ENGO Controls EFAN-24 PWM Fan Speed Controller
Προδιαγραφές
- Πρωτόκολλο: MODBUS RTU
- Μοντέλο χειριστηρίου: EFAN-24
- Διεπαφή επικοινωνίας: RS485
- Εύρος Διεύθυνσης: 1-247
- Μέγεθος δεδομένων: 32-bit
Οδηγίες χρήσης προϊόντος
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Data Size: 2 bytes per MODBUS data register
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
Γενικές πληροφορίες
Γενικές πληροφορίες για το MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Δεν μπορούν να συνδεθούν περισσότερα από δύο καλώδια σε κάθε ακροδέκτη, διασφαλίζοντας ότι χρησιμοποιείται μια διαμόρφωση "Daisy Chain" (σε σειρά) ή "ευθεία γραμμή" (απευθείας). Δεν συνιστάται η σύνδεση αστεριού ή δικτύου (ανοιχτή), καθώς οι αντανακλάσεις μέσα στο καλώδιο μπορεί να προκαλέσουν καταστροφή δεδομένων.
Διαμόρφωση
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
ΠΡΟΣΟΧΗ:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
Λειτουργία δικτύου MODBUS RTU – Λειτουργία υποτελούς λειτουργίας
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Επιτρέπει την πρόσβαση σε όλους tags and data used in the controller’s ladder program.
- Υποτελής διεύθυνση 8-bit
- Μέγεθος δεδομένων 32 bit (1 διεύθυνση = επιστροφή δεδομένων 32 bit)
- Each MODBUS data register has a size of 2 bytes.
ΠΡΟΣΟΧΗ:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
ΠΡΟΣΟΧΗ:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Πνευματικά δικαιώματα – Αυτό το έγγραφο μπορεί να αναπαραχθεί και να διανεμηθεί μόνο με τη ρητή άδεια της Engo Controls και μπορεί να παρασχεθεί μόνο σε εξουσιοδοτημένα άτομα ή εταιρείες με την απαιτούμενη τεχνική εξειδίκευση.
ρυθμίσεις επικοινωνίας
Ρυθμίσεις επικοινωνίας RS-485
Pxx | Λειτουργία | Αξία | Περιγραφή | Αθέτηση αξία |
Προσθήκη | Διεύθυνση υποτελούς συσκευής MODBUS (ID). | 1 – 247 | Διεύθυνση υποτελούς συσκευής MODBUS (ID). | 1 |
BAUD |
Baud |
4800 |
Ρυθμός bit (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
ΠΑΡΙ |
Bit ισοτιμίας – ορίζει την ισοτιμία δεδομένων για τον εντοπισμό σφαλμάτων |
Κανένας | Κανένας |
Κανένας |
Ακόμη και | Ακόμη και | |||
Περιττός | Περιττός | |||
ΣΤΑΣΗ | StopBit | 1 | 1 μπιτ στοπ | 1 |
2 | 2 μπιτ στοπ |
Υποστηρίζει τους ακόλουθους κωδικούς λειτουργίας:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
Εγγραφές INPUT – μόνο για ανάγνωση
Διεύθυνση | Πρόσβαση | Περιγραφή | Εύρος τιμών | Μέσα | Αθέτηση | |
Δεκ | Γοητεύω | |||||
0 | 0x0000 | R (#03) | Engo MODBUS Model ID | 1-247 | MODBUS Slave (ID) | 1 |
1 | 0x0001 | R (#03) | Υλικολογισμικό-Έκδοση | 0x0001-0x9999 | 0x1110=1.1.10 (κωδικός BCD) | |
2 |
0x0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0x0003 | R (#03) | Τιμή του ενσωματωμένου αισθητήρα θερμοκρασίας, °C | 50 – 500 | Ν-> θερμοκρασία=N/10 °C | |
5 |
0x0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0x0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0x0007 |
R (#03) |
Οπαδική κατάσταση |
0b00000000 – 0b00001111 |
0b00000000= OFF
0b00000001= I Fan stage χαμηλό 0b00000010= II Ανεμιστήρας stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0x0008 | R (#03) | Valve 1 stat | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0x0009 | R (#03) | Valve 2 state | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0x000A | R (#03) | Humidity measurement (with 5% indication accuracy) | 0 – 100 | N-> humidity=N % |
HOLDING μητρώα – για ανάγνωση και γραφή
Διεύθυνση | Πρόσβαση | Περιγραφή | Εύρος τιμών | Μέσα | Αθέτηση | |
Δεκ | Γοητεύω | |||||
0 | 0x0000 | Δ/Υ (#04) | Engo MODBUS Model ID | 1-247 | MODBUS Slave (ID) | 1 |
234 |
0x00EA |
Δ/Υ (#06) |
Τύπος fancoil |
1 – 6 |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 σωλήνων – ενδοδαπέδια θέρμανση & ψύξη με fancoil |
0 |
235 |
0x00EB |
Δ/Υ (#06) |
S1-COM input configuration (Installer Parameters -P01) |
0 | Η είσοδος είναι ανενεργή. Εναλλαγή μεταξύ θέρμανσης και ψύξης με τα κουμπιά. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode – S1-COM βραχυκυκλωμένο –> Λειτουργία COOL |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Ο ελεγκτής αλλάζει μεταξύ θέρμανσης και λειτουργίες ψύξης με βάση τη θερμοκρασία του σωλήνα που έχει οριστεί στις παραμέτρους P17 και P18. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Ενεργοποίηση του αισθητήρα δαπέδου στη διαμόρφωση της θέρμανσης δαπέδου. | |||||
236 |
0x00EC |
Δ/Υ (#06) |
S2-COM input configuration (Installer Parameters -P02) |
0 | Η είσοδος είναι απενεργοποιημένη |
0 |
1 | Αισθητήρας κατάληψης (όταν ανοίγουν οι επαφές, ενεργοποιήστε τη λειτουργία ECO) | |||||
2 | Εξωτερικός αισθητήρας θερμοκρασίας | |||||
237 |
0x00 ΕΔ |
Δ/Υ (#06) |
Επιλέξιμη λειτουργία ECO (Παράμετροι εγκατάστασης -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00EE | Δ/Υ (#06) | Τιμή θερμοκρασίας λειτουργίας ECO για θέρμανση (Παράμετροι εγκατάστασης -P08) | 50 – 450 | Ν-> θερμοκρασία=N/10 °C | 150 |
239 | 0x00EF | Δ/Υ (#06) | Τιμή θερμοκρασίας λειτουργίας ECO για ψύξη (Παράμετροι εγκατάστασης -P09) | 50 – 450 | Ν-> θερμοκρασία=N/10 °C | 300 |
240 |
0x00F0 |
Δ/Υ (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 |
Ν-> θερμοκρασία=N/10 °C |
10 |
241 |
0x00F1 |
Δ/Υ (#06) |
Fan on temperature for heating
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0 – 50 |
Ν-> θερμοκρασία=N/10 °C |
50 |
Διεύθυνση | Πρόσβαση | Περιγραφή | Εύρος τιμών | Μέσα | Αθέτηση | |||
Δεκ | Γοητεύω | |||||||
242 |
0x00F2 |
Δ/Υ (#06) |
Αλγόριθμος ελέγχου
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0 – 20 |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00F3 |
Δ/Υ (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Παράμετροι προγράμματος εγκατάστασης -P16) |
5 – 50 |
Ν-> θερμοκρασία=N/10 °C |
20 |
||
244 |
0x00F4 |
Δ/Υ (#06) |
Ανεμιστήρας σε θερμοκρασία για ψύξη.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0 – 50 |
Ν-> θερμοκρασία=N/10 °C |
50 |
||
245 | 0x00F5 | Δ/Υ (#06) | Τιμή υστέρησης για τη βαλβίδα ψύξης (Παράμετροι εγκατάστασης -P20) | 1 – 20 | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00F6 |
Δ/Υ (#06) |
Νεκρή ζώνη μεταγωγής θέρμανσης/ψύξης
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Παράμετροι προγράμματος εγκατάστασης -P21) |
5 – 50 |
Ν-> θερμοκρασία=N/10 °C |
20 |
||
247 |
0x00F7 |
Δ/Υ (#06) |
Η τιμή της θερμοκρασίας εναλλαγής από θέρμανση σε ψύξη
– Σύστημα 2 σωλήνων. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270 – 400 |
Ν-> θερμοκρασία=N/10 °C |
300 |
||
248 |
0x00F8 |
Δ/Υ (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100 – 250 |
Ν-> θερμοκρασία=N/10 °C |
100 |
||
249 |
0x00F9 |
Δ/Υ (#06) |
Καθυστέρηση ψύξης ON.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0 – 15 λεπτά |
0 |
|||
250 |
0x00FA |
Δ/Υ (#06) |
Μέγιστη θερμοκρασία δαπέδου
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Παράμετροι προγράμματος εγκατάστασης -P25) |
50 – 450 |
Ν-> θερμοκρασία=N/10 °C |
350 |
||
251 |
0x00FB |
Δ/Υ (#06) |
Ελάχιστη θερμοκρασία δαπέδου
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50 – 450 |
Ν-> θερμοκρασία=N/10 °C |
150 |
||
254 | 0x00FE | Δ/Υ (#06) | Κωδικός PIN για ρυθμίσεις προγράμματος εγκατάστασης (Παράμετροι εγκατάστασης -P28) | 0 – 1 | 0 = απενεργοποιημένο
1 = PIN (First default code 0000) |
0 |
Διεύθυνση | Πρόσβαση | Περιγραφή | Εύρος τιμών | Μέσα | Αθέτηση | |
Δεκ | Γοητεύω | |||||
255 | 0x00 FF | Δ/Υ (#06) | Απαίτηση κωδικού PIN για το ξεκλείδωμα των κλειδιών (Παράμετροι εγκατάστασης -P29) | 0 – 1 | 0 = NIE
1 = TAK |
0 |
256 |
0x0100 |
Δ/Υ (#06) |
Λειτουργία ανεμιστήρα (Παράμετροι εγκατάστασης - FAN) |
0 – 1 |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = ΝΑΙ |
1 |
257 | 0x0101 | Δ/Υ (#06) | Ενεργοποίηση/απενεργοποίηση – απενεργοποίηση του ρυθμιστή | 0,1 | 0 = OFF
1 = ΟΝ |
1 |
258 |
0x0102 |
Δ/Υ (#06) |
Τρόπος λειτουργίας |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0x0104 |
Δ/Υ (#06) |
Ρύθμιση ταχύτητας ανεμιστήρα |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0x0106 | Δ/Υ (#06) | Κλειδαριά με κλειδί | 0,1 | 0=ξεκλείδωτο 1=Κλειδωμένο | 0 |
263 | 0x0107 | Δ/Υ (#06) | Φωτεινότητα οθόνης (Παράμετροι εγκατάστασης -P27) | 0-100 | N-> Φωτεινότητα =N% | 30 |
268 | 0x010C | Δ/Υ (#06) | Clock – minutes | 0-59 | Πρακτικά | 0 |
269 | 0x010D | Δ/Υ (#06) | Clock – hours | 0-23 | Ώρες | 0 |
270 | 0x010E | Δ/Υ (#06) | Clock – Day of the week (1=Monday) | 1~7 | Ημέρα της εβδομάδας | 3 |
273 | 0x0111 | Δ/Υ (#06) | Set the temperature in schedule mode | 50-450 | Ν-> θερμοκρασία=N/10 °C | 210 |
274 | 0x0112 | Δ/Υ (#06) | Set temperature in manual mode | 50-450 | Ν-> θερμοκρασία=N/10 °C | 210 |
275 | 0x0113 | Δ/Υ (#06) | Set the temperature in FROST mode | 50 | Ν-> θερμοκρασία=N/10 °C | 50 |
279 | 0x0117 | Δ/Υ (#06) | Μέγιστη θερμοκρασία σημείου ρύθμισης | 50-450 | Ν-> θερμοκρασία=N/10 °C | 350 |
280 | 0x0118 | Δ/Υ (#06) | Ελάχιστη επιθυμητή θερμοκρασία | 50-450 | Ν-> θερμοκρασία=N/10 °C | 50 |
284 | 0x011C | Δ/Υ (#06) | Accuracy of displayed temperature | 1, 5 | Ν-> θερμοκρασία=N/10 °C | 1 |
285 | 0x011D | Δ/Υ (#06) | Διόρθωση της εμφανιζόμενης θερμοκρασίας | -3.0… 3.0°C | in steps of 0.5 | 0 |
288 | 0x0120 | Δ/Υ (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = Θέρμανση
1 = Ψύξη |
0 |
291 | 0x0123 | Δ/Υ (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 | N-> speed=N % | 10 |
292 | 0x0124 | Δ/Υ (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 | N-> speed=N % | 90 |
293 | 0x0125 | Δ/Υ (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 | N-> speed=N % | 30 |
294 | 0x0126 | Δ/Υ (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 | N-> speed=N % | 60 |
295 | 0x0127 | Δ/Υ (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 | N-> speed=N % | 90 |
FAQ
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.