments to destroke the pump with reduced servo pressure. Heavy duty pumps with standard springs can be used in most applications.
FEATURES
- Short circuit and reverse polarity protected
- Rugged design resists shock, vibration, humidity and rain
- Instant load shedding avoids engine stall
- Versatile installation with either surface or panel mounting
- Remotely mounted controls allow operator to adapt to varied load conditions
- Available in both 12 and 24 volt models
- Requires no sophisticated tools to calibrate
- Adaptable to any heavy-equipment engine
- Forward/Reverse acting
ORDERING INFORMATION
SPECIFY
Model Number MCE101C1016, MCE101C1022. See Table A. for electrical and performance characteristics adaptable to customer requirements.
DEVICE NUMBER |
SUPPLY VOLTAGE(Vdc) |
RATED OUTPUT VOLTAGE (Vdc) |
RATED OUTPUT CURRENT(AMPS) |
MINIMUM LOAD RESISTANCE (OHMS) |
RPM ADJUST ON/OFF SWITCH |
FREQUENCY RANGE(Hz) |
PROPOR- TIONING BAND (%) |
DITHER | MOUNTING | ACTING |
MCE101C1016 | 11 – 15 | 10 | 1.18 | 8.5 | REMOTE | 300 – 1100 | 40 | 50 HZ 100 mAmp |
SURFACE | REVERSE |
MCE101C1022 | 22 – 30 | 20 | 0.67 | 30 | REMOTE | 1500 – 5000 | 40 | 50 HZ 100 mAmp |
SURFACE | FORWARD |
MAXIMUM OUTPUT = + SUPPLY – 3 Vdc. SUPPLY CURRENT = LOAD CURRENT + 0.1 AMP
TECHNICAL DATA
Variations in electrical specifications for devices are reflected in Table A. Controllers with specifications different from those in Table A. are available upon request. See Table A. in Ordering Information.
OPERATING TEMPERATURE
-20° to 65° C (-4° to 149° F)
STORAGE TEMPERATURE
-30° to 65° C (-22° to 149° F)
HUMIDITY
After being placed in a controlled atmosphere of 95% humidity at 40° C for 10 days, the Controller will perform within specification limits.
RAIN
After being showered from all directions by a high pressure hose down, the Controller will perform within specification limits.
VIBRATION
Withstands a vibration test designed for mobile equipment controls consisting of two parts:
- Cycling from 5 to 2000 Hz in each of the three axes.
- Resonance dwell for one million cycles for each resonance point in each of the three axes.
Run from 1 to 8 g’s. Acceleration level varies with frequency.
SHOCK
50 g for 11 milliseconds. Three shocks in both directions of the three mutually perpendicular axes for a total of 18 shocks.
DIMENSIONS
See Dimensions – MCE101C1016 and MCE101C1022
AUTO/MANUAL SWITCH
AUTO: Controller ON
MANUAL: Controller OFF
RPM ADJUST CONTROL
Operator-adjusted in accordance with load conditions. The adjustment is a percentage of the RPM setpoint.
RPM SETPOINT
A 25-turn, infinite adjustment control.
FEEDBACK FREQUENCY INPUT RANGE
Controllers are shipped with fixed frequency ranges. Table A shows the full frequency span.
50 Vdc maximum
Indefinite. Models with supply current over 1 amp with voltages at high end of rating and at high ambient temperatures may have their performance degraded after several minutes of short circuit.
DIMENSIONS – MCE101C1016 and MCE101C1022
THEORY OF OPERATION
The MCE101A Load Controller is used to reduce the power requested from a system under conditions which would otherwise overstress the system. The work function being controlled may be the ground speed of a ditcher, chain velocity of a wood chipper or other applications in which engine speed must be kept near an optimum horsepower
MCE101C1016 Curves – Diagram 1
MCE101C1016 Load Controller Curves Showing Output Voltage as a Function of Engine Droop. The Setpoint Illustrated is 920 Hz. Setpoint and Sensitivity are Adjustable. 5-2
MCE101C1022 Curves – Diagram 2
MCE101C1022 Load Controller Curves Showing Output Voltage as a Function of Engine Speed.
The Setpoint Illustrated is 3470 Hz. Setpoint and Sensitivity are Adjustable
Wiring connections are made with Packard Connectors. Engine input to the Controller must be an AC voltage frequency. Attach to a single-phase tap when using the alternator
The MCE101C Controllers listed in Table A are surface- mount models only. See Dimensions-MCE101C1016 and MCE101C1022
There are two control parameters that must be adjusted: AUTO-ON/OFF switch and RPM ADJUST setpoint. See MCE101C Curves Diagram 1 and Curves Diagram 2.
- AUTO ON/OFF SWITCH The Load Controller will be ON during normal machine use but is overriden in OFF position. Work to be done while machine is in idle must be done with switch OFF.
- RPM ADJUST SETPOINT The RPM setpoint is varied through a 1-turn potentiom- eter. The potentiometer is mounted on the Controller’s front panel, or remotely mounted
There are two control parameters that must be adjusted: AUTO-ON/OFF switch and RPM ADJUST setpoint. See MCE101C Curves Diagram 1 and Curves Diagram 2. 1. AUTO ON/OFF SWITCH The Load Controller will be ON during normal machine use but is overriden in OFF position. Work to be done while machine is in idle must be done with switch OFF. 2. RPM ADJUST SETPOINT The RPM setpoint is varied through a 1-turn potentiom- eter. The potentiometer is mounted on the Controller’s front panel, or remotely mounted
BLOCK DIAGRAM
MCE101C Used in a Closed-loop Load Control System.
CONNECTION DIAGRAM 1
Typical Wiring Schematic for MCE101C1016 and MCE101C1022 Load Controller With Remote AUTO/ON/OFF Switch and RPM ADJUST
TROUBLE SHOOTING
The MCE101C should give years of trouble-free service. If the Controller fails to hold an engine RPM after having previously run properly, any one of the system components could be the problem source. All Load Controller tests should be run on Auto Mode. Check the system as follows:
- If the voltage across MCE101C output is zero when OFF but high when ON, regardless of engine RPM, put the VOM across the alternator connection. It should read approximately 7 Vdc, indicating that the alternator is actually connected.
- If the alternator voltage is low, check the alternator belt. A loose or broken belt should be replaced.
- If the alternator is OK, but voltage across MCE101C output is low at high idle engine RPM, check controller voltage supply
- If normal electrical output shows, the valve and trans- mission should function properly. If not, one of them is the problem source
- If the above problems have been ruled out, the Load Controller will have to be returned to the factory. It is not field-repairable. See Customer Service Section.
CUSTOMER SERVICE
NORTH AMERICA
ORDER FROM
Danfoss (US) Company Customer Service Department 3500 Annapolis Lane North Minneapolis, Minnesota 55447
Phone: 763-509-2084
Fax: 763-559-0108
DEVICE REPAIR
For devices in need of repair, include a description of the problem, a copy of the purchase order and your name, address and telephone number.
RETURN TO
Danfoss (US) Company Return Goods Department 3500 Annapolis Lane North Minneapolis, Minnesota 55447
ORDER FROM
Danfoss ( Neumünster) GmbH & Co. Order Entry Department Krokamp 35 Postfach 2460 D-24531 Neumünster Germany
Phone: 49-4321-8710
Fax: 49-4321-871355

Documents / Resources
![]() |
Danfoss MCE101C Load Controller [pdf] User Guide MCE101C Load Controller, MCE101C, Load Controller, Controller |