Mga pagtutukoy

  • Protocol: MODBUS RTU
  • Modelo ng Controller: EFAN-24
  • Interface ng Komunikasyon: RS485
  • Saklaw ng Address: 1-247
  • Laki ng Data: 32-bit

Mga Tagubilin sa Paggamit ng Produkto

  • Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
  • Failure to adhere to instructions may void the manufacturer’s responsibility.
  • The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
  • Network Connection: RS-485 serial interface
  • Data Configuration: Address, speed, and format are determined by hardware
  • Data Access: Full access to the controller’s ladder program data
  • Laki ng Data: 2 bytes bawat rehistro ng data ng MODBUS
  • Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
  • Unconfigured controllers should not be connected to the network to avoid operational issues.

Pangkalahatang impormasyon

Pangkalahatang impormasyon tungkol sa MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-1

Hindi hihigit sa dalawang wire ang maaaring ikonekta sa bawat terminal, na tinitiyak na ang isang "Daisy Chain" (sa serye) o "tuwid na linya" (direktang) configuration ay ginagamit. Hindi inirerekomenda ang koneksyon ng star o network (bukas), dahil ang mga pagmuni-muni sa loob ng cable ay maaaring magdulot ng katiwalian ng data.ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-2

Configuration

  • Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
  • The manufacturer will not be held responsible for any conduct not following the instructions.

PANSIN:

There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.

MODBUS RTU network operation – Slave mode

Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:

  • Network connection via RS-485 serial interface.
  • Address, communication speed, and byte format are determined by hardware configuration.
  • Nagbibigay-daan sa pag-access sa lahat tags and data used in the controller’s ladder program.
  • 8-bit na address ng alipin
  • 32-bit na laki ng data (1 address = 32-bit na data return)
  • Each MODBUS data register has a size of 2 bytes.

PANSIN:

  • Before the controller is connected to the RS-485 network, it must first be properly configured.
  • The communication settings are configured in the service parameters of the regulator (device).

PANSIN:

  • Connecting unconfigured controllers to the RS-485 network will result in improper operation.
  • Copyright – Ang dokumentong ito ay maaari lamang kopyahin at ipamahagi nang may malinaw na pahintulot ng Engo Controls at maaari lamang ibigay sa mga awtorisadong tao o kumpanyang may kinakailangang teknikal na kadalubhasaan.

mga setting ng komunikasyon

Mga setting ng komunikasyon ng RS-485

Pxx Function Halaga Paglalarawan Default halaga
Addr Address ng device (ID) ng MODBUS Slave. 1 – 247 Address ng device (ID) ng MODBUS Slave. 1
 

BAUD

 

Baud

4800  

Bitrate (Baud)

 

9600

9600
19200
38400
 

PARI

 

Parity bit – nagtatakda ng parity ng data para sa pagtuklas ng error

wala wala  

wala

Kahit na Kahit na
Kakaiba Kakaiba
TUMIGIL StopBit 1 1 stop bit 1
2 2 stop bit

Sinusuportahan ang mga sumusunod na function code:

  • 03 – reading n registers (Holding Registers)
  • 04 – reading n registers (Input Registers)
  • 06 – Write 1 register (Holding Register)

INPUT registers – read only

Address Access Paglalarawan Saklaw ng halaga ibig sabihin Default
Dec Hex
0 0x0000 R (#03) Engo MODBUS Model ID 1-247 MODBUS Slave (ID) 1
1 0x0001 R (#03) Firmware-Bersyon 0x0001-0x9999 0x1110=1.1.10 (BCD code)
 

2

 

0x0002

 

R (#03)

 

Working-state

0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling

0b00001000 = Idle, sensor error

3 0x0003 R (#03) Halaga ng Integrated temperature sensor, °C 50 – 500 N-> temp=N/10 °C
 

5

 

0x0005

 

R (#03)

 

Value of the External temperature sensor S1, °C

 

50 – 500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

6

 

0x0006

 

R (#03)

 

Value of the External temperature sensor S2, °C

 

50 – 500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

 

7

 

 

0x0007

 

 

R (#03)

 

 

Estado ng fan

 

 

0b00000000 –

0b00001111

0b00000000= OFF

0b00000001= I Fan stage mababa 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF

0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high

8 0x0008 R (#03) Valve 1 stat 0 – 1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

9 0x0009 R (#03) Valve 2 state 0 – 1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

10 0x000A R (#03) Humidity measurement (with 5% indication accuracy) 0 – 100 N-> humidity=N %

HOLDING registers – para sa pagbabasa at pagsusulat

Address Access Paglalarawan Saklaw ng halaga ibig sabihin Default
Dec Hex
0 0x0000 R/W (#04) Engo MODBUS Model ID 1-247 MODBUS Slave (ID) 1
 

 

234

 

 

0x00EA

 

 

R/W (#06)

 

 

Uri ng fancoil

 

 

1 – 6

1 = 2 pipe – only heating 2 = 2 pipe – only cooling

3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling

6 = 4 pipe – underfloor heating at cooling sa pamamagitan ng fancoil

 

 

0

 

 

 

 

 

 

 

 

235

 

 

 

 

 

 

 

 

0x00EB

 

 

 

 

 

 

 

 

R/W (#06)

 

 

 

 

 

 

 

 

S1-COM input configuration (Mga Parameter ng Installer -P01)

0 Hindi aktibo ang input. Magpalit sa pagitan ng pagpainit at paglamig gamit ang mga pindutan.  

 

 

 

 

 

 

 

0

 

1

Input used to change heating/cooling via external contact connected to S1-COM:

– S1-COM open –> HEAT mode

– S1-COM shorted -> COOL mode

 

 

2

Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.

Ang controller ay lumilipat sa pagitan ng pag-init

at mga mode ng paglamig batay sa temperatura ng tubo na itinakda sa mga parameter na P17 at P18.

 

 

3

Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode

– The pipe sensor will not allow the fan to run.

The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18.

4 Pag-activate ng floor sensor sa floor heating configuration.
 

 

236

 

 

0x00EC

 

 

R/W (#06)

 

S2-COM input configuration (Mga Parameter ng Installer -P02)

0 Na-disable ang input  

 

0

1 Occupancy sensor (kapag binuksan ang mga contact, i-activate ang ECO mode)
2 Panlabas na sensor ng temperatura
 

237

 

0x00ED

 

R/W (#06)

Napipiling ECO mode (Mga Parameter ng Installer -P07) 0 NO – Disabled  

0

1 YES – Active
238 0x00EE R/W (#06) Halaga ng temperatura ng ECO mode para sa pagpainit (Mga parameter ng installer -P08) 50 – 450 N-> temp=N/10 °C 150
239 0x00EF R/W (#06) Halaga ng temperatura ng ECO mode para sa paglamig (Mga parameter ng installer -P09) 50 – 450 N-> temp=N/10 °C 300
 

 

 

240

 

 

 

0x00F0

 

 

 

R/W (#06)

ΔT of 0- 10V valve operation

This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size

of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17)

 

 

 

1-20

 

 

 

N-> temp=N/10 °C

 

 

 

10

 

 

241

 

 

0x00F1

 

 

R/W (#06)

Fan sa temperatura para sa pagpainit

The fan will start working if the temperature in the room drops below the preset

by the value of the parameter (Installer parameters -P15)

 

 

0 – 50

 

 

N-> temp=N/10 °C

 

 

50

Address Access Paglalarawan Saklaw ng halaga ibig sabihin Default
Dec Hex
 

242

 

0x00F2

 

R/W (#06)

Kontrolin ang algorithm

(TPI or hysteresis) for the heating valve (Installer parameters -P18)

 

0 – 20

0 = TPI

1 = ±0,1C

2 = ±0,2C…

N-> temp=N/10 °C (±0,1…±2C)

 

5

 

 

 

 

 

243

 

 

 

 

 

0x00F3

 

 

 

 

 

R/W (#06)

FAN delta algorithm for cooling

The parameter determines the width of the temperature range in which the fan operates in cooling mode.

If the room temperature increases, then:

1. When a small value of Delta FAN,

the faster the response of the fan to a change in temperature

temperature – faster the increase in speed.

 

2. When large value of Delta FAN, the slower fan increases speed.

(Mga parameter ng installer -P16)

 

 

 

 

 

5 – 50

 

 

 

 

 

N-> temp=N/10 °C

 

 

 

 

 

20

 

 

244

 

 

0x00F4

 

 

R/W (#06)

Fan sa temperatura para sa paglamig.

The fan will start working if the temperature in the room rises above the

setpoint by the value of the parameter. (Installer parameters -P19)

 

 

0 – 50

 

 

N-> temp=N/10 °C

 

 

50

245 0x00F5 R/W (#06) Halaga ng hysteresis para sa cooling valve (Mga parameter ng installer -P20) 1 – 20 N-> temp=N/10 °C (±0,1…±2C) 5
 

 

246

 

 

0x00F6

 

 

R/W (#06)

Dead zone ng switching heating/cool

In a 4-pipe system.The difference between the Set temperature and the room temperature,

at which the controller will automatically change the heating/cooling operation mode.

(Mga parameter ng installer -P21)

 

 

5 – 50

 

 

N-> temp=N/10 °C

 

 

20

 

 

247

 

 

0x00F7

 

 

R/W (#06)

Ang pagpapalit ng halaga ng temperatura mula sa pagpainit hanggang sa paglamig

– 2-pipe system.

In a 2-pipe system, below this value, the system switches to cooling mode

and allows the fan to start. (Installer parameters -P22)

 

 

270 – 400

 

 

N-> temp=N/10 °C

 

 

300

 

 

248

 

 

0x00F8

 

 

R/W (#06)

The value of the switching temperature from cooling to heating, 2-pipe system.

In a 2-pipe system, above this value, the system switches to heating mode

and allows the fan to start. (Installer parameters -P23)

 

 

100 – 250

 

 

N-> temp=N/10 °C

 

 

100

 

 

249

 

 

0x00F9

 

 

R/W (#06)

Paglamig SA pagkaantala.

A parameter used in 4-pipe systems with automatic switching between heating and cooling.

This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24)

 

 

0 – 15 min

 

 

0

 

 

250

 

 

0x00FA

 

 

R/W (#06)

Pinakamataas na temperatura sa sahig

To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value.

(Mga parameter ng installer -P25)

 

 

50 – 450

 

 

N-> temp=N/10 °C

 

 

350

 

 

251

 

 

0x00FB

 

 

R/W (#06)

Pinakamababang temperatura sa sahig

To protect the floor, heating will be switched on, when the floor sensor temperature drops

below the minimum value. (Installer parameters -P26)

 

 

50 – 450

 

 

N-> temp=N/10 °C

 

 

150

254 0x00FE R/W (#06) PIN code para sa mga setting ng installer (Mga Parameter ng Installer -P28) 0 – 1 0 = hindi pinagana

1 = PIN (First default code 0000)

0
Address Access Paglalarawan Saklaw ng halaga ibig sabihin Default
Dec Hex
255 0x00FF R/W (#06) Nangangailangan ng PIN code para i-unlock ang mga key (Mga Parameter ng Installer -P29) 0 – 1 0 = NIE

1 = TAK

0
 

256

 

0x0100

 

R/W (#06)

Operasyon ng fan (Mga parameter ng installer -FAN)  

0 – 1

0 = NO – Inactive – output contacts for fan control are completely disabled

1 = OO

 

1

257 0x0101 R/W (#06) Power on/off – pinapatay ang regulator 0,1 0 = OFF

1 = ON

1
 

258

 

0x0102

 

R/W (#06)

 

Mode ng operasyon

 

0,1,3

0=Manual 1=Schedule

3=FROST – anti-freeze mode

 

0

 

 

 

260

 

 

 

0x0104

 

 

 

R/W (#06)

 

 

 

Setting ng bilis ng fan

0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear

0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear

262 0x0106 R/W (#06) Key lock 0,1 0=naka-unlock 1=Naka-lock 0
263 0x0107 R/W (#06) Liwanag ng display (Mga Parameter ng Installer -P27) 0-100 N-> Liwanag =N% 30
268 0x010C R/W (#06) Clock – minutes 0-59 Mga minuto 0
269 0x010D R/W (#06) Clock – hours 0-23 Mga oras 0
270 0x010E R/W (#06) Clock – Day of the week (1=Monday) 1~7 Araw ng linggo 3
273 0x0111 R/W (#06) Set the temperature in schedule mode 50-450 N-> temp=N/10 °C 210
274 0x0112 R/W (#06) Set temperature in manual mode 50-450 N-> temp=N/10 °C 210
275 0x0113 R/W (#06) Set the temperature in FROST mode 50 N-> temp=N/10 °C 50
279 0x0117 R/W (#06) Maximum na temperatura ng setpoint 50-450 N-> temp=N/10 °C 350
280 0x0118 R/W (#06) Minimum na temperatura ng setpoint 50-450 N-> temp=N/10 °C 50
284 0x011C R/W (#06) Accuracy of displayed temperature 1, 5 N-> temp=N/10 °C 1
285 0x011D R/W (#06) Pagwawasto ng ipinapakitang temperatura -3.0… 3.0°C in steps of 0.5 0
288 0x0120 R/W (#06) Selection of system type – heating/cooling (dependent on the setting of input S1) 0,1 0 = Pag-init

1 = Paglamig

0
291 0x0123 R/W (#06) Minimum fan speed (Installer Parameters-P10) 0-100 N-> bilis=N % 10
292 0x0124 R/W (#06) Maximum fan speed (Installer Parameters-P11) 0-100 N-> bilis=N % 90
293 0x0125 R/W (#06) Speed of fan 1st gear in manual mode (Installer parameters-P12) 0-100 N-> bilis=N % 30
294 0x0126 R/W (#06) Speed of fan 2nd gear in manual mode (Installer parameters-P13) 0-100 N-> bilis=N % 60
295 0x0127 R/W (#06) Speed of fan 3rd gear in manual mode (Installer parameters-P14) 0-100 N-> bilis=N % 90

FAQ

  • Q: What are the default communication settings for the EFAN-24 controller?
  • A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
  • Q: How can I access different data registers in the MODBUS RTU network?
  • A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.