ENGO Controls EFAN-24 PWM Fan Speed Controller
Spesifikasies
- Protokol: MODBUS RTU
- Beheerdermodel: EFAN-24
- Kommunikasie-koppelvlak: RS485
- Adresreeks: 1-247
- Datagrootte: 32-bis
Produkgebruiksinstruksies
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Data Size: 2 bytes per MODBUS data register
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
Algemene inligting
Algemene inligting oor MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Nie meer as twee drade kan aan elke terminaal gekoppel word nie, en verseker dat 'n "Daisy Chain" (in serie) of "reguitlyn" (direk) konfigurasie gebruik word. Ster- of netwerk (oop) verbinding word nie aanbeveel nie, aangesien weerkaatsings binne die kabel datakorrupsie kan veroorsaak.
Konfigurasie
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
AANDAG:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
MODBUS RTU-netwerkwerking – Slaafmodus
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Laat toegang tot almal toe tags and data used in the controller’s ladder program.
- 8-bis slaaf adres
- 32-bis datagrootte (1 adres = 32-bis dataterugsending)
- Each MODBUS data register has a size of 2 bytes.
AANDAG:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
AANDAG:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Kopiereg – Hierdie dokument mag slegs gereproduseer en versprei word met die uitdruklike toestemming van Engo Controls en mag slegs aan gemagtigde persone of maatskappye met die vereiste tegniese kundigheid verskaf word.
kommunikasie instellings
RS-485 kommunikasie instellings
Pxx | Funksie | Waarde | Beskrywing | Verstek waarde |
addr | MODBUS Slaaf toestel adres (ID). | 1 – 247 | MODBUS Slaaf toestel adres (ID). | 1 |
BAUD |
Baud |
4800 |
Bitsnelheid (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
PARI |
Pariteitsbis – stel datapariteit vir foutopsporing |
Geen | Geen |
Geen |
Selfs | Selfs | |||
Vreemd | Vreemd | |||
STOP | StopBit | 1 | 1 stop bietjie | 1 |
2 | 2 stop bietjie |
Ondersteun die volgende funksiekodes:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
INSET registers – leesalleen
Adres | Toegang | Beskrywing | Waardereeks | Beteken | Verstek | |
Des | Heks | |||||
0 | 0x0000 | R (#03) | Engo MODBUS Model ID | 1-247 | MODBUS Slaaf (ID) | 1 |
1 | 0x0001 | R (#03) | Firmware-weergawe | 0x0001-0x9999 | 0x1110=1.1.10 (BCD-kode) | |
2 |
0x0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0x0003 | R (#03) | Waarde van die Geïntegreerde temperatuursensor, °C | 50 – 500 | N-> temp=N/10 °C | |
5 |
0x0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0x0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0x0007 |
R (#03) |
Aanhangerstaat |
0b00000000 – 0b00001111 |
0b00000000= OFF
0b00000001= I Fan stage laag 0b00000010= II Waaier stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0x0008 | R (#03) | Valve 1 stat | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0x0009 | R (#03) | Valve 2 state | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0x000A | R (#03) | Humidity measurement (with 5% indication accuracy) | 0 – 100 | N-> humidity=N % |
HOU registers – vir lees en skryf
Adres | Toegang | Beskrywing | Waardereeks | Beteken | Verstek | |
Des | Heks | |||||
0 | 0x0000 | R/W (#04) | Engo MODBUS Model ID | 1-247 | MODBUS Slaaf (ID) | 1 |
234 |
0x00EA |
R/W (#06) |
Tipe waaierspiraal |
1 – 6 |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 pype – ondervloerse verhitting en verkoeling deur middel van waaierspiraal |
0 |
235 |
0x00EB |
R/W (#06) |
S1-COM input configuration (Installer Parameters -P01) |
0 | Invoer onaktief. Wissel tussen verhitting en verkoeling met die knoppies. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode – S1-COM kortgesluit –> KOELmodus |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Die beheerder skakel tussen verhitting en verkoelingsmodusse gebaseer op die pyptemperatuur wat in parameters P17 en P18 gestel is. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Aktivering van die vloersensor in die vloerverhittingskonfigurasie. | |||||
236 |
0x00EC |
R/W (#06) |
S2-COM input configuration (Installer Parameters -P02) |
0 | Invoer gedeaktiveer |
0 |
1 | Besettingsensor (aktiveer ECO-modus wanneer kontakte oopgemaak word) | |||||
2 | Eksterne temperatuursensor | |||||
237 |
0x00ED |
R/W (#06) |
Kiesbare ECO-modus (Installeerderparameters -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00 EE | R/W (#06) | ECO-modus temperatuurwaarde vir verhitting (Installeerderparameters -P08) | 50 – 450 | N-> temp=N/10 °C | 150 |
239 | 0x00EF | R/W (#06) | ECO-modus temperatuurwaarde vir verkoeling (Installeerderparameters -P09) | 50 – 450 | N-> temp=N/10 °C | 300 |
240 |
0x00F0 |
R/W (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 |
N-> temp=N/10 °C |
10 |
241 |
0x00F1 |
R/W (#06) |
Fan on temperature for heating
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0 – 50 |
N-> temp=N/10 °C |
50 |
Adres | Toegang | Beskrywing | Waardereeks | Beteken | Verstek | |||
Des | Heks | |||||||
242 |
0x00F2 |
R/W (#06) |
Beheer algoritme
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0 – 20 |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00F3 |
R/W (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Installeerderparameters -P16) |
5 – 50 |
N-> temp=N/10 °C |
20 |
||
244 |
0x00F4 |
R/W (#06) |
Waaier op temperatuur vir verkoeling.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0 – 50 |
N-> temp=N/10 °C |
50 |
||
245 | 0x00F5 | R/W (#06) | Histeresewaarde vir die verkoelingsklep (Installeerderparameters -P20) | 1 – 20 | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00F6 |
R/W (#06) |
Dooie sone van skakeling tussen verhitting/verkoeling
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Installeerderparameters -P21) |
5 – 50 |
N-> temp=N/10 °C |
20 |
||
247 |
0x00F7 |
R/W (#06) |
Die oorskakeltemperatuurwaarde van verhitting na verkoeling
– 2-pypstelsel. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270 – 400 |
N-> temp=N/10 °C |
300 |
||
248 |
0x00F8 |
R/W (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100 – 250 |
N-> temp=N/10 °C |
100 |
||
249 |
0x00F9 |
R/W (#06) |
Verkoeling AAN-vertraging.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0 – 15 min |
0 |
|||
250 |
0x00FA |
R/W (#06) |
Maksimum vloertemperatuur
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Installeerderparameters -P25) |
50 – 450 |
N-> temp=N/10 °C |
350 |
||
251 |
0x00fb |
R/W (#06) |
Minimum vloer temperatuur
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50 – 450 |
N-> temp=N/10 °C |
150 |
||
254 | 0x00FE | R/W (#06) | PIN-kode vir installeerderinstellings (Installeerderparameters -P28) | 0 – 1 | 0 = gedeaktiveer
1 = PIN (First default code 0000) |
0 |
Adres | Toegang | Beskrywing | Waardereeks | Beteken | Verstek | |
Des | Heks | |||||
255 | 0x00FF | R/W (#06) | Vereis 'n PIN-kode om die sleutels te ontsluit (Installeerderparameters -P29) | 0 – 1 | 0 = NIE
1 = TAK |
0 |
256 |
0x0100 |
R/W (#06) |
Waaierwerking (Installeerderparameters -WAAIER) |
0 – 1 |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = JA |
1 |
257 | 0x0101 | R/W (#06) | Aan/af – skakel die reguleerder af | 0,1 | 0 = AF
1 = AAN |
1 |
258 |
0x0102 |
R/W (#06) |
Bedryfsmodus |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0x0104 |
R/W (#06) |
Fan spoed instelling |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0x0106 | R/W (#06) | Sleutelslot | 0,1 | 0=ontsluit 1=Gesluit | 0 |
263 | 0x0107 | R/W (#06) | Helderheid van skerm (Installeerderparameters -P27) | 0-100 | N-> Helderheid =N% | 30 |
268 | 0x010C | R/W (#06) | Clock – minutes | 0-59 | Minute | 0 |
269 | 0x010d | R/W (#06) | Clock – hours | 0-23 | Ure | 0 |
270 | 0x010E | R/W (#06) | Clock – Day of the week (1=Monday) | 1~7 | Dag van die week | 3 |
273 | 0x0111 | R/W (#06) | Set the temperature in schedule mode | 50-450 | N-> temp=N/10 °C | 210 |
274 | 0x0112 | R/W (#06) | Set temperature in manual mode | 50-450 | N-> temp=N/10 °C | 210 |
275 | 0x0113 | R/W (#06) | Set the temperature in FROST mode | 50 | N-> temp=N/10 °C | 50 |
279 | 0x0117 | R/W (#06) | Maksimum ingestelde temperatuur | 50-450 | N-> temp=N/10 °C | 350 |
280 | 0x0118 | R/W (#06) | Minimum setpoint temperatuur | 50-450 | N-> temp=N/10 °C | 50 |
284 | 0x011C | R/W (#06) | Accuracy of displayed temperature | 1, 5 | N-> temp=N/10 °C | 1 |
285 | 0x011d | R/W (#06) | Regstelling van die vertoonde temperatuur | -3.0… 3.0°C | in steps of 0.5 | 0 |
288 | 0x0120 | R/W (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = Verhitting
1 = Verkoeling |
0 |
291 | 0x0123 | R/W (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 | N-> speed=N % | 10 |
292 | 0x0124 | R/W (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 | N-> speed=N % | 90 |
293 | 0x0125 | R/W (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 | N-> speed=N % | 30 |
294 | 0x0126 | R/W (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 | N-> speed=N % | 60 |
295 | 0x0127 | R/W (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 | N-> speed=N % | 90 |
Gereelde vrae
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.
Dokumente / Hulpbronne
![]() |
ENGO Controls EFAN-24 PWM Fan Speed Controller [pdf] Instruksiehandleiding EFAN-230B, EFAN-230W, EFAN-24 PWM Fan Speed Controller, EFAN-24, PWM Fan Speed Controller, Fan Speed Controller, Speed Controller |