GOODWE - logoMPD Series Automatic Backup Device
Fa'atonu Taiala

GOODWE MPD Series Automatic Backup Device

FAATONUGA TAU SAOGALEMU

FAASAO NEI FAATONGA
You shall follow all the safety precautions mentioned in this manual when working on the device.
Lapataiga icon LAPATAIGA
The product is designed and tested to strictly comply with related safety rules. Read and follow all the safety instructions and cautions before any operations. Improper operations might cause personal injury or property damage as the device is electrical equipment.
1.1 Hazard Level Definition
O tulaga eseese o savali lapatai i totonu o lenei tusi lesona ua faauigaina e faapea:
Lapataiga icon TALA
Fa'ailoa mai se tulaga lamatia maualuga, afai e le 'alofia, o le a i'u i le oti po'o se manu'a tuga.
Lapataiga icon LAPATAIGA
O lo'o fa'ailoa mai ai se tulaga lamatia maualuga, afai e le 'alofia, e ono i'u ai i le oti po'o se manu'a tuga.
Lapataiga icon FAATUATUA
O lo'o fa'ailoa mai ai se tulaga lamatia maualalo, afai e le 'alofia, e ono i'u ai i manu'a la'ititi pe feololo.
FAAALIGA
Highlights key information and supplements other text. It may include skills and methods to solve product-related problems.
1.2 Saogalemu Lautele
FAAALIGA

  • The information in this manual is subject to change due to product updates or other reasons. This guide cannot replace the product labels or other safety precautions unless otherwise specified. All descriptions here are for guidance only.
  • Before installation, read through this manual to learn about the product and the precautions.
  • O gaioiga uma e tatau ona fa'atinoina e ni tekinisia ua a'oa'oina ma le poto ua masani i tulaga fa'alotoifale ma tulafono faatonutonu mo le saogalemu.
  • Use insulating tools and wear personal protective equipment when operating the device to ensure personal safety. Wear anti-static gloves, cloths, and wrist strips when touching electronic devices to protect the device from damage.
  • Strictly follow the installation, operation, and configuration instructions in this manual. The manufacturer shall not be liable for device damage or personal injury if you do not follow the instructions. Visit https://en.goodwe.com to get more information about product warranty.

1.3 Saogalemu o Meafaigaluega
Lapataiga icon LAPATAIGA
Le voltagu ma le taimi i le nofoaga feso'ota'i e tatau ona fetaui ma mana'oga i luga ole laiga.
Make sure that the current rating of this product’s main breaker meets the specifications of the household power distribution unit.
The PE (equipment grounding) cable of the device must be connected firmly (1.6N·m).
For AC circuit connections, copper (CU) conductors are recommended.
Lapataiga icon TALA
All labels and warning marks should be visible after the installation. Do not scrawl on, damage, or cover any label on the device.
Unauthorized dismantling or modification may damage the equipment. Such action may damage the equipment and is not covered under the warranty. Warning labels on the device are as follows.

Faailo Lapataiga Eletise TALA High voltagu lamatiaga. Aveese uma le eletise o loʻo sau ma tape le oloa aʻo leʻi galue i ai.
LG LW6024R Smart Wi Fi Fa'agata Fa'amalama Fa'amalama - Fa'ailoga 4 Faitau le tusi fa'aoga a'o le'i galue i lenei masini.
AVTech BATR3CWWW Ma'a Ma'a - Fa'ailoga 3 Tulaga maualuga o le vevela. Aua le pa'i i le oloa o lo'o fa'agaioia ina ia 'alofia le mu.
WEE-Disposal-icon.png Do not dispose of the device as household waste. Discard the product in compliance with local laws and regulations, or send it back to the manufacturer.
GOODWE MPD Series Automatic Backup Device - icon Fa'atuai ona alu ese. Faatali mo le 5 minute pe a uma le paoa seia mae'a atoa vaega.
lapata'iga - 1 O lo'o iai a'afiaga e ono tula'i mai. Fa'aofu lelei PPE a'o le'i faia se gaioiga.
HITACHI RAK-QJ18PCBST Potu Air Conditioner - fa'ailoga 1 Nofoaga fa'avae.
GOODWE MPD Series Automatic Backup Device - icon 1 SGS certification mark.

1.4 Manaoga Faaletagata Lava Ia
FAAALIGA

  • Personnel who install or maintain the device must be strictly trained, learn about safety precautions and correct operations.
  • E na'o tagata tomai fa'apitoa po'o tagata faigaluega ua a'oa'oina e fa'atagaina e fa'apipi'i, fa'agaioi, tausia, ma sui le masini po'o vaega.

Folasaga o oloa

2.1 Folasaga o oloa
Fa'amatalaga Galuega
The device transfers between on-grid mode and backup mode with an integrated switch.
The device connects the main panel, the utility grid, and the AC output of the inverter to form an on-grid system when the utility grid works normally. Once the utility grid fails, the device will connect loads and the AC output of the inverter only to form a backup system.
The ABD supports one inverter and the MPD supports up to three inverters. Model Description
This manual covers listed device below:
ABD Series

  • ABD200-40-US10
  • ABD200-63-US10
  • ABD100-40-US10
  • ABD100-63-US10

MPD Fa'asologa

  • MPD200-40-US10
  • MPD200-63-US10

Fa'ata'ita'iga Fa'amatalaga
GOODWE MPD Series Automatic Backup Device - Model Explanation

Leai. Uiga Fa'amatalaga
1 Oloa ABD: Automatic Backup Device MPD: Multi-inverter Parallel Device
2 Main breaker rating 200: Applies to the main service panel whose main breaker rating is smaller than or equal to 200A and larger than 100A.
100: Applies to the main service panel whose main breaker rating is smaller than or equal to 100A.
3 Protection current of the inverter breaker 40/63: The protection current of the inverter breaker is 40A or 63A, which matches with the following inverters:
Hybrid inverters: GW5000/6000/7600/9600/11K-ES-US20 AC-coupled inverters: GW5000/6000/7600/9600/11K-SBP-U520
4 Fa'ailoga itulagi US: the U.S.
5 Generation code 10: generation 1.0

Supported Grid Type
The inverter supports 120/240V split phase grid type.GOODWE MPD Series Automatic Backup Device - Grid Type2.2 Fa'atinoga Fa'atusa
Add an ABD (Automatic Backup Device) in the system to realize the whole home backup. Once the utility grid fails, the ABD will disconnect the main service panel from the utility grid, and the inverter will switch to off-grid working mode to supply power to the loads.
2.2.1 Application Scenarios – ABD
• Whole Home Backup SystemGOODWE MPD Series Automatic Backup Device - Backup System

Microgrid SystemGOODWE MPD Series Automatic Backup Device - Microgrid System2.2.2 Application Scenarios – MPD

GOODWE MPD Series Automatic Backup Device - Application Scenarios - MPD2.3 Ata eletise
2.3.1 Electrical Diagram – ABDGOODWE MPD Series Automatic Backup Device - Electrical Diagram2.3.2 Electrical Diagram – MPDGOODWE MPD Series Automatic Backup Device - Electrical Diagram - MPD2.4 Fa'aaliga
2.4.1 VaegaGOODWE MPD Series Automatic Backup Device - Electrical Diagram - Appearance

Leai. Vaega Fa'amatalaga
1 Fa'ailoga LED Indicates the working status of the device.
2 Loka To lock the device’s door (key included).
3 Faʻatautau tautau Hangs the device on the mounting support.
4 mita atamai Contact after-sales service for support or replacement.
5 laupapa fa'amama Ensures personal safety and protects the device.
6 Inverter breaker Provides overcurrent protection for the inverter.
Recommended specifications: 40A or 63A (or 60A when the ALT of the installation site is less than 2000m) Breaker, UL489 certified. ABD: 1 x inverter breaker. MPD: 3 x inverter breakers.
O oloa moni e ono eseese.
7 Tu'u Autu This breaker is optional when the main panel is also equipped with a breaker. Provides overcurrent protection from utility grid.

2.4.2 FuaGOODWE MPD Series Automatic Backup Device - Dimensions2.4.3 Fa'ailoga

Fa'ailoga Tulaga Fa'amatalaga
GOODWE MPD Series Automatic Backup Device - icon 2 GOODWE MPD Series Automatic Backup Device - icon 4 ON= The grid is abnormal and the system is in Back-up mode.
GOODWE MPD Series Automatic Backup Device - icon 5 BLINK = The grid is normal and the system is in On-grid mode.
GOODWE MPD Series Automatic Backup Device - icon 6 OFF = With no input source, the system is in waiting mode.
GOODWE MPD Series Automatic Backup Device - icon 3 GOODWE MPD Series Automatic Backup Device - icon 7 ON = The communication with the inverter is normal, and the 12V power supply from the inverter is normal.
GOODWE MPD Series Automatic Backup Device - icon 8 BLINK 1= The communication with the inverter is normal, and the 12V power supply from the inverter is abnormal.
GOODWE MPD Series Automatic Backup Device - icon 9 BLINK 2= The communication with the inverter is abnormal, and the 12V power supply from the inverter is normal.
GOODWE MPD Series Automatic Backup Device - icon 6 Off = The communication with the inverter is abnormal, and the 12V power supply from the inverter is abnormal.
lapata'iga 2 GOODWE MPD Series Automatic Backup Device - icon 10 On = Fault has occurred.
GOODWE MPD Series Automatic Backup Device - icon 6 Off = No fault.

2.5 Tuuina atuGOODWE MPD Series Automatic Backup Device - DeliverablesFAAALIGA

  • N = Quantity depends on the device model.
  • The number of pin terminals and communication terminal are various depending on different devices. The actual accessories may differ.
  • The communication cable for parallel connection is only for MPD.

Fa'apipi'i

3.1 Fa'apipi'i Manaoga
Faʻapipiʻi Siʻosiʻomaga ManaʻomiaGOODWE MPD Series Automatic Backup Device - Installation RequirementsFa'apipi'i Angle ManaogaGOODWE MPD Series Automatic Backup Device - 1

3.2 Fa'apipi'i Mea
FAAALIGA

  • Aloese mai paipa vai ma uaea e tanumia i le puipui pe a vili pu.
  • Fai mata tioata ma se ufimata pefu e puipuia ai le pefu mai le manava pe faʻafesoʻotaʻi mata pe a vili pu.

Step 1 Put the mounting bracket on the wall or the support horizontally and mark positions for drilling holes.
Step 2 Drill holes to a depth of 80mm(3.15in) using the hammer drill. The diameter of the drill bit should be 10mm(0.39in).
Step 3 Secure the mounting bracket using the expansion bolts.
Step 4 Install the device on the mounting bracket.
Step 5 Screw to secure the device and the mounting bracket.GOODWE MPD Series Automatic Backup Device - mounting bracket

Fesootaiga Eletise

4.1 Puipuiga o le Saogalemu

lapata'iga 2 TALA
FAATONUGA E FAI I SE MATA'AGA O LE MU PO'O LE PILI ELETI

  • Perform electrical connections, including operations, cables, and component specifications in compliance with local laws and regulations ANSI/NFPA 70.
  • The input and output circuits are isolated from the enclosure and that system grounding, if required by the National Electric Code, ANSI/NFPA 70, is the responsibility of the installer.
  • Power off the device before any electrical connections. Otherwise, an electric shock may occur.
  • Nonoa faatasi uaea o le ituaiga tutusa, ma tuu ese uaea o ituaiga eseese. Aua ne'i tu'u uaea ua nonoa pe sopoia.
  • If the tension is too large, the cable may be poorly connected. You have to reserve a certain length of the cable before connecting it to the device cable port. • Make sure that the cable conductor is in full contact with the terminal and the cable insulation part is not crimped with the terminal when crimping the terminal. Otherwise, the device may not be able to work properly, or the connection may be unreliable during working, which may cause terminal block damage, etc.

FAAALIGA

  • O lanu uaea i lenei pepa e na'o le fa'asinomaga. O fa'amatalaga uaea e tatau ona fetaui ma tulafono ma tulafono fa'alotoifale.

4.2 Preparing Conductor Conduit & Fittings
4.2.1 Conduit Holes
LAPATAIGA

  • Wiring conduits are additionally required, not included in the scope of delivery. The conduit must be UL514B listed and meet the specifications of the waterproof nut.
  • To avoid influencing the protection class or damaging the equipment, check the wiring conduit to make sure that the conduit is installed properly and the holes are sealed.

GOODWE MPD Series Automatic Backup Device - Conduit Holes

Conduit Hole Fa'amatalaga Alavai
AC Grid Install the wiring conduit and run Grid-L1, Grid-L2, and Neutral wire through the cable hole. 2 inch conduit
Uta AC Install the wiring conduit and run Load-L1, Load-L2, Neutral wire, and PE through the cable hole. 2 inch conduit
Inverter Install the wiring conduit and run Inverter-L1,
Inverter-L2, Neutral wire, PE cable, and communication cable through the cable hole.
1 inch conduit

4.2.2 Fa'amatalaga Uea

GOODWE MPD Series Automatic Backup Device - Wiring Specifications

Leai. Vaega Fa'ailoga Fa'amatalaga
1. Inverter communication terminal Inverter COM •    Terminal for connecting the communication cable of the inverter.
•    Recommended specification: RJ45 cable, 24AWG, CAT5e or better.
2. CT terminal for solar inverter •    Terminal for connecting the CT for the solar inverter.
3. CT
4. Inverter terminal Inverter A-L1 / L2, Inverter B-L1 / L2, Inverter C-L1 / L2, Inverter-N •    Terminal for connecting the AC conductor of the inverter.
•    Inverter B and Inverter C are only for MPD series products.
•    Recommended specification: 6-8AWG, copper conductor, 90℃.
5. AC Grid terminal Grid-L1, Grid-L2, Grid-N •    Terminal for connecting the Grid conductor.
•    Recommended specification:
•  4/0AWG, copper conductor, 90℃ for ABD200- 40-US10, ABD200-63-US10, MPD200-40-US10, and MPD200-63-US10.
•  3AWG, copper conductor, 90℃ for ABD100-40- US10 and ABD100-63-US10.
6. AC Loads terminal Load-L1, Load-L2, Load-N •    Terminal for connecting the AC conductor of the load.
•    Recommended specification:
•  4/0AWG, copper conductor, 90℃ for ABD200- 40-US10, ABD200-63-US10, MPD200-40-US10, and MPD200-63-US10.
•  3AWG, copper conductor, 90℃ for ABD100-40- US10 and ABD100-63-US10.
7. Fa'apalapala fa'alalo •    Busbar for connecting the PE cable.
•    Recommended specification:
•  Load-PE: 4-6AWG, copper conductor, 90℃.
•  Inverter-PE: 10AWG, copper conductor, 90℃.

4.3 Opening the Cabinet Door
Step 1 Unlock the cabinet door using the included key.
Step 2 Remove the six screws fixing the insulation board(torque: 0.8Nm).
Step 3 Remove the insulation board.GOODWE MPD Series Automatic Backup Device - Cabinet Door4.4 Connecting the Conductors
lapata'iga 2 LAPATAIGA

  • Connect the conductors to the right terminals like L1, L2, and N. The device may be damaged if the conductors are connected inappropriately.
  • Make sure that the whole conductors are inserted into the terminal holes. No part of the conductor can be exposed.
  • Make sure that the conductors are connected securely. Otherwise, the terminal may get too hot and damage the device.

4.4.1 Connecting the AC Conductors (Grid)
lapata'iga 2 LAPATAIGA
The ac output (neutral) is not bonded to ground.
Step 1 Strip the conductor wiring.
Step 2 Remove the waterproof cover using the included cap removal tool.
Step 3 Insert the desired conduit and corresponding adaptors, fittings, and bushings.
Step 4 Insert the conductors into the device and tighten the conduit.GOODWE MPD Series Automatic Backup Device - Conductors4.4.2 Connecting the AC Conductors (Load)
Step 1 Strip the conductor wiring.
Step 2 Remove the waterproof cover using the included cap removal tool.
Step 3 Insert the desired conduit and corresponding adaptors, fittings, and bushings.
Step 4 Insert the conductors into the device and tighten the conduit.GOODWE MPD Series Automatic Backup Device - Conductors 14.4.3 Connecting the AC Conductors (Inverter)
Step 1 Strip the conductor wiring, crimp the conductor with appropriate wire connector.
Step 2 Remove the waterproof cover using the included cap removal tool.
Step 3 Insert the desired conduit and corresponding adaptors, fittings, and bushings.
Step 4 Insert the conductors into the device and tighten the conduit.GOODWE MPD Series Automatic Backup Device - AC Conductors4.4.4 Feso'ota'i le Uaea Feso'ota'i
Step 1 Prepare a RJ45 network cable and insert it into the terminal.
Step 2 Run the cable through the cable clip and the conduit.GOODWE MPD Series Automatic Backup Device - Communication Cable4.4.5 Connecting the CT Cable (Optional)
FAAALIGA

  • Only for AC coupled inverters.

Laasaga 1 Clamp the CT around the cable to be measured.
Step 2 Insert the CT cable into the terminal block.
Ituaiga 1GOODWE MPD Series Automatic Backup Device - Type 1Ituaiga 2GOODWE MPD Series Automatic Backup Device - Type 24.5 Closing the Cabinet Door
Step 1 Install the insulation board.
Step 2 Tighten the six screws fix the insulation board (torque: 0.8Nm).
Step 3 Optional. Lock up the device using the cabinet key. Keep the key properly for future use.GOODWE MPD Series Automatic Backup Device - Cabinet Door

Fa'atonuga o Meafaigaluega

5.1 Siaki A'o le'i OLA

Leai. Siaki Mea
1 The product is firmly installed at a clean place that is well-ventilated and easy-to- operate.
2 The PE, power, and communication cables are connected correctly and securely.
3 O nonoa uaea o lo'o atoatoa, fa'asolo lelei ma tutusa.
4 Unused ports and terminals are fitted using the waterproof caps.
5 The insulation board is installed properly.
6 Le voltage and frequency at the connection point meet the grid connection requirements.
7 Ua fa'amauina pu o alavai eletise.

5.2 Power ON the Device
Step 1 Turn on the main breaker of the device.
Step 2 Turn on the inverter breaker of the device.

Tausiga

6.1 Power OFF the Device
lapata'iga 2 TALA
FAATONUGA E FAI I SE MATA'AGA O LE MU PO'O LE PILI ELETI

  • Power off the device before operations and maintenance. Otherwise, the device may be damaged or electric shocks may occur.
  • Delayed discharge. Wait until the components are discharged and the LED indicators are off after power off.

Step 1 Turn off the main breaker of the device.
Step 2 Turn off the inverter breaker of the device.
Step 3 Turn off the breaker of the main panel.
Step 4 Power off the inverter.

6.2 Replacing the Inverter Breaker
lapata'iga 2 LAPATAIGA

  • Make sure that the device is powered off.
  • Wear proper personal protective equipment before any operations.

Step 1 Loosen the screws and cables of the breaker.
Step 2 Pull the plastic slot under the breaker.
Step 3 Replace the breaker with a new one, the new breaker shall be AC40A or 63A(60A) and UL489 certified.
Step 4 Place the breaker properly and push the plastic slot. Make sure that the breaker is securely installed.
Step 5 Tighten the cables.

Vaega Fa'atekinisi

7.1 ABD Series Technical Parameters

Fa'amatalaga Fa'atekinisi ABD200- 40-US10 ABD200- 63-US10 ABD100- 40-US10 ABD100- 63-US10
Fa'amatalaga Fa'aeletise
Tulaga Fa'ailo Voltagu (V) 240
Galuega Faatino Voltage Va'aiga (V) 211~264
Feed-in Type Vaeluaina Vaega
Numera AC Voltage of Line Conductor (V) 120/240
Fa'aigoa ole AC (Hz) 60
AC Frequency Range (Hz) 58.5~61.2
Current Rating (From Grid)(A) 200
Max. Continuous Current From Inverter (A) 32 47.5 32 47.5
Maximum Overcurrent Protection of Main Breaker (A)*1 200 100
Maximum Overcurrent Protection of Circuit Breaker of Inverter (A) 40 63 40 63
Fa'amatalaga Lautele
Operating Temperature Range (℉) -13℉~+140℉ (-25℃~+60℃)*2
Max. Operating Altitude (ft) 9842ft (3000m)
Metotia malulu Natura Faʻafeiloaʻiga
Fesootaiga ma Inverter RS485
mamafa (lb) 26lb (12kg)
Dimension (W×H×D in) 17.7×24×5.9 in (450×610×150 mm)
Auala fa'apipi'i Fa'amau i le Pa
Ingress Protection Rating Type 3R, IP44
Tusipasi
Tulafono Faatonutonu o le Saogalemu UL1741, CSA 22.2 No. 107-01
EMC FCC part15 CLASS B
*1: The main breaker is optional.
*2: Derating temperature: 113℉(45℃).

7.2 MPD Series Technical Parameters

Fa'amatalaga Fa'atekinisi MPD200-40-US10 MPD200-63-US10
Fa'amatalaga Fa'aeletise
Tulaga Fa'ailo Voltagu (V) 240
Galuega Faatino Voltage Va'aiga (V) 211~264
Feed-in Type Vaeluaina Vaega
Numera AC Voltage of Line Conductor (V) 120/240
Fa'aigoa ole AC (Hz) 60
AC Frequency Range (Hz) 58.5~61.2
Current Rating (From Grid)(A) 200
Max. Continuous Current From Inverter (A) 32 47.5
Max. Amount of Inverters in Parallel 3
Maximum Overcurrent Protection of Main Breaker (A)*1 200
Maximum Overcurrent Protection of Circuit Breaker of Inverter (A) 40 63
Fa'amatalaga Lautele
Operating Temperature Range (℉) -13℉~+140℉ (-25℃~+60℃)*2
Max. Operating Altitude (ft) 9842ft (3000m)
Metotia malulu Natura Faʻafeiloaʻiga
Fesootaiga ma Inverter RS485
mamafa (lb) 30lb (13.5kg)
Dimension (W×H×D in) 17.7×24×5.9 in (450×610×150 mm)
Auala fa'apipi'i Fa'amau i le Pa
Ingress Protection Rating Type 3R, IP44
Tusipasi
Tulafono Faatonutonu o le Saogalemu UL1741, CSA 22.2 No. 107-01
EMC FCC part15 CLASS B
*1: The main breaker is optional.
*2: Derating temperature: 113℉(45℃).

GOODWE MPD Series Automatic Backup Device - qr codehttps://en.goodwe.com/GOODWE MPD Series Automatic Backup Device - qr code 1https://en.goodwe.com/contact-us.aspGOODWE MPD Series Automatic Backup Device - qr code 2340-00797-04

GoodWe Technologies Co., Ltd.
GOODWE MPD Series Automatic Backup Device - icon 5 Nu. 90 Zijin Rd., Itumalo Fou, Suzhou, 215011, Saina
TVONE 1RK SPDR PWR Spider Power Module - Ata 2 www.goodwe.com
TVONE 1RK SPDR PWR Spider Power Module - Ata 3 service@goodwe.com

Pepa / Punaoa

GOODWE MPD Series Automatic Backup Device [pdf] Fa'atonu Taiala
ABD200-40-US10, ABD200-63-US10, ABD100-40-US10, ABD100-63-US10, MPD200-40-US10, MPD200-63-US10, MPD Series Automatic Backup Device, MPD Series, Automatic Backup Device, Backup Device

Fa'asinomaga

Tuu se faamatalaga

E le fa'asalalauina lau tuatusi imeli. Fa'ailogaina fanua mana'omia *