ENGO-LOGO

ENGO EFAN-24 PWM የደጋፊ ፍጥነት መቆጣጠሪያን ይቆጣጠራል

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-PRODUCT

ዝርዝሮች

  • ፕሮቶኮል፡ MODBUS RTU
  • የመቆጣጠሪያ ሞዴል: EFAN-24
  • የግንኙነት በይነገጽ: RS485
  • የአድራሻ ክልል፡ 1-247
  • የውሂብ መጠን: 32-ቢት

የምርት አጠቃቀም መመሪያዎች

  • Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
  • Failure to adhere to instructions may void the manufacturer’s responsibility.
  • The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
  • Network Connection: RS-485 serial interface
  • Data Configuration: Address, speed, and format are determined by hardware
  • Data Access: Full access to the controller’s ladder program data
  • የውሂብ መጠን፡ 2 ባይት በ MODBUS የውሂብ መመዝገቢያ
  • Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
  • Unconfigured controllers should not be connected to the network to avoid operational issues.

አጠቃላይ መረጃ

ስለ MODBUS RTU አጠቃላይ መረጃ
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-1

ከእያንዳንዱ ተርሚናል ጋር ከሁለት በላይ ገመዶች ሊገናኙ አይችሉም, ይህም "Daisy Chain" (በተከታታይ) ወይም "ቀጥታ መስመር" (ቀጥታ) ውቅር ጥቅም ላይ ይውላል. በኬብሉ ውስጥ ያለው ነጸብራቅ የውሂብ መበላሸትን ሊያስከትል ስለሚችል የኮከብ ወይም የአውታረ መረብ (ክፍት) ግንኙነት አይመከርም።ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-2

ማዋቀር

  • Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
  • The manufacturer will not be held responsible for any conduct not following the instructions.

ትኩረት፡

There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.

MODBUS RTU አውታረ መረብ ክወና - የባሪያ ሁነታ

Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:

  • Network connection via RS-485 serial interface.
  • Address, communication speed, and byte format are determined by hardware configuration.
  • ለሁሉም መዳረሻ ይፈቅዳል tags and data used in the controller’s ladder program.
  • 8-ቢት ባሪያ አድራሻ
  • 32-ቢት የውሂብ መጠን (1 አድራሻ = 32-ቢት የውሂብ መመለስ)
  • Each MODBUS data register has a size of 2 bytes.

ትኩረት፡

  • Before the controller is connected to the RS-485 network, it must first be properly configured.
  • The communication settings are configured in the service parameters of the regulator (device).

ትኩረት፡

  • Connecting unconfigured controllers to the RS-485 network will result in improper operation.
  • የቅጂ መብት - ይህ ሰነድ ሊባዛ እና ሊሰራጭ የሚችለው በ Engo Controls ፈጣን ፈቃድ ብቻ ነው እና ለተፈቀደላቸው ሰዎች ወይም አስፈላጊ የቴክኒክ እውቀት ላላቸው ኩባንያዎች ብቻ ሊሰጥ ይችላል።

የግንኙነት ቅንብሮች

RS-485 የግንኙነት ቅንብሮች

ፒክስክስ ተግባር ዋጋ መግለጫ ነባሪ ዋጋ
ጨማሪ MODBUS የስላቭ መሳሪያ አድራሻ (መታወቂያ)። 1 - 247 MODBUS የስላቭ መሳሪያ አድራሻ (መታወቂያ)። 1
 

BAUD

 

ባውድ

4800  

ቢትሬት (ባውድ)

 

9600

9600
19200
38400
 

PARI

 

የተመጣጣኝ ቢት - ስህተትን ለመለየት የውሂብ እኩልነትን ያዘጋጃል።

ምንም ምንም  

ምንም

እንኳን እንኳን
እንግዳ እንግዳ
ተወ StopBit 1 1 ማቆሚያ ቢት 1
2 2 ማቆሚያ ቢት

የሚከተሉትን የተግባር ኮዶች ይደግፋል፡

  • 03 – reading n registers (Holding Registers)
  • 04 – reading n registers (Input Registers)
  • 06 – Write 1 register (Holding Register)

INPUT መመዝገቢያዎች - ማንበብ ብቻ

አድራሻ መዳረሻ መግለጫ የእሴት ክልል ማለት ነው። ነባሪ
ዲሴምበር ሄክስ
0 0x0000 አር (#03) Engo MODBUS Model ID 1-247 MODBUS ባሪያ (መታወቂያ) 1
1 0x0001 አር (#03) Firmware-ስሪት 0x0001-0x9999 0x1110=1.1.10 (BCD ኮድ)
 

2

 

0x0002

 

አር (#03)

 

Working-state

0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling

0b00001000 = Idle, sensor error

3 0x0003 አር (#03) የተቀናጀ የሙቀት ዳሳሽ ዋጋ ፣ ° ሴ 50 - 500 N-> temp=N/10 °C
 

5

 

0x0005

 

አር (#03)

 

Value of the External temperature sensor S1, °C

 

50 - 500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

6

 

0x0006

 

አር (#03)

 

Value of the External temperature sensor S2, °C

 

50 - 500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

 

7

 

 

0x0007

 

 

አር (#03)

 

 

የደጋፊዎች ሁኔታ

 

 

0b00000000 –

0b00001111

0b00000000= OFF

0b00000001= I Fan stage ዝቅተኛ 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF

0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high

8 0x0008 አር (#03) Valve 1 stat 0 - 1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

9 0x0009 አር (#03) Valve 2 state 0 - 1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

10 0x000A አር (#03) Humidity measurement (with 5% indication accuracy) 0 - 100 N-> humidity=N %

መዝገቦችን መያዝ - ለማንበብ እና ለመጻፍ

አድራሻ መዳረሻ መግለጫ የእሴት ክልል ማለት ነው። ነባሪ
ዲሴምበር ሄክስ
0 0x0000 አር/ደብሊው (#04) Engo MODBUS Model ID 1-247 MODBUS ባሪያ (መታወቂያ) 1
 

 

234

 

 

0x00EA

 

 

አር/ደብሊው (#06)

 

 

Fancoil አይነት

 

 

1 - 6

1 = 2 pipe – only heating 2 = 2 pipe – only cooling

3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling

6 = 4 ቧንቧ - ከወለል በታች ማሞቂያ እና ማቀዝቀዣ በፋንኮይል

 

 

0

 

 

 

 

 

 

 

 

235

 

 

 

 

 

 

 

 

0x00ኢቢ

 

 

 

 

 

 

 

 

አር/ደብሊው (#06)

 

 

 

 

 

 

 

 

S1-COM የግቤት ውቅር (የጫኝ መለኪያዎች -P01)

0 ግቤት ቦዝኗል። በአዝራሮች በማሞቅ እና በማቀዝቀዝ መካከል ይቀይሩ.  

 

 

 

 

 

 

 

0

 

1

Input used to change heating/cooling via external contact connected to S1-COM:

– S1-COM open –> HEAT mode

- S1-COM አጭር -> አሪፍ ሁነታ

 

 

2

Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.

መቆጣጠሪያው በማሞቅ መካከል ይቀየራል

እና በፒ 17 እና ፒ 18 ውስጥ በተቀመጠው የቧንቧ ሙቀት መሰረት የማቀዝቀዣ ሁነታዎች.

 

 

3

Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode

– The pipe sensor will not allow the fan to run.

The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18.

4 በፎቅ ማሞቂያ ውቅር ውስጥ የወለል ዳሳሽ ማግበር.
 

 

236

 

 

0x00EC

 

 

አር/ደብሊው (#06)

 

S2-COM የግቤት ውቅር (የጫኝ መለኪያዎች -P02)

0 ግቤት ተሰናክሏል።  

 

0

1 የመኖርያ ዳሳሽ (እውቂያዎች ሲከፈቱ፣ ECO ሁነታን ያግብሩ)
2 የውጭ ሙቀት ዳሳሽ
 

237

 

0x00ED

 

አር/ደብሊው (#06)

ሊመረጥ የሚችል የኢኮ ሁነታ (የጫኝ መለኪያዎች -P07) 0 NO – Disabled  

0

1 YES – Active
238 0x00EE አር/ደብሊው (#06) ለማሞቂያ የኢኮ ሞድ የሙቀት ዋጋ (የጫኝ መለኪያዎች -P08) 50 - 450 N-> temp=N/10 °C 150
239 0x00EF አር/ደብሊው (#06) ለማቀዝቀዝ የኢኮ ሞድ የሙቀት ዋጋ (የጫኝ መለኪያዎች -P09) 50 - 450 N-> temp=N/10 °C 300
 

 

 

240

 

 

 

0x00F0

 

 

 

አር/ደብሊው (#06)

ΔT of 0- 10V valve operation

This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size

of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17)

 

 

 

1-20

 

 

 

N-> temp=N/10 °C

 

 

 

10

 

 

241

 

 

0x00F1

 

 

አር/ደብሊው (#06)

ለማሞቅ በሙቀት ላይ ደጋፊ

The fan will start working if the temperature in the room drops below the preset

by the value of the parameter (Installer parameters -P15)

 

 

0 - 50

 

 

N-> temp=N/10 °C

 

 

50

አድራሻ መዳረሻ መግለጫ የእሴት ክልል ማለት ነው። ነባሪ
ዲሴምበር ሄክስ
 

242

 

0x00F2

 

አር/ደብሊው (#06)

የቁጥጥር ስልተ ቀመር

(TPI or hysteresis) for the heating valve (Installer parameters -P18)

 

0 - 20

0 = TPI

1 = ±0,1C

2 = ±0,2C…

N-> temp=N/10 °C (±0,1…±2C)

 

5

 

 

 

 

 

243

 

 

 

 

 

0x00F3

 

 

 

 

 

አር/ደብሊው (#06)

FAN delta algorithm for cooling

The parameter determines the width of the temperature range in which the fan operates in cooling mode.

If the room temperature increases, then:

1. When a small value of Delta FAN,

the faster the response of the fan to a change in temperature

temperature – faster the increase in speed.

 

2. When large value of Delta FAN, the slower fan increases speed.

(የጫኝ መለኪያዎች -P16)

 

 

 

 

 

5 - 50

 

 

 

 

 

N-> temp=N/10 °C

 

 

 

 

 

20

 

 

244

 

 

0x00F4

 

 

አር/ደብሊው (#06)

ለማቀዝቀዝ በሙቀት ላይ አድናቂ።

The fan will start working if the temperature in the room rises above the

setpoint by the value of the parameter. (Installer parameters -P19)

 

 

0 - 50

 

 

N-> temp=N/10 °C

 

 

50

245 0x00F5 አር/ደብሊው (#06) ለማቀዝቀዣው ቫልቭ የሃይስቴሬሲስ ዋጋ (የጫኝ መለኪያዎች -P20) 1 - 20 N-> temp=N/10 °C (±0,1…±2C) 5
 

 

246

 

 

0x00F6

 

 

አር/ደብሊው (#06)

የማሞቅ/የማቀዝቀዝ ሙት ዞን

In a 4-pipe system.The difference between the Set temperature and the room temperature,

at which the controller will automatically change the heating/cooling operation mode.

(የጫኝ መለኪያዎች -P21)

 

 

5 - 50

 

 

N-> temp=N/10 °C

 

 

20

 

 

247

 

 

0x00F7

 

 

አር/ደብሊው (#06)

የመቀየሪያ ሙቀት ዋጋ ከማሞቂያ ወደ ማቀዝቀዝ

- 2-ፓይፕ ሲስተም.

In a 2-pipe system, below this value, the system switches to cooling mode

and allows the fan to start. (Installer parameters -P22)

 

 

270 - 400

 

 

N-> temp=N/10 °C

 

 

300

 

 

248

 

 

0x00F8

 

 

አር/ደብሊው (#06)

The value of the switching temperature from cooling to heating, 2-pipe system.

In a 2-pipe system, above this value, the system switches to heating mode

and allows the fan to start. (Installer parameters -P23)

 

 

100 - 250

 

 

N-> temp=N/10 °C

 

 

100

 

 

249

 

 

0x00F9

 

 

አር/ደብሊው (#06)

በማዘግየት ላይ ማቀዝቀዝ።

A parameter used in 4-pipe systems with automatic switching between heating and cooling.

This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24)

 

 

0 - 15 ደቂቃ

 

 

0

 

 

250

 

 

0x00ኤፍኤ

 

 

አር/ደብሊው (#06)

ከፍተኛው የወለል ሙቀት

To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value.

(የጫኝ መለኪያዎች -P25)

 

 

50 - 450

 

 

N-> temp=N/10 °C

 

 

350

 

 

251

 

 

0x00FB

 

 

አር/ደብሊው (#06)

ዝቅተኛው ወለል ሙቀት

To protect the floor, heating will be switched on, when the floor sensor temperature drops

below the minimum value. (Installer parameters -P26)

 

 

50 - 450

 

 

N-> temp=N/10 °C

 

 

150

254 0x00FE አር/ደብሊው (#06) ፒን ኮድ ለጫኚ ቅንጅቶች (የጫኝ መለኪያዎች -P28) 0 - 1 0 = ተሰናክሏል

1 = PIN (First default code 0000)

0
አድራሻ መዳረሻ መግለጫ የእሴት ክልል ማለት ነው። ነባሪ
ዲሴምበር ሄክስ
255 0x00FF አር/ደብሊው (#06) ቁልፎቹን ለመክፈት ፒን ኮድ ያስፈልጋል (የጫኝ መለኪያዎች -P29) 0 - 1 0 = NIE

1 = TAK

0
 

256

 

0x0100

 

አር/ደብሊው (#06)

የደጋፊ አሠራር (የጫኝ መለኪያዎች - ፋን)  

0 - 1

0 = NO – Inactive – output contacts for fan control are completely disabled

1 = አዎ

 

1

257 0x0101 አር/ደብሊው (#06) ማብራት / ማጥፋት - መቆጣጠሪያውን ማጥፋት 0,1 0 = ጠፍቷል

1 = በርቷል

1
 

258

 

0x0102

 

አር/ደብሊው (#06)

 

የክወና ሁነታ

 

0,1,3

0=Manual 1=Schedule

3=FROST – anti-freeze mode

 

0

 

 

 

260

 

 

 

0x0104

 

 

 

አር/ደብሊው (#06)

 

 

 

የደጋፊ ፍጥነት ቅንብር

0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear

0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear

262 0x0106 አር/ደብሊው (#06) ቁልፍ መቆለፊያ 0,1 0=የተከፈተ 1=ተቆልፏል 0
263 0x0107 አር/ደብሊው (#06) ብሩህነት አሳይ (የጫኝ መለኪያዎች -P27) 0-100 N-> ብሩህነት = N% 30
268 0x010 ሴ አር/ደብሊው (#06) Clock – minutes 0-59 ደቂቃዎች 0
269 0x010D አር/ደብሊው (#06) Clock – hours 0-23 ሰዓታት 0
270 0x010E አር/ደብሊው (#06) Clock – Day of the week (1=Monday) 1~7 የሳምንቱ ቀን 3
273 0x0111 አር/ደብሊው (#06) Set the temperature in schedule mode 50-450 N-> temp=N/10 °C 210
274 0x0112 አር/ደብሊው (#06) Set temperature in manual mode 50-450 N-> temp=N/10 °C 210
275 0x0113 አር/ደብሊው (#06) Set the temperature in FROST mode 50 N-> temp=N/10 °C 50
279 0x0117 አር/ደብሊው (#06) ከፍተኛ የአቀማመጥ የሙቀት መጠን 50-450 N-> temp=N/10 °C 350
280 0x0118 አር/ደብሊው (#06) ዝቅተኛው የአቀማመጥ ሙቀት 50-450 N-> temp=N/10 °C 50
284 0x011 ሴ አር/ደብሊው (#06) Accuracy of displayed temperature 1፣ 5 N-> temp=N/10 °C 1
285 0x011D አር/ደብሊው (#06) የሚታየውን የሙቀት መጠን ማስተካከል -3.0… 3.0°ሴ in steps of 0.5 0
288 0x0120 አር/ደብሊው (#06) Selection of system type – heating/cooling (dependent on the setting of input S1) 0,1 0 = ማሞቂያ

1 = ማቀዝቀዝ

0
291 0x0123 አር/ደብሊው (#06) Minimum fan speed (Installer Parameters-P10) 0-100 N-> ፍጥነት=N % 10
292 0x0124 አር/ደብሊው (#06) Maximum fan speed (Installer Parameters-P11) 0-100 N-> ፍጥነት=N % 90
293 0x0125 አር/ደብሊው (#06) Speed of fan 1st gear in manual mode (Installer parameters-P12) 0-100 N-> ፍጥነት=N % 30
294 0x0126 አር/ደብሊው (#06) Speed of fan 2nd gear in manual mode (Installer parameters-P13) 0-100 N-> ፍጥነት=N % 60
295 0x0127 አር/ደብሊው (#06) Speed of fan 3rd gear in manual mode (Installer parameters-P14) 0-100 N-> ፍጥነት=N % 90

የሚጠየቁ ጥያቄዎች

  • Q: What are the default communication settings for the EFAN-24 controller?
  • A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
  • Q: How can I access different data registers in the MODBUS RTU network?
  • A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.

ሰነዶች / መርጃዎች

ENGO EFAN-24 PWM የደጋፊ ፍጥነት መቆጣጠሪያን ይቆጣጠራል [pdf] መመሪያ መመሪያ
EFAN-230B፣ EFAN-230W፣ EFAN-24 PWM የደጋፊ ፍጥነት መቆጣጠሪያ፣ EFAN-24፣ PWM የደጋፊ ፍጥነት መቆጣጠሪያ፣ የደጋፊ ፍጥነት መቆጣጠሪያ፣ የፍጥነት መቆጣጠሪያ

ዋቢዎች

አስተያየት ይስጡ

የኢሜል አድራሻዎ አይታተምም። አስፈላጊ መስኮች ምልክት ተደርጎባቸዋል *