ENGO Controls EFAN-24 PWM Ntxuam Ceev Controller
Specifications
- raws tu qauv: MODBUS RTU
- Tus Qauv Zauv: EFAN-24
- Kev sib txuas lus Interface: RS485
- Chaw nyob: 1-247
- Cov ntaub ntawv loj: 32-ntsis
Cov lus qhia siv khoom
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Cov ntaub ntawv loj: 2 bytes ib MODBUS cov ntaub ntawv sau npe
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
Cov ntaub ntawv dav dav
Cov ntaub ntawv dav dav txog MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Tsis pub ntau tshaj ob lub xov hlau tuaj yeem txuas mus rau txhua lub davhlau ya nyob twg, kom ntseeg tau tias siv "Daisy Chain" (hauv series) lossis "txoj kab ncaj nraim" (direct) teeb tsa. Lub hnub qub lossis lub network (qhib) kev sib txuas tsis pom zoo, vim tias qhov kev xav hauv lub cable tuaj yeem ua rau cov ntaub ntawv tsis raug cai.
Kev teeb tsa
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
CEEB TOOM:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
MODBUS RTU network ua haujlwm - hom qhev
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Tso cai nkag mus rau txhua tus tags and data used in the controller’s ladder program.
- 8-ntsis qhev chaw nyob
- 32-ntsis cov ntaub ntawv loj (1 chaw nyob = 32-ntsis cov ntaub ntawv rov qab)
- Each MODBUS data register has a size of 2 bytes.
CEEB TOOM:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
CEEB TOOM:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Copyright - Cov ntaub ntawv no tsuas yog muab luam tawm thiab xa tawm nrog kev tso cai ntawm Engo Controls thiab tsuas yog muab rau cov neeg tau tso cai lossis cov tuam txhab uas xav tau kev txawj ntse.
teeb tsa kev sib txuas lus
RS-485 kev sib txuas lus teeb tsa
Pxx | Muaj nuj nqi | Tus nqi | Kev piav qhia | Default tus nqi |
Ntxiv | MODBUS Slave device address (ID). | 1–247 : kuv | MODBUS Slave device address (ID). | 1 |
BAUD |
Baud |
4800 |
Bitrate (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
PARI |
Parity ntsis - teeb tsa cov ntaub ntawv sib luag rau kev tshawb pom qhov yuam kev |
Tsis muaj | Tsis muaj |
Tsis muaj |
Txawm | Txawm | |||
khib | khib | |||
TSIS TAU | StopBit | 1 | 1 nres bit | 1 |
2 | 2 nres bit |
Txhawb cov lej ua haujlwm hauv qab no:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
INPUT cov ntawv sau npe - nyeem nkaus xwb
Chaw nyob | Nkag mus | Kev piav qhia | Tus nqi ntau | txhais tau tias | Default | |
Dec | Hex | |||||
0 | 0 x 0000 | R (#03) | Engo MODBUS Model ID | 1-247 : kuv | MODBUS Slave (ID) | 1 |
1 | 0 x 0001 | R (#03) | Firmware-Version | 0x0001x 0 | 0x1110 = 1.1.10 (BCD code) | |
2 |
0 x 0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0 x 0003 | R (#03) | Tus nqi ntawm Integrated kub sensor, ° C | 50–500 : kuv | N-> temp = N / 10 ° C | |
5 |
0 x 0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50–500 : kuv |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0 x 0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50–500 : kuv |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0 x 0007 |
R (#03) |
Fan xeev |
0b00000000 – 0b00001111 ua |
0b00000000= OFF
0b00000001= I Fan stage low 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0 x 0008 | R (#03) | Valve 1 stat | 0–1000 : kuv | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0 x 0009 | R (#03) | Valve 2 state | 0–1000 : kuv | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0 x000a | R (#03) | Humidity measurement (with 5% indication accuracy) | 0–100 : kuv | N-> humidity=N % |
HOLDING cov ntawv sau npe - rau kev nyeem ntawv thiab sau ntawv
Chaw nyob | Nkag mus | Kev piav qhia | Tus nqi ntau | txhais tau tias | Default | |
Dec | Hex | |||||
0 | 0 x 0000 | R/W (#04) | Engo MODBUS Model ID | 1-247 : kuv | MODBUS Slave (ID) | 1 |
234 |
0x00 ua |
R/W (#06) |
Hom Fancoil |
1–6 : kuv |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 yeeb nkab - underfloor cua sov & cua txias los ntawm fancoil |
0 |
235 |
0x00 ib |
R/W (#06) |
S1-COM input configuration (Installer Parameters -P01) |
0 | Input inactive. Hloov ntawm cua sov thiab txias nrog cov nyees khawm. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode - S1-COM luv -> COOL hom |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Tus maub los hloov ntawm cov cua sov thiab hom cua txias raws li cov yeeb nkab kub tau teeb tsa hauv qhov ntsuas P17 thiab P18. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Ua kom lub hauv pem teb sensor nyob rau hauv pem teb cua sov configuration. | |||||
236 |
0 x00ec |
R/W (#06) |
S2-COM input configuration (Installer Parameters -P02) |
0 | Kev nkag tsis tau |
0 |
1 | Nyob sensor (thaum qhib kev sib cuag, qhib ECO hom) | |||||
2 | Sab nraud kub sensor | |||||
237 |
0 x00ed |
R/W (#06) |
Xaiv tau ECO hom (Installer Parameters -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00 ua | R/W (#06) | ECO hom kub tus nqi rau cua sov (Installer tsis -P08) | 50–450 : kuv | N-> temp = N / 10 ° C | 150 |
239 | 0x00 ua | R/W (#06) | ECO hom kub tus nqi rau txias (Installer tsis -P09) | 50–450 : kuv | N-> temp = N / 10 ° C | 300 |
240 |
0x00f 0 |
R/W (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 : kuv |
N-> temp = N / 10 ° C |
10 |
241 |
0x00f 1 |
R/W (#06) |
Ntxuam ntawm qhov kub thiab txias rau cua sov
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0–50 : kuv |
N-> temp = N / 10 ° C |
50 |
Chaw nyob | Nkag mus | Kev piav qhia | Tus nqi ntau | txhais tau tias | Default | |||
Dec | Hex | |||||||
242 |
0x00f 2 |
R/W (#06) |
Tswj algorithm
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0–20 : kuv |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00f 3 |
R/W (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Installer parameters -P16) |
5–50 : kuv |
N-> temp = N / 10 ° C |
20 |
||
244 |
0x00f 4 |
R/W (#06) |
Ntxuam ntawm qhov kub kom txias.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0–50 : kuv |
N-> temp = N / 10 ° C |
50 |
||
245 | 0x00f 5 | R/W (#06) | Hysteresis tus nqi rau qhov txias valve (Installer tsis -P20) | 1–20 : kuv | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00f 6 |
R/W (#06) |
Qhov chaw tuag ntawm kev hloov cua sov / cua txias
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Installer parameters -P21) |
5–50 : kuv |
N-> temp = N / 10 ° C |
20 |
||
247 |
0x00f 7 |
R/W (#06) |
Hloov qhov ntsuas kub ntawm qhov cua sov mus rau qhov txias
- 2-kab system. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270–400 : kuv |
N-> temp = N / 10 ° C |
300 |
||
248 |
0x00f 8 |
R/W (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100–250 : kuv |
N-> temp = N / 10 ° C |
100 |
||
249 |
0x00f 9 |
R/W (#06) |
Txias ON ncua.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0-15 feeb |
0 |
|||
250 |
0x00f ua |
R/W (#06) |
Qhov siab tshaj plaws hauv pem teb
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Installer parameters -P25) |
50–450 : kuv |
N-> temp = N / 10 ° C |
350 |
||
251 |
0 x00fb |
R/W (#06) |
Yam tsawg kawg hauv pem teb kub
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50–450 : kuv |
N-> temp = N / 10 ° C |
150 |
||
254 | 0 x00f | R/W (#06) | PIN code rau installer nqis (Installer Parameters -P28) | 0–1 : kuv | 0 = neeg tsis taus
1 = PIN (First default code 0000) |
0 |
Chaw nyob | Nkag mus | Kev piav qhia | Tus nqi ntau | txhais tau tias | Default | |
Dec | Hex | |||||
255 | 0x00 FF | R/W (#06) | Requiring a PIN code to unlock the keys (Installer Parameters -P29) | 0–1 : kuv | 0 = NIE
1 = TAK |
0 |
256 |
0 x 0100 |
R/W (#06) |
Fan operation (Installer parameters -FAN) |
0–1 : kuv |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = YES |
1 |
257 | 0 x 0101 | R/W (#06) | Fais fab on/off - switching off the regulator | 0,1 | 0 = TAWM
1 = YOG |
1 |
258 |
0 x 0102 |
R/W (#06) |
Hom kev ua haujlwm |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0 x 0104 |
R/W (#06) |
Kev teeb tsa kiv cua ceev |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0 x 0106 | R/W (#06) | Lub xauv xauv | 0,1 | 0 = xauv 1 = xauv | 0 |
263 | 0 x 0107 | R/W (#06) | Zaub brightness (Installer Parameters -P27) | 0-100 : kuv | N-> Brightness = N% | 30 |
268 | 0x010 wb | R/W (#06) | Clock – minutes | 0-59 : kuv | feeb | 0 |
269 | 0 x010d | R/W (#06) | Clock – hours | 0-23 : kuv | Teev | 0 |
270 | 0 x010e | R/W (#06) | Clock – Day of the week (1=Monday) | 1-7 : kuv | Hnub ntawm lub lim tiam | 3 |
273 | 0 x 0111 | R/W (#06) | Set the temperature in schedule mode | 50-450 : kuv | N-> temp = N / 10 ° C | 210 |
274 | 0 x 0112 | R/W (#06) | Set temperature in manual mode | 50-450 : kuv | N-> temp = N / 10 ° C | 210 |
275 | 0 x 0113 | R/W (#06) | Set the temperature in FROST mode | 50 | N-> temp = N / 10 ° C | 50 |
279 | 0 x 0117 | R/W (#06) | Maximum setpoint kub | 50-450 : kuv | N-> temp = N / 10 ° C | 350 |
280 | 0 x 0118 | R/W (#06) | Yam tsawg kawg setpoint kub | 50-450 : kuv | N-> temp = N / 10 ° C | 50 |
284 | 0x011 wb | R/W (#06) | Accuracy of displayed temperature | 1, 5 | N-> temp = N / 10 ° C | 1 |
285 | 0 x011d | R/W (#06) | Kho qhov pom qhov kub thiab txias | -3.0… 3.0°C | in steps of 0.5 | 0 |
288 | 0 x 0120 | R/W (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = Cua sov
1 = Cua txias |
0 |
291 | 0 x 0123 | R/W (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 : kuv | N-> ceev = N% | 10 |
292 | 0 x 0124 | R/W (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 : kuv | N-> ceev = N% | 90 |
293 | 0 x 0125 | R/W (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 : kuv | N-> ceev = N% | 30 |
294 | 0 x 0126 | R/W (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 : kuv | N-> ceev = N% | 60 |
295 | 0 x 0127 | R/W (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 : kuv | N-> ceev = N% | 90 |
FAQ
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.
Cov ntaub ntawv / Cov ntaub ntawv
![]() |
ENGO Controls EFAN-24 PWM Ntxuam Ceev Controller [ua pdf] Phau ntawv qhia EFAN-230B, EFAN-230W, EFAN-24 PWM Ntxuam Ceev Controller, EFAN-24, PWM Ntxuam Ceev Controller, Ntxuam Ceev Controller, Ceev Controller |