Product Usage Instructions
Safety Notes
Please read the user manual carefully before using the device for the first time. The device should only be operated by qualified personnel and any repairs should be done by PCE Instruments personnel. Failure to follow the manual may result in damage or injuries not covered by warranty.
Installation
Follow the wiring diagrams provided in the manual for sensor installation. Ensure proper cable connections and torque settings on the terminal strip. Mount the sensor securely according to the specified dimensions.
Calibration
Refer to section 8 of the manual for calibration instructions. Regular calibration is essential to maintain accurate readings.
Contact Information
If you have any questions or need assistance, contact PCE Instruments at the provided contact details in section 9 of the manual.
Disposal
When disposing of the product, follow the guidelines in section 10 of the manual to ensure environmentally friendly disposal.
FAQs
- Q: Can unqualified personnel use the device?
A: No, the device should only be used by qualified personnel as stated in the safety notes. - Q: How often should calibration be performed?
A: Calibration should be performed regularly as indicated in the calibration section of the manual to maintain accuracy. - Q: What are the storage conditions for the device?
A: The storage conditions are specified in the manual under operating and storage conditions.
User manuals in various languages (français, italiano, español, português, nederlands, türk, polski, русский, 中文) can be found by using our product search on: www.pce-instruments.com.
Safety notes
Please read this manual carefully and completely before you use the device for the first time. The device may only be used by qualified personnel and repaired by PCE Instruments personnel. Damage or injuries caused by non-observance of the manual are excluded from our liability and not covered by our warranty.
- The device must only be used as described in this instruction manual. If used otherwise, this can cause dangerous situations for the user and damage to the meter.
- The instrument may only be used if the environmental conditions (temperature, relative humidity, …) are within the ranges stated in the technical specifications. Do not expose the device to extreme temperatures, direct sunlight, extreme humidity or moisture.
- Do not expose the device to shocks or strong vibrations.
- The case should only be opened by qualified PCE Instruments personnel.
- Never use the instrument when your hands are wet.
- You must not make any technical changes to the device.
- The appliance should only be cleaned with a damp cloth. Use only pH-neutral cleaner, no abrasives or solvents.
- The device must only be used with accessories from PCE Instruments or equivalent.
- Before each use, inspect the case for visible damage. If any damage is visible, do not use the device.
- Do not use the instrument in explosive atmospheres.
- The measurement range as stated in the specifications must not be exceeded under any circumstances.
- Non-observance of the safety notes can cause damage to the device and injuries to the user.
We do not assume liability for printing errors or any other mistakes in this manual.
We expressly point to our general guarantee terms which can be found in our general terms of business.
Specifications
Temperature PCE-EMD 5 | |
Measurement range | 0 … 50 °C |
Resolution | 0,1 °C |
Accuracy | ±0,5 °C |
Temperature PCE-EMD 10 | |
Measurement range | 32 … 122 °F |
Resolution | 0,1 °F |
Accuracy | ±0,9 °F |
Humidity | |
Measurement range | 0…. 99.9 % RH |
Resolution | 0.1 % RH |
Accuracy | ±3 % RH |
Further specifications | |
Response time | <15 seconds |
Number of usable sensors | 4 |
Digit height | 100 mm / 3.9″ |
Digit colour | white |
Sensor supply voltage | 12 and 24 V DC |
Maximum sensor supply current | 100 mA |
Impedance current input | <200 Ω |
Display housing material | Black lacquered aluminium housing |
Display protection | Anti-reflective methacrylate |
Sensor housing material | ABS |
Display protection class | IP20 |
Sensor protection class | IP30 |
Power supply | 110 … 220 V AC 50 / 60 Hz |
Maximum power consumption | 18 W |
Display mounting | Flat on a surface via a monitor stand (75 x 75 mm / 2.95 x 2.95″) |
Sensor mounting | flat on a surface |
Cable cross-section of terminal strip power supply | 0.5…. 2.5 mm² (AWG 14) rigid cable
0.5…. 1.5 mm² (AWG 15) flexible cable |
Cable cross-section of terminal strip sensor connection | 0.14 0.15 mm² (AWG 18) rigid cable
0.15 1 mm² (AWG16) flexible cable |
Terminal strip torque | 1.2 Nm |
Terminal strip screw length | <12 mm / 0.47″ |
Display dimensions | 535 x 327 x 53 mm / 21.0 x 12.8 x 2.0″ |
Sensor dimensions | 80 x 80 x 35 mm / 3.1 x 3.1 x 1.3″ |
Operating conditions | -10 … 60 ºC, 5 … 95 % RH, non-condensing |
Storage conditions | -20 … 70 ºC, 5 … 95 % RH, non-condensing |
Display weight | 4579 g / 161.5 oz |
Sensor weight | 66 g / 2.3 oz |
Delivery scope
- 1x large display PCE-EMD series (depending on model)
- 2x brackets for wall mounting
- 1x user manual
Dimensions
Display dimensions
Sensor dimensions
Wiring diagram
4 … 20 mA sensors on the display
Sensor connection
Diagram to PCE-EMD series (display)
Designation | Meaning |
24 V | Supply voltage 24 V |
12 V | Supply voltage 12 V |
Hx | Connection for humidity |
Tx | Connection for temperature |
GND | Dimensions |
Wiring diagram sensor (insulated)
Wiring diagram sensor (standard)
Instructions
To use the display, between one and four sensors must be connected to it. As there are no keys on the display, no operation is required. The display works completely automatically.
The display works as follows:
Number of sensors | Display |
0 | 99.9 °C / °F and 99.9 % RH |
1 | Measured values |
2 or more | Average of all sensors |
Calibration
To perform a calibration, there is a row of switches on the inside of the sensor. These switches can be used to change the temperature signal. The measured value can be added and subtracted by turning these switches on and off. It is not recommended to change these switches as the sensor is already set appropriately at the factory.
Position 1 | Position 2 | Position 3 | Position 4 | Correction |
– | – | – | – | 0 |
On | – | – | – | 0.2 |
– | On | – | – | 0.4 |
On | On | – | – | 0.6 |
– | – | On | – | 0.8 |
On | – | On | – | 1.0 |
– | On | On | – | 1.2 |
On | On | On | – | 1.4 |
Contact
If you have any questions, suggestions or technical problems, please do not hesitate to contact us. You will find the relevant contact information at the end of this user manual.
Disposal
For the disposal of batteries in the EU, the 2006/66/EC directive of the European Parliament applies. Due to the contained pollutants, batteries must not be disposed of as household waste. They must be given to collection points designed for that purpose.
In order to comply with the EU directive 2012/19/EU we take our devices back. We either re-use them or give them to a recycling company which disposes of the devices in line with law.
For countries outside the EU, batteries and devices should be disposed of in accordance with your local waste regulations.
If you have any questions, please contact PCE Instruments.
PCE Instruments contact information
Germany
PCE Deutschland GmbH
Im Langel 26
D-59872 Meschede
Deutschland
Tel.: +49 (0) 2903 976 99 0
Fax: +49 (0) 2903 976 99 29
info@pce-instruments.com
www.pce-instruments.com/deutsch
United Kingdom
PCE Instruments UK Ltd
Trafford House
Chester Rd, Old Trafford Manchester M32 0RS
United Kingdom
Tel: +44 (0) 161 464902 0
Fax: +44 (0) 161 464902 9
info@pce-instruments.co.uk
www.pce-instruments.com/english
The Netherlands
PCE Brookhuis B.V. Institutenweg 15
7521 PH Enschede
Nederland
Telefoon: +31 (0)53 737 01 92
info@pcebenelux.nl
www.pce-instruments.com/dutch
France
PCE Instruments France EURL
23, rue de Strasbourg
67250 Soultz-Sous-Forets
France
Téléphone: +33 (0) 972 3537 17 Numéro de fax: +33 (0) 972 3537 18
info@pce-france.fr
www.pce-instruments.com/french
Italy
PCE Italia s.r.l.
Via Pesciatina 878 / B-Interno 6 55010 Loc. Gragnano
Capannori (Lucca)
Italia
Telefono: +39 0583 975 114
Fax: +39 0583 974 824
info@pce-italia.it
www.pce-instruments.com/italiano
United States of America
PCE Americas Inc.
1201 Jupiter Park Drive, Suite 8 Jupiter / Palm Beach
33458 FL
USA
Tel: +1 561-320-9162
Fax: +1 561-320-9176
info@pce-americas.com
www.pce-instruments.com/us
Spain
PCE Ibérica S.L.
Calle Mula, 8
02500 Tobarra (Albacete) España
Tel. : +34 967 543 548
Fax: +34 967 543 542
info@pce-iberica.es
www.pce-instruments.com/espanol
Turkey
PCE Teknik Cihazları Ltd.Şti. Halkalı Merkez Mah.
Pehlivan Sok. No.6/C
34303 Küçükçekmece – İstanbul Türkiye
Tel: 0212 471 11 47
Faks: 0212 705 53 93
info@pce-cihazlari.com.tr
www.pce-instruments.com/turkish
Denmark
PCE Instruments Denmark ApS Birk Centerpark 40
7400 Herning
Denmark
Tel.: +45 70 30 53 08
kontakt@pce-instruments.com
www.pce-instruments.com/dansk
Documents / Resources
![]() |