ENGO Controls EFAN-24 PWM ventilatorhastighedsregulator
Specifikationer
- Protokol: MODBUS RTU
- Controller Model: EFAN-24
- Kommunikationsgrænseflade: RS485
- Adresseområde: 1-247
- Datastørrelse: 32-bit
Produktbrugsvejledning
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Datastørrelse: 2 bytes pr. MODBUS-dataregister
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
Generel information
Generel information om MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Der kan ikke tilsluttes mere end to ledninger til hver terminal, hvilket sikrer, at der bruges en "Daisy Chain" (i serie) eller "lige linje" (direkte) konfiguration. Stjerne- eller netværksforbindelse (åben) anbefales ikke, da refleksioner i kablet kan forårsage datakorruption.
Konfiguration
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
OPMÆRKSOMHED:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
MODBUS RTU netværksdrift – Slavetilstand
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Giver adgang til alle tags and data used in the controller’s ladder program.
- 8-bit slaveadresse
- 32-bit datastørrelse (1 adresse = 32-bit dataretur)
- Each MODBUS data register has a size of 2 bytes.
OPMÆRKSOMHED:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
OPMÆRKSOMHED:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Copyright – Dette dokument må kun reproduceres og distribueres med udtrykkelig tilladelse fra Engo Controls og må kun udleveres til autoriserede personer eller virksomheder med den nødvendige tekniske ekspertise.
kommunikationsindstillinger
RS-485 kommunikationsindstillinger
Pxx | Fungere | Værdi | Beskrivelse | Misligholdelse værdi |
adr | MODBUS Slave-enhedsadresse (ID). | 1 – 247 | MODBUS Slave-enhedsadresse (ID). | 1 |
BAUD |
Baud |
4800 |
Bitrate (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
PARI |
Paritetsbit – indstiller dataparitet til fejldetektion |
Ingen | Ingen |
Ingen |
Endog | Endog | |||
Ulige | Ulige | |||
STOP | StopBit | 1 | 1 stop bit | 1 |
2 | 2 stop bit |
Understøtter følgende funktionskoder:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
INPUT-registre – skrivebeskyttet
Adresse | Adgang | Beskrivelse | Værdiinterval | Midler | Misligholdelse | |
dec | Hex | |||||
0 | 0x0000 | R (#03) | Engo MODBUS Model ID | 1-247 | MODBUS-slave (ID) | 1 |
1 | 0x0001 | R (#03) | Firmware-version | 0x0001-0x9999 | 0x1110=1.1.10 (BCD-kode) | |
2 |
0x0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0x0003 | R (#03) | Værdien af den integrerede temperaturføler, °C | 50 – 500 | N-> temp=N/10 °C | |
5 |
0x0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0x0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0x0007 |
R (#03) |
Ventilatortilstand |
0b00000000 – 0b00001111 |
0b00000000= OFF
0b00000001= I Fan stage lav 0b00000010= II Ventilator stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0x0008 | R (#03) | Valve 1 stat | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0x0009 | R (#03) | Valve 2 state | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0x000A | R (#03) | Humidity measurement (with 5% indication accuracy) | 0 – 100 | N-> humidity=N % |
HOLDING registre – til læsning og skrivning
Adresse | Adgang | Beskrivelse | Værdiinterval | Midler | Misligholdelse | |
dec | Hex | |||||
0 | 0x0000 | R/W (#04) | Engo MODBUS Model ID | 1-247 | MODBUS-slave (ID) | 1 |
234 |
0x00EA |
R/W (#06) |
Fancoil type |
1 – 6 |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 rør – gulvvarme & køling med fancoil |
0 |
235 |
0x00EB |
R/W (#06) |
S1-COM-indgangskonfiguration (Installationsparametre -P01) |
0 | Input inaktivt. Skift mellem opvarmning og køling med knapperne. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode – S1-COM kortsluttet –> COOL-tilstand |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Styringen skifter mellem opvarmning og køletilstande baseret på rørtemperaturen indstillet i parametrene P17 og P18. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Aktivering af gulvføleren i gulvvarmekonfigurationen. | |||||
236 |
0x00EC |
R/W (#06) |
S2-COM-indgangskonfiguration (Installationsparametre -P02) |
0 | Input deaktiveret |
0 |
1 | Tilstedeværelsessensor (når kontakter åbnes, aktiver ECO-tilstand) | |||||
2 | Ekstern temperaturføler | |||||
237 |
0x00ED |
R/W (#06) |
Valgbar ECO-tilstand (installatørparametre -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00EE | R/W (#06) | ECO-tilstand temperaturværdi for opvarmning (installatørparametre -P08) | 50 – 450 | N-> temp=N/10 °C | 150 |
239 | 0x00EF | R/W (#06) | ECO-tilstand temperaturværdi for køling (installatørparametre -P09) | 50 – 450 | N-> temp=N/10 °C | 300 |
240 |
0x00F0 |
R/W (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 |
N-> temp=N/10 °C |
10 |
241 |
0x00F1 |
R/W (#06) |
Ventilatortemperatur til opvarmning
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0 – 50 |
N-> temp=N/10 °C |
50 |
Adresse | Adgang | Beskrivelse | Værdiinterval | Midler | Misligholdelse | |||
dec | Hex | |||||||
242 |
0x00F2 |
R/W (#06) |
Kontrolalgoritme
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0 – 20 |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00F3 |
R/W (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Installationsparametre -P16) |
5 – 50 |
N-> temp=N/10 °C |
20 |
||
244 |
0x00F4 |
R/W (#06) |
Ventilator på temperatur til afkøling.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0 – 50 |
N-> temp=N/10 °C |
50 |
||
245 | 0x00F5 | R/W (#06) | Hystereseværdi for køleventilen (installatørparametre -P20) | 1 – 20 | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00F6 |
R/W (#06) |
Død zone for omskiftning af varme/køling
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Installationsparametre -P21) |
5 – 50 |
N-> temp=N/10 °C |
20 |
||
247 |
0x00F7 |
R/W (#06) |
Skifttemperaturværdien fra opvarmning til afkøling
– 2-rørssystem. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270 – 400 |
N-> temp=N/10 °C |
300 |
||
248 |
0x00F8 |
R/W (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100 – 250 |
N-> temp=N/10 °C |
100 |
||
249 |
0x00F9 |
R/W (#06) |
Køling TIL forsinkelse.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0 – 15 min |
0 |
|||
250 |
0x00FA |
R/W (#06) |
Maksimal gulvtemperatur
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Installationsparametre -P25) |
50 – 450 |
N-> temp=N/10 °C |
350 |
||
251 |
0x00FB |
R/W (#06) |
Minimum gulvtemperatur
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50 – 450 |
N-> temp=N/10 °C |
150 |
||
254 | 0x00FE | R/W (#06) | PIN-kode til installatørindstillinger (installatørparametre -P28) | 0 – 1 | 0 = deaktiveret
1 = PIN (First default code 0000) |
0 |
Adresse | Adgang | Beskrivelse | Værdiinterval | Midler | Misligholdelse | |
dec | Hex | |||||
255 | 0x00FF | R/W (#06) | Kræver en PIN-kode for at låse nøglerne op (installatørparametre -P29) | 0 – 1 | 0 = NIE
1 = TAK |
0 |
256 |
0x0100 |
R/W (#06) |
Ventilatordrift (installatørparametre -FAN) |
0 – 1 |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = JA |
1 |
257 | 0x0101 | R/W (#06) | Tænd/sluk – slukker for regulatoren | 0,1 | 0 = FRA
1=TIL |
1 |
258 |
0x0102 |
R/W (#06) |
Driftstilstand |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0x0104 |
R/W (#06) |
Indstilling af blæserhastighed |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0x0106 | R/W (#06) | Nøglelås | 0,1 | 0=ulåst 1=Låst | 0 |
263 | 0x0107 | R/W (#06) | Skærmens lysstyrke (installatørparametre -P27) | 0-100 | N-> Lysstyrke =N% | 30 |
268 | 0x010C | R/W (#06) | Clock – minutes | 0-59 | Referat | 0 |
269 | 0x010D | R/W (#06) | Clock – hours | 0-23 | Timer | 0 |
270 | 0x010E | R/W (#06) | Clock – Day of the week (1=Monday) | 1~7 | Ugedag | 3 |
273 | 0x0111 | R/W (#06) | Set the temperature in schedule mode | 50-450 | N-> temp=N/10 °C | 210 |
274 | 0x0112 | R/W (#06) | Set temperature in manual mode | 50-450 | N-> temp=N/10 °C | 210 |
275 | 0x0113 | R/W (#06) | Set the temperature in FROST mode | 50 | N-> temp=N/10 °C | 50 |
279 | 0x0117 | R/W (#06) | Maksimal sætpunktstemperatur | 50-450 | N-> temp=N/10 °C | 350 |
280 | 0x0118 | R/W (#06) | Minimum sætpunktstemperatur | 50-450 | N-> temp=N/10 °C | 50 |
284 | 0x011C | R/W (#06) | Accuracy of displayed temperature | 1, 5 | N-> temp=N/10 °C | 1 |
285 | 0x011D | R/W (#06) | Korrektion af den viste temperatur | -3.0…3.0°C | in steps of 0.5 | 0 |
288 | 0x0120 | R/W (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = Opvarmning
1 = Køling |
0 |
291 | 0x0123 | R/W (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 | N-> hastighed=N % | 10 |
292 | 0x0124 | R/W (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 | N-> hastighed=N % | 90 |
293 | 0x0125 | R/W (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 | N-> hastighed=N % | 30 |
294 | 0x0126 | R/W (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 | N-> hastighed=N % | 60 |
295 | 0x0127 | R/W (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 | N-> hastighed=N % | 90 |
FAQ
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.
Dokumenter/ressourcer
![]() |
ENGO Controls EFAN-24 PWM ventilatorhastighedsregulator [pdf] Brugsanvisning EFAN-230B, EFAN-230W, EFAN-24 PWM ventilatorhastighedsregulator, EFAN-24, PWM ventilatorhastighedsregulator, Ventilatorhastighedsregulator, Hastighedsregulator |