ENGO контроли EFAN-24 PWM контролер за брзина на вентилаторот
Спецификации
- Протокол: MODBUS RTU
- Модел на контролер: EFAN-24
- Комуникациски интерфејс: RS485
- Опсег на адреси: 1-247
- Големина на податоци: 32-битни
Упатство за употреба на производот
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Големина на податоци: 2 бајти по MODBUS регистар на податоци
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
Општи информации
Општи информации за MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Не може да се поврзат повеќе од две жици на секој терминал, осигурувајќи дека се користи конфигурација „Daisy Chain“ (во серија) или „права линија“ (директна). Ѕвезда или мрежна (отворена) врска не се препорачува, бидејќи рефлексиите во кабелот може да предизвикаат оштетување на податоците.
Конфигурација
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
ВНИМАНИЕ:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
Работа на мрежата MODBUS RTU – Режим на робови
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Овозможува пристап до сите tags and data used in the controller’s ladder program.
- 8-битна slave адреса
- 32-битна големина на податоци (1 адреса = 32-битна враќање на податоци)
- Each MODBUS data register has a size of 2 bytes.
ВНИМАНИЕ:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
ВНИМАНИЕ:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Авторски права – Овој документ може да се репродуцира и дистрибуира само со експлицитна дозвола на Engo Controls и може да се обезбеди само на овластени лица или компании со потребната техничка експертиза.
поставки за комуникација
Поставки за комуникација RS-485
Pxx | Функција | Вредност | Опис | Стандардно вредност |
Адресар | MODBUS Slave адреса на уред (ID). | 1 – 247 | MODBUS Slave адреса на уред (ID). | 1 |
BAUD |
Бауд |
4800 |
Брзина на битови (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
ПАРИ |
Бит за паритет – поставува паритет на податоците за откривање грешки |
Никој | Никој |
Никој |
Дури и | Дури и | |||
Чудно | Чудно | |||
СТОП | СтопБит | 1 | 1 стоп бит | 1 |
2 | 2 стоп бит |
Ги поддржува следните функционални кодови:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
INPUT регистри – само за читање
Адреса | Пристап | Опис | Опсег на вредности | Средства | Стандардно | |
Дек | Хекс | |||||
0 | 0x0000 | R (#03) | Engo MODBUS Model ID | 1-247 | MODBUS Slave (ID) | 1 |
1 | 0x0001 | R (#03) | Верзија на фирмвер | 0х0001-0х9999 | 0x1110=1.1.10 (BCD код) | |
2 |
0x0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0x0003 | R (#03) | Вредност на интегрираниот сензор за температура, °C | 50 – 500 | N-> температура=N/10 °C | |
5 |
0x0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0x0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0x0007 |
R (#03) |
Навивачка држава |
0b00000000 – 0b00001111 |
0b00000000= OFF
0b00000001= I Fan stage низок 0b00000010= II Вентилатор stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0x0008 | R (#03) | Valve 1 stat | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0x0009 | R (#03) | Valve 2 state | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0x000A | R (#03) | Humidity measurement (with 5% indication accuracy) | 0 – 100 | N-> humidity=N % |
HOLDING регистри – за читање и пишување
Адреса | Пристап | Опис | Опсег на вредности | Средства | Стандардно | |
Дек | Хекс | |||||
0 | 0x0000 | R/W (#04) | Engo MODBUS Model ID | 1-247 | MODBUS Slave (ID) | 1 |
234 |
0x00EA |
R/W (#06) |
Тип на фенкоил |
1 – 6 |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 цевки – подно греење и ладење со фенкоил |
0 |
235 |
0x00EB |
R/W (#06) |
Конфигурација на влез S1-COM (Параметри на инсталерот -P01) |
0 | Внесувањето е неактивен. Променете помеѓу греење и ладење со копчињата. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode – S1-COM скратен –> COOL режим |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Контролорот се префрла помеѓу греењето и режими на ладење врз основа на температурата на цевката поставена во параметрите P17 и P18. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Активирање на подниот сензор во конфигурацијата за подно греење. | |||||
236 |
0x00EC |
R/W (#06) |
Конфигурација на влез S2-COM (Параметри на инсталерот -P02) |
0 | Внесувањето е оневозможено |
0 |
1 | Сензор за зафаќање (кога се отвораат контактите, активирајте го ECO режимот) | |||||
2 | Надворешен сензор за температура | |||||
237 |
0х00ЕД |
R/W (#06) |
Може да се избере ECO режим (Параметри на инсталаторот -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00EE | R/W (#06) | Вредност на температурата на режимот ЕКО за греење (Параметри на инсталаторот -P08) | 50 – 450 | N-> температура=N/10 °C | 150 |
239 | 0x00EF | R/W (#06) | Вредност на температурата на режимот ECO за ладење (Параметри на инсталаторот -P09) | 50 – 450 | N-> температура=N/10 °C | 300 |
240 |
0x00F0 |
R/W (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 |
N-> температура=N/10 °C |
10 |
241 |
0x00F1 |
R/W (#06) |
Температура на вентилаторот за греење
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0 – 50 |
N-> температура=N/10 °C |
50 |
Адреса | Пристап | Опис | Опсег на вредности | Средства | Стандардно | |||
Дек | Хекс | |||||||
242 |
0x00F2 |
R/W (#06) |
Контролен алгоритам
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0 – 20 |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00F3 |
R/W (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Параметри на инсталаторот -P16) |
5 – 50 |
N-> температура=N/10 °C |
20 |
||
244 |
0x00F4 |
R/W (#06) |
Вентилатор на температура за ладење.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0 – 50 |
N-> температура=N/10 °C |
50 |
||
245 | 0x00F5 | R/W (#06) | Вредност на хистерезис за вентилот за ладење (Параметри на инсталаторот -P20) | 1 – 20 | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00F6 |
R/W (#06) |
Мртва зона на прекинувачко греење/ладење
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Параметри на инсталаторот -P21) |
5 – 50 |
N-> температура=N/10 °C |
20 |
||
247 |
0x00F7 |
R/W (#06) |
Вредноста на температурата на префрлување од греење до ладење
– Систем со 2 цевки. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270 – 400 |
N-> температура=N/10 °C |
300 |
||
248 |
0x00F8 |
R/W (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100 – 250 |
N-> температура=N/10 °C |
100 |
||
249 |
0x00F9 |
R/W (#06) |
Доцнење на ладењето ВКЛУЧЕНО.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0 – 15 мин |
0 |
|||
250 |
0x00FA |
R/W (#06) |
Максимална температура на подот
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Параметри на инсталаторот -P25) |
50 – 450 |
N-> температура=N/10 °C |
350 |
||
251 |
0x00FB |
R/W (#06) |
Минимална температура на подот
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50 – 450 |
N-> температура=N/10 °C |
150 |
||
254 | 0x00FE | R/W (#06) | ПИН-код за поставките на инсталерот (Параметри на инсталерот -P28) | 0 – 1 | 0 = оневозможено
1 = PIN (First default code 0000) |
0 |
Адреса | Пристап | Опис | Опсег на вредности | Средства | Стандардно | |
Дек | Хекс | |||||
255 | 0x00FF | R/W (#06) | Потребна е PIN-код за отклучување на клучевите (Параметри на инсталерот -P29) | 0 – 1 | 0 = NIE
1 = TAK |
0 |
256 |
0x0100 |
R/W (#06) |
Работа со вентилатор (Параметри на инсталаторот - FAN) |
0 – 1 |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = ДА |
1 |
257 | 0x0101 | R/W (#06) | Вклучување/исклучување – исклучување на регулаторот | 0,1 | 0 = ИСКЛУЧЕН
1=ВКЛУЧЕНО |
1 |
258 |
0x0102 |
R/W (#06) |
Режим на работа |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0x0104 |
R/W (#06) |
Поставување брзина на вентилаторот |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0x0106 | R/W (#06) | Заклучување со клучеви | 0,1 | 0=отклучен 1=Заклучен | 0 |
263 | 0x0107 | R/W (#06) | Осветленост на екранот (Параметри на инсталаторот -P27) | 0-100 | N-> Осветленост = N% | 30 |
268 | 0х010С | R/W (#06) | Clock – minutes | 0-59 | Минути | 0 |
269 | 0x010D | R/W (#06) | Clock – hours | 0-23 | Часови | 0 |
270 | 0x010E | R/W (#06) | Clock – Day of the week (1=Monday) | 1~7 | Ден во неделата | 3 |
273 | 0x0111 | R/W (#06) | Set the temperature in schedule mode | 50-450 | N-> температура=N/10 °C | 210 |
274 | 0x0112 | R/W (#06) | Set temperature in manual mode | 50-450 | N-> температура=N/10 °C | 210 |
275 | 0x0113 | R/W (#06) | Set the temperature in FROST mode | 50 | N-> температура=N/10 °C | 50 |
279 | 0x0117 | R/W (#06) | Максимална зададена температура | 50-450 | N-> температура=N/10 °C | 350 |
280 | 0x0118 | R/W (#06) | Минимална зададена температура | 50-450 | N-> температура=N/10 °C | 50 |
284 | 0х011С | R/W (#06) | Accuracy of displayed temperature | 1, 5 | N-> температура=N/10 °C | 1 |
285 | 0x011D | R/W (#06) | Корекција на прикажаната температура | -3.0… 3.0°C | in steps of 0.5 | 0 |
288 | 0x0120 | R/W (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = Греење
1 = Ладење |
0 |
291 | 0x0123 | R/W (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 | N-> брзина=N % | 10 |
292 | 0x0124 | R/W (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 | N-> брзина=N % | 90 |
293 | 0x0125 | R/W (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 | N-> брзина=N % | 30 |
294 | 0x0126 | R/W (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 | N-> брзина=N % | 60 |
295 | 0x0127 | R/W (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 | N-> брзина=N % | 90 |
Најчесто поставувани прашања
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.