MPD Series Automatic Backup Device
“
Product Information
Specifications
- Product Name: Automatic Backup Device (ABD Series)
- Models: ABD200-40-US10, ABD200-63-US10, ABD100-40-US10,
ABD100-63-US10 - Type: Multi-inverter Parallel Device (MPD Series)
- Models: MPD200-40-US10, MPD200-63-US10
- Version: V1.4-2025-06-09
Product Usage Instructions
1. Important Safety Instructions
SAVE THESE INSTRUCTIONS. Follow all safety precautions mentioned
in the manual when working on the device.
2. Product Introduction
Introduces the product and provides application scenarios for
its use.
3. Installation
Details installation requirements and steps for device
installation.
4. Electrical Connection
Includes safety precautions, preparing conductor conduit &
fittings, opening/closing the cabinet door.
4.1 Safety Precaution
Instructions on safety measures to be taken during electrical
connections.
4.2 Preparing Conductor Conduit & Fittings
Details on conduit holes, wiring specifications.
5. Equipment Commissioning
Checklist before powering on the device and steps to power it
on.
6. Maintenance
Guidance on powering off the device and replacing the inverter
breaker.
7. Technical Parameters
Technical specifications for both ABD Series and MPD Series.
FAQ
- Q: What should I do if the device malfunctions?
- A: Refer to the troubleshooting section in the user manual or
contact customer support for assistance. - Q: Can I install this device outdoors?
- A: The user manual should provide guidance on suitable
installation environments. Please refer to it for more
information.
“`
Quick Installation Guide
Automatic Backup Device
ABD Series
(ABD200-40-US10 | ABD200-63-US10 | ABD100-40-US10 | ABD100-63-US10)
Multi-inverter Parallel Device
MPD Series
(MPD200-40-US10 | MPD200-63-US10) V1.4-2025-06-09
CONTENT
User Manual V1.4-2025-06-09
CONTENT
1 IMPORTANT SAFETY INSTRUCTIONS ………………………………4
1.1 Hazard Level Definition …………………………………………………………………….4 1.2 General Safety ………………………………………………………………………………….4 1.3 Device Safety……………………………………………………………………………………5 1.4 Personal Requirements …………………………………………………………………….5
2 Product Introduction …………………………………………………….6
2.1 Product Introduction ……………………………………………………………………….6 2.2 Application Scenarios ……………………………………………………………………….7
2.2.1 Application Scenarios – ABD………………………………………………………………………7 2.2.2 Application Scenarios – MPD……………………………………………………………………..8 2.3 Electrical Diagram …………………………………………………………………………….9 2.3.1 Electrical Diagram – ABD …………………………………………………………………………..9 2.3.2 Electrical Diagram – MPD…………………………………………………………………………..9 2.4 Appearance …………………………………………………………………………………….10 2.4.1 Parts……………………………………………………………………………………………………….10 2.4.2 Dimensions …………………………………………………………………………………………….11 2.4.3 Indicators ……………………………………………………………………………………………….11 2.5 Deliverables ……………………………………………………………………………………12
3 Installation ………………………………………………………………….13
3.1 Installation Requirements……………………………………………………………….13 3.2 Device Installation………………………………………………………………………….14
4 Electrical Connection …………………………………………………..15
4.1 Safety Precaution …………………………………………………………………………..15 4.2 Preparing Conductor Conduit & Fittings…………………………………………15
4.2.1 Conduit Holes ………………………………………………………………………………………..15 4.2.2 Wiring Specifications ……………………………………………………………………………..16 4.3 Opening the Cabinet Door……………………………………………………………..18
2
User Manual V1.4-2025-06-09
CONTENT
4.4 Connecting the Conductors ……………………………………………………………………..19 4.4.1 Connecting the AC Conductors (Grid) ……………………………………………………..19 4.4.2 Connecting the AC Conductors (Load) …………………………………………………….20 4.4.3 Connecting the AC Conductors (Inverter)………………………………………………..20 4.4.4 Connecting the Communication Cable ……………………………………………………22 4.4.5 Connecting the CT Cable (Optional) ………………………………………………………..22
4.5 Closing the Cabinet Door ………………………………………………………………..23
5 Equipment Commissioning…………………………………………..24
5.1 Check Before Power ON ………………………………………………………………….24 5.2 Power ON the Device ………………………………………………………………………24
6 Maintenance ……………………………………………………………….25
6.1 Power OFF the Device ……………………………………………………………………..25 6.2 Replacing the Inverter Breaker………………………………………………………………….25
7 Technical Parameters …………………………………………………..26
7.1 ABD Series Technical Parameters………………………………………………….26 7.2 MPD Series Technical Parameters…………………………………………………27
3
1 IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS You shall follow all the safety precautions mentioned in this manual when working on the device.
WARNING The product is designed and tested to strictly comply with related safety rules. Read and follow all the safety instructions and cautions before any operations. Improper operations might cause personal injury or property damage as the device is electrical equipment.
1.1 Hazard Level Definition
Different levels of warning messages in this manual are defined as follows:
DANGER Indicates a high-level hazard that, if not avoided, will result in death or serious injury.
WARNING Indicates a medium-level hazard that, if not avoided, could result in death or serious injury.
CAUTION Indicates a low-level hazard that, if not avoided, could result in minor or moderate injury.
NOTICE Highlights key information and supplements other text. It may include skills and methods to solve product-related problems.
1.2 General Safety
NOTICE · The information in this manual is subject to change due to product updates or other
reasons. This guide cannot replace the product labels or other safety precautions unless otherwise specified. All descriptions here are for guidance only. · Before installation, read through this manual to learn about the product and the precautions. · All operations should be performed by trained and knowledgeable technicians who are familiar with local standards and safety regulations. · Use insulating tools and wear personal protective equipment when operating the device to ensure personal safety. Wear anti-static gloves, cloths, and wrist strips when touching electronic devices to protect the device from damage. · Strictly follow the installation, operation, and configuration instructions in this manual. The manufacturer shall not be liable for device damage or personal injury if you do not follow the instructions. Visit https://en.goodwe.com to get more information about product warranty.
4
1.3 Device Safety
WARNING
The voltage and frequency at the connecting point should meet the on-grid requirements. Make sure that the current rating of this product’s main breaker meets the specifications of the household power distribution unit. The PE (equipment grounding) cable of the device must be connected firmly (1.6N·m). For AC circuit connections, copper (CU) conductors are recommended.
DANGER
All labels and warning marks should be visible after the installation. Do not scrawl on, damage, or cover any label on the device. Unauthorized dismantling or modification may damage the equipment. Such action may damage the equipment and is not covered under the warranty. Warning labels on the device are as follows.
DANGER High voltage hazard. Disconnect all incoming power and turn off the product before working on it.
Read through the user manual before working on this device.
High-temperature hazard. Do not touch the product under operation to avoid being burnt.
Do not dispose of the device as household waste. Discard the product in compliance with local laws and regulations, or send it back to the manufacturer.
Delayed discharge. Wait 5 minutes after power off until the components are completely discharged. Potential risks exist. Wear proper PPE before any operations. Grounding point.
SGS certification mark.
1.4 Personal Requirements
NOTICE
· Personnel who install or maintain the device must be strictly trained, learn about safety precautions and correct operations.
· Only qualified professionals or trained personnel are allowed to install, operate, maintain, and replace the device or parts.
5
2 Product Introduction
2.1 Product Introduction
Function Description
The device transfers between on-grid mode and backup mode with an integrated switch. The device connects the main panel, the utility grid, and the AC output of the inverter to form an on-grid system when the utility grid works normally. Once the utility grid fails, the device will connect loads and the AC output of the inverter only to form a backup system. The ABD supports one inverter and the MPD supports up to three inverters.
Model Description
This manual covers listed device below:
ABD Series
MPD Series
· ABD200-40-US10 · ABD200-63-US10 · ABD100-40-US10 · ABD100-63-US10
· MPD200-40-US10 · MPD200-63-US10
Model Explanation
ABD200-40-US10
1
2 3 45
No. Meaning
Description
1 Product
ABD: Automatic Backup Device MPD: Multi-inverter Parallel Device
2 Main breaker rating 200: Applies to the main service panel whose main breaker rating is smaller than or equal to 200A and larger than 100A. 100: Applies to the main service panel whose main breaker rating is smaller than or equal to 100A.
3 Protection current of 40/63: The protection current of the inverter breaker is 40A or the inverter breaker 63A, which matches with the following inverters: Hybrid inverters: GW5000/6000/7600/9600/11K-ES-US20 AC-coupled inverters: GW5000/6000/7600/9600/11K-SBP-US20
4 Region code
US: the U.S.
5 Generation code
10: generation 1.0
Supported Grid Type
The inverter supports 120/240V split phase grid type. L1
120V N
120V
6
240V L2
2.2 Application Scenarios
Add an ABD (Automatic Backup Device) in the system to realize the whole home backup. Once the utility grid fails, the ABD will disconnect the main service panel from the utility grid, and the inverter will switch to off-grid working mode to supply power to the loads.
2.2.1 Application Scenarios – ABD
· Whole Home Backup System
Emergency stop button
Hybrid,ACCoupled inverter
PV module strings
Battery breaker
Generator
ABD
Utility meter
Auto transfer switch
Utility Grid
Battery
· Microgrid System
Battery
Battery breaker
Electric vehicle
Power cable
Main panel
Load Household breaker loads
Signal cable
Emergency stop button
AC coupled inverter
ABD
Electric vehicle
Grid
tied PV inverter
PV module strings
Utility meter Utility Grid
AC breaker
Power cable
7
CT
Main panel
Load Household
breaker
loads
Signal cable
2.2.2 Application Scenarios – MPD
PV module strings
Inverter inverter
Inverter PV module strings
MPD
Utility meter
Utility Grid
PV module strings
Inverter
Hybrid inverter
Power cable
Main panel Signal cable
Household loads
8
2.3 Electrical Diagram 2.3.1 Electrical Diagram – ABD
MCB L1 L2 N
Control Board
L1
Inverter L2 N PE
INVCB
2.3.2 Electrical Diagram – MPD
MCB L1 L2 N
Control Board
L1
L2 Inverter N
PE
L1
Inverter
L2 N
PE
L1
Inverter
L2 N
PE
INVCB INVCB INVCB
CT1
RLY
CT2
Meter
CT1
RLY
CT2
Meter
9
L1 L2 Main
Panel N PE
L1 L2 Main N Panel PE
2.4 Appearance
2.4.1 Parts 1
3 2
2
4 5 6 7
No. Part
1
LED indicator
2
Lock
3
Hanging bracket
4
Smart meter
5
Insulation board
6
Inverter breaker
7
Main Breaker
Description
Indicates the working status of the device. To lock the device’s door (key included). Hangs the device on the mounting support. Contact after-sales service for support or replacement. Ensures personal safety and protects the device. Provides overcurrent protection for the inverter. Recommended specifications: 40A or 63A (or 60A when the ALT of the installation site is less than 2000m) Breaker, UL489 certified. ABD: 1 x inverter breaker. MPD: 3 x inverter breakers. Actual product may vary. This breaker is optional when the main panel is also equipped with a breaker. Provides overcurrent protection from utility grid.
10
2.4.2 Dimensions
150mm (5.9in)
450mm (17.7in)
100mm 100mm (3.94in) (3.94in)
145mm (5.71)
610mm (24in)
2.4.3 Indicators
Indicator
Status
Explanation
ON= The grid is abnormal and the system is in Back-up mode.
BLINK = The grid is normal and the system is in On-grid mode.
OFF = With no input source, the system is in waiting mode.
ON = The communication with the inverter is normal, and the 12V power supply from the inverter is normal.
BLINK 1= The communication with the inverter is normal, and the 12V power supply from the inverter is abnormal.
BLINK 2= The communication with the inverter is abnormal, and the 12V power supply from the inverter is normal.
Off = The communication with the inverter is abnormal, and the 12V power supply from the inverter is abnormal.
On = Fault has occurred.
Off = No fault.
11
2.5 Deliverables
Device *1
Mounting bracket *1
Waterproof nut remove tool *1
Expansion bolt *4
Cable tie for Screw *N communication
cable *2
10AWG pin 6AWG pin Terminal for terminal *N terminal *N Neutral wire *N
Communication terminal and CT *1
Documents *1
Communication cable for parallel
connection *N
Key *4
NOTICE
· N = Quantity depends on the device model. · The number of pin terminals and communication terminal are various depending on
different devices. The actual accessories may differ. · The communication cable for parallel connection is only for MPD.
12
3 Installation
3.1 Installation Requirements
Installation Environment Requirements
Prevent Child Access
200mm 7.87in
200mm 7.87in
200mm 7.87in
500mm 19.68in
300mm 11.81in
-31°F~140°F (-35°C~60°C)
IP44 TYPE 3R
0%~95%RH Installation Angle Requirements
ALT: 3000m 9842ft
13
3.2 Device Installation
NOTICE
· Avoid the water pipes and cables buried in the wall when drilling holes. · Wear goggles and a dust mask to prevent the dust from being inhaled or contacting eyes
when drilling holes.
Step 1 Put the mounting bracket on the wall or the support horizontally and mark positions for drilling holes. Step 2 Drill holes to a depth of 80mm(3.15in) using the hammer drill. The diameter of the drill bit should be 10mm(0.39in). Step 3 Secure the mounting bracket using the expansion bolts. Step 4 Install the device on the mounting bracket. Step 5 Screw to secure the device and the mounting bracket.
1
2
3
4 5
14
4 Electrical Connection
4.1 Safety Precaution
DANGER
INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK · Perform electrical connections, including operations, cables, and component specifications
in compliance with local laws and regulations ANSI/NFPA 70. · The input and output circuits are isolated from the enclosure and that system grounding,
if required by the National Electric Code, ANSI/NFPA 70, is the responsibility of the installer. · Power off the device before any electrical connections. Otherwise, an electric shock may
occur. · Tie the cables of the same type together, and place cables of different types apart. Do not
place the cables entangled or crossed. · If the tension is too large, the cable may be poorly connected. You have to reserve a certain
length of the cable before connecting it to the device cable port. · Make sure that the cable conductor is in full contact with the terminal and the cable insulation
part is not crimped with the terminal when crimping the terminal. Otherwise, the device may not be able to work properly, or the connection may be unreliable during working, which may cause terminal block damage, etc.
NOTICE
· Cable colors in this document are for reference only. The cable specifications shall meet local laws and regulations.
4.2 Preparing Conductor Conduit & Fittings
4.2.1 Conduit Holes
WARNING
· Wiring conduits are additionally required, not included in the scope of delivery. The conduit must be UL514B listed and meet the specifications of the waterproof nut.
· To avoid influencing the protection class or damaging the equipment, check the wiring conduit to make sure that the conduit is installed properly and the holes are sealed.
AC Grid conduit hole
AC Loads conduit hole
Inverter conduit hole
15
Conduit Hole AC Grid AC Loads
Inverter
Description
Install the wiring conduit and run Grid-L1, Grid-L2, and Neutral wire through the cable hole.
Install the wiring conduit and run Load-L1, Load-L2, Neutral wire, and PE through the cable hole.
Install the wiring conduit and run Inverter-L1, Inverter-L2, Neutral wire, PE cable, and communication cable through the cable hole.
Conduit 2 inch conduit 2 inch conduit
1 inch conduit
4.2.2 Wiring Specifications Type 1
2 1
3 3
4
6 5
7
Type 2
16
No.
Parts
Labeling
Description
1. Inverter
Inverter COM
communication
terminal
2. CT terminal for solar inverter
3. CT
–
· Terminal for connecting the communication cable of the inverter.
· Recommended specification: RJ45 cable, 24AWG, CAT5e or better.
· Terminal for connecting the CT for the solar inverter.
–
4. Inverter terminal
5. AC Grid terminal
6. AC Loads terminal
7. Grounding busbar
Inverter A-L1 / L2, Inverter B-L1 / L2, Inverter C-L1 / L2, Inverter-N
Grid-L1, Grid-L2, Grid-N
Load-L1, Load-L2, Load-N
· Terminal for connecting the AC conductor of the inverter.
· Inverter B and Inverter C are only for MPD series products.
· Recommended specification: 6-8AWG, copper conductor, 90.
· Terminal for connecting the Grid conductor. · Recommended specification:
· 4/0AWG, copper conductor, 90 for ABD20040-US10, ABD200-63-US10, MPD200-40-US10, and MPD200-63-US10.
· 3AWG, copper conductor, 90 for ABD100-40US10 and ABD100-63-US10.
· Terminal for connecting the AC conductor of the load.
· Recommended specification: · 4/0AWG, copper conductor, 90 for ABD20040-US10, ABD200-63-US10, MPD200-40-US10, and MPD200-63-US10. · 3AWG, copper conductor, 90 for ABD100-40US10 and ABD100-63-US10.
· Busbar for connecting the PE cable. · Recommended specification:
· Load-PE: 4-6AWG, copper conductor, 90. · Inverter-PE: 10AWG, copper conductor, 90.
17
4.3 Opening the Cabinet Door
Step 1 Unlock the cabinet door using the included key. Step 2 Remove the six screws fixing the insulation board(torque: 0.8Nm). Step 3 Remove the insulation board.
1
2
1
1
1
2
1
1
1
1 0.8N·m
18
4.4 Connecting the Conductors
WARNING · Connect the conductors to the right terminals like L1, L2, and N. The device may be
damaged if the conductors are connected inappropriately. · Make sure that the whole conductors are inserted into the terminal holes. No part of the
conductor can be exposed. · Make sure that the conductors are connected securely. Otherwise, the terminal may get
too hot and damage the device.
4.4.1 Connecting the AC Conductors (Grid)
WARNING The ac output (neutral) is not bonded to ground.
Step 1 Strip the conductor wiring. Step 2 Remove the waterproof cover using the included cap removal tool. Step 3 Insert the desired conduit and corresponding adaptors, fittings, and bushings. Step 4 Insert the conductors into the device and tighten the conduit.
3
1
2
18-22mm
4
4
2 1
3
4
2
2
1
4 M16 10N·m
2 M16 10N·m
19
4.4.2 Connecting the AC Conductors (Load)
Step 1 Strip the conductor wiring. Step 2 Remove the waterproof cover using the included cap removal tool. Step 3 Insert the desired conduit and corresponding adaptors, fittings, and bushings. Step 4 Insert the conductors into the device and tighten the conduit.
3
M5 4 1.6N·m 5 M16 10N·m 4
5 5 4
2
1
3
1
2
18-22mm
10-12mm
M5 2 1.6N·m
4
4 3
2 1
4 M16 10N·m
4.4.3 Connecting the AC Conductors (Inverter)
Step 1 Strip the conductor wiring, crimp the conductor with appropriate wire connector. Step 2 Remove the waterproof cover using the included cap removal tool. Step 3 Insert the desired conduit and corresponding adaptors, fittings, and bushings. Step 4 Insert the conductors into the device and tighten the conduit.
20
1
13-15mm
6-9mm 10-12mm
2
3
4
2
2
1
1
3 3
5
6
2 1
M6 2 3N·m
3
1
2
1
3
2
M5 1 1.6N·m M5 3 1.6N·m
3 M16 0.8N·m 1 M16 0.8N·m
21
4.4.4 Connecting the Communication Cable
Step 1 Prepare a RJ45 network cable and insert it into the terminal. Step 2 Run the cable through the cable clip and the conduit.
ABD or MPD
4.4.5 Connecting the CT Cable (Optional)
· Only for AC coupled inverters.
NOTICE
Step 1 Clamp the CT around the cable to be measured. Step 2 Insert the CT cable into the terminal block.
Type 1
Grid tied PV inverter
ABD or MPD
22
Inverter
L1 L2
Main Panel
Type 2
4.5 Closing the Cabinet Door
Step 1 Install the insulation board. Step 2 Tighten the six screws fix the insulation board (torque: 0.8Nm). Step 3 Optional. Lock up the device using the cabinet key. Keep the key properly for future use.
2
2
1
2
1
2
2
2
2
3
2 0.8N·m
23
5 Equipment Commissioning
5.1 Check Before Power ON
No.
Check Item
1 The product is firmly installed at a clean place that is well-ventilated and easy-tooperate.
2 The PE, power, and communication cables are connected correctly and securely. 3 Cable ties are intact, routed properly and evenly. 4 Unused ports and terminals are fitted using the waterproof caps. 5 The insulation board is installed properly. 6 The voltage and frequency at the connection point meet the grid connection
requirements. 7 The electrical conduit holes are sealed.
5.2 Power ON the Device
Step 1 Turn on the main breaker of the device. Step 2 Turn on the inverter breaker of the device.
24
6 Maintenance
6.1 Power OFF the Device
DANGER INSTRUCTIONS PERTAINING TO A RISK OF FIRE OR ELECTRIC SHOCK · Power off the device before operations and maintenance. Otherwise, the device may be
damaged or electric shocks may occur. · Delayed discharge. Wait until the components are discharged and the LED indicators are
off after power off. Step 1 Turn off the main breaker of the device. Step 2 Turn off the inverter breaker of the device. Step 3 Turn off the breaker of the main panel. Step 4 Power off the inverter.
6.2 Replacing the Inverter Breaker
WARNING · Make sure that the device is powered off. · Wear proper personal protective equipment before any operations. Step 1 Loosen the screws and cables of the breaker. Step 2 Pull the plastic slot under the breaker. Step 3 Replace the breaker with a new one, the new breaker shall be AC40A or 63A(60A) and UL489 certified. Step 4 Place the breaker properly and push the plastic slot. Make sure that the breaker is securely installed. Step 5 Tighten the cables.
25
7 Technical Parameters
7.1 ABD Series Technical Parameters
Technical Data
ABD20040-US10
ABD20063-US10
ABD10040-US10
ABD10063-US10
Electrical Data
Nominal Output Voltage (V)
240
Output Voltage Range (V)
211~264
Feed-in Type
Split Phase
Nominal AC Voltage of Line Conductor (V)
120/240
Nominal AC Frequency (Hz)
60
AC Frequency Range (Hz)
58.5~61.2
Current Rating (From Grid)(A)
200
Max. Continuous Current From Inverter (A)
32
47.5
32
47.5
Maximum Overcurrent Protection of
200
100
Main Breaker (A)*1
Maximum Overcurrent Protection of
40
63
40
63
Circuit Breaker of Inverter (A)
General Data
Operating Temperature Range ()
-13~+140 (-25~+60)*2
Max. Operating Altitude (ft)
9842ft (3000m)
Cooling Method
Natural Convection
Communication with Inverter
RS485
Weight (lb)
26lb (12kg)
Dimension (W×H×D in)
17.7×24×5.9 in (450×610×150 mm)
Mounting Method
Wall Mounted
Ingress Protection Rating
Type 3R, IP44
Certification
Safety Regulation
UL1741, CSA 22.2 No. 107-01
EMC
FCC part15 CLASS B
*1: The main breaker is optional. *2: Derating temperatrure: 113(45).
26
7.2 MPD Series Technical Parameters
Technical Data Electrical Data Nominal Output Voltage (V) Output Voltage Range (V) Feed-in Type Nominal AC Voltage of Line Conductor (V) Nominal AC Frequency (Hz) AC Frequency Range (Hz) Current Rating (From Grid)(A) Max. Continuous Current From Inverter (A) Max. Amount of Inverters in Parallel Maximum Overcurrent Protection of Main Breaker (A)*1 Maximum Overcurrent Protection of Circuit Breaker of Inverter (A) General Data Operating Temperature Range () Max. Operating Altitude (ft) Cooling Method Communication with Inverter Weight (lb) Dimension (W×H×D in) Mounting Method Ingress Protection Rating Certification Safety Regulation EMC *1: The main breaker is optional. *2: Derating temperatrure: 113(45).
MPD200-40-US10
MPD200-63-US10
240
211~264
Split Phase 120/240 60
58.5~61.2 200
32
47.5
3
200
40
63
-13~+140 (-25~+60)*2 9842ft (3000m)
Natural Convection RS485
30lb (13.5kg) 17.7×24×5.9 in (450×610×150 mm)
Wall Mounted Type 3R, IP44
UL1741, CSA 22.2 No. 107-01 FCC part15 CLASS B
27
Website
GoodWe Technologies Co., Ltd.
No. 90 Zijin Rd., New District, Suzhou, 215011, China www.goodwe.com service@goodwe.com
Contact Info
340-00797-04
Documents / Resources
![]() |
GOODWE MPD Series Automatic Backup Device [pdf] Installation Guide ABD200-40-US10, ABD200-63-US10, ABD100-40-US10, ABD100-63-US10, MPD200-40-US10, MPD200-63-US10, MPD Series Automatic Backup Device, MPD Series, Automatic Backup Device, Backup Device |