ENGO Controls EFAN-24 PWM Kontwolè Vitès Fanatik
Espesifikasyon
- Pwotokòl: MODBUS RTU
- Modèl contrôleur: EFAN-24
- Entèfas kominikasyon: RS485
- Adrès Range: 1-247
- Gwosè Done: 32-bit
Enstriksyon Itilizasyon Pwodwi
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Gwosè Done: 2 okte pou chak rejis done MODBUS
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
Enfòmasyon jeneral
Enfòmasyon jeneral sou MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Pa plis pase de fil ka konekte nan chak tèminal, asire ke yo itilize yon konfigirasyon "Daisy Chain" (an seri) oswa "liy dwat" (dirèk). Koneksyon zetwal oswa rezo (ouvè) pa rekòmande, paske refleksyon nan kab la ka lakòz koripsyon done yo.
Konfigirasyon
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
ATANSYON:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
Operasyon rezo MODBUS RTU - mòd esklav
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Pèmèt aksè a tout moun tags and data used in the controller’s ladder program.
- 8-bit adrès esklav
- Gwosè done 32-bit (1 adrès = retounen done 32-bit)
- Each MODBUS data register has a size of 2 bytes.
ATANSYON:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
ATANSYON:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Dwa – Dokiman sa a ka sèlman repwodui ak distribye avèk pèmisyon eksprime Engo Controls epi yo ka bay sèlman moun ki otorize oswa konpayi ki gen ekspètiz teknik ki nesesè yo.
anviwònman kominikasyon
Anviwònman kominikasyon RS-485
Pxx | Fonksyon | Valè | Deskripsyon | Default valè |
Addr | Adrès aparèy MODBUS esklav (ID). | 1 – 247 | Adrès aparèy MODBUS esklav (ID). | 1 |
BAUD |
Baud |
4800 |
Bitrate (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
PARI |
Bit parite - mete parite done pou deteksyon erè |
Okenn | Okenn |
Okenn |
Menm | Menm | |||
Enpè | Enpè | |||
SISPANN | StopBit | 1 | 1 arè bit | 1 |
2 | 2 arè bit |
Sipòte kòd fonksyon sa yo:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
Enskri INPUT - li sèlman
Adrès | Aksè | Deskripsyon | Ranje valè | Vle di | Default | |
Desanm | Egzagòn | |||||
0 | 0x0000 | R (#03) | Engo MODBUS Model ID | 1-247 | MODBUS esklav (ID) | 1 |
1 | 0x0001 | R (#03) | Firmware-vèsyon | 0x0001-0x9999 | 0x1110 = 1.1.10 (BCD kòd) | |
2 |
0x0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0x0003 | R (#03) | Valè Capteur tanperati entegre, °C | 50 – 500 | N-> temp = N/10 °C | |
5 |
0x0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0x0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50 – 500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0x0007 |
R (#03) |
Eta fanatik |
0b00000000 – 0b00001111 |
0b00000000= OFF
0b00000001= I Fan stage ba 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0x0008 | R (#03) | Valve 1 stat | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0x0009 | R (#03) | Valve 2 state | 0 – 1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0x000A | R (#03) | Humidity measurement (with 5% indication accuracy) | 0 – 100 | N-> humidity=N % |
HOLDING anrejistre - pou lekti ak ekri
Adrès | Aksè | Deskripsyon | Ranje valè | Vle di | Default | |
Desanm | Egzagòn | |||||
0 | 0x0000 | R/W (#04) | Engo MODBUS Model ID | 1-247 | MODBUS esklav (ID) | 1 |
234 |
0x00EA |
R/W (#06) |
Fancoil kalite |
1 – 6 |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 tiyo - chofaj anba planche ak refwadisman pa fancoil |
0 |
235 |
0x00EB |
R/W (#06) |
Konfigirasyon antre S1-COM (Paramèt Enstalatè -P01) |
0 | Antre inaktif. Chanje ant chofaj ak refwadisman ak bouton yo. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode – S1-COM kout –> mòd COOL |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Kontwolè a chanje ant chofaj ak mòd refwadisman ki baze sou tanperati tiyo ki tabli nan paramèt P17 ak P18. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Aktivasyon Capteur etaj la nan konfigirasyon chofaj etaj la. | |||||
236 |
0x00EC |
R/W (#06) |
Konfigirasyon antre S2-COM (Paramèt Enstalatè -P02) |
0 | Antre enfim |
0 |
1 | Capteur Okipasyon (lè kontak yo louvri, aktive mòd ECO) | |||||
2 | Capteur tanperati ekstèn | |||||
237 |
0x00ED |
R/W (#06) |
Mòd ECO ka chwazi (Paramèt Enstalatè -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00EE | R/W (#06) | Valè tanperati mòd ECO pou chofaj (paramèt Enstalatè -P08) | 50 – 450 | N-> temp = N/10 °C | 150 |
239 | 0x00EF | R/W (#06) | Valè tanperati mòd ECO pou refwadisman (paramèt Enstalatè -P09) | 50 – 450 | N-> temp = N/10 °C | 300 |
240 |
0x00F0 |
R/W (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 |
N-> temp = N/10 °C |
10 |
241 |
0x00F1 |
R/W (#06) |
Tanperati vantilatè a sou pou chofaj
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0 – 50 |
N-> temp = N/10 °C |
50 |
Adrès | Aksè | Deskripsyon | Ranje valè | Vle di | Default | |||
Desanm | Egzagòn | |||||||
242 |
0x00F2 |
R/W (#06) |
Algorithm kontwòl
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0 – 20 |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00F3 |
R/W (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Paramèt Enstalatè -P16) |
5 – 50 |
N-> temp = N/10 °C |
20 |
||
244 |
0x00F4 |
R/W (#06) |
Fanatik sou tanperati pou refwadisman.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0 – 50 |
N-> temp = N/10 °C |
50 |
||
245 | 0x00F5 | R/W (#06) | Valè isterèz pou valv la refwadisman (paramèt Enstalatè -P20) | 1 – 20 | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00F6 |
R/W (#06) |
Zòn mouri nan chanje chofaj / refwadisman
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Paramèt Enstalatè -P21) |
5 – 50 |
N-> temp = N/10 °C |
20 |
||
247 |
0x00F7 |
R/W (#06) |
Valè tanperati a chanje soti nan chofaj ak refwadisman
- 2-tiyo sistèm. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270 – 400 |
N-> temp = N/10 °C |
300 |
||
248 |
0x00F8 |
R/W (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100 – 250 |
N-> temp = N/10 °C |
100 |
||
249 |
0x00F9 |
R/W (#06) |
Refwadisman ON reta.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0-15 min |
0 |
|||
250 |
0x00FA |
R/W (#06) |
Tanperati maksimòm etaj la
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Paramèt Enstalatè -P25) |
50 – 450 |
N-> temp = N/10 °C |
350 |
||
251 |
0x00FB |
R/W (#06) |
Tanperati minimòm etaj la
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50 – 450 |
N-> temp = N/10 °C |
150 |
||
254 | 0x00FE | R/W (#06) | Kòd PIN pou anviwònman enstalatè (Paramèt Enstalatè -P28) | 0 – 1 | 0 = andikape
1 = PIN (First default code 0000) |
0 |
Adrès | Aksè | Deskripsyon | Ranje valè | Vle di | Default | |
Desanm | Egzagòn | |||||
255 | 0x00FF | R/W (#06) | Egzije yon kòd PIN pou déblotché kle yo (Paramèt Enstalatè -P29) | 0 – 1 | 0 = NIE
1 = TAK |
0 |
256 |
0x0100 |
R/W (#06) |
Operasyon fanatik (paramèt Enstalatè -FAN) |
0 – 1 |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = WI |
1 |
257 | 0x0101 | R/W (#06) | Pouvwa sou / koupe - koupe regilatè a | 0,1 | 0 = OFF
1 = ON |
1 |
258 |
0x0102 |
R/W (#06) |
Mòd operasyon |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0x0104 |
R/W (#06) |
Anviwònman vitès fanatik la |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0x0106 | R/W (#06) | Kle fèmen | 0,1 | 0 = debloke 1 = fèmen | 0 |
263 | 0x0107 | R/W (#06) | Ekspozisyon klète (Paramèt Enstalatè -P27) | 0-100 | N-> Klate = N% | 30 |
268 | 0x010C | R/W (#06) | Clock – minutes | 0-59 | Minit | 0 |
269 | 0x010D | R/W (#06) | Clock – hours | 0-23 | Orè | 0 |
270 | 0x010E | R/W (#06) | Clock – Day of the week (1=Monday) | 1 ~ 7 | Jou nan semèn nan | 3 |
273 | 0x0111 | R/W (#06) | Set the temperature in schedule mode | 50-450 | N-> temp = N/10 °C | 210 |
274 | 0x0112 | R/W (#06) | Set temperature in manual mode | 50-450 | N-> temp = N/10 °C | 210 |
275 | 0x0113 | R/W (#06) | Set the temperature in FROST mode | 50 | N-> temp = N/10 °C | 50 |
279 | 0x0117 | R/W (#06) | Maksimòm tanperati setpoint | 50-450 | N-> temp = N/10 °C | 350 |
280 | 0x0118 | R/W (#06) | Minimòm tanperati setpoint | 50-450 | N-> temp = N/10 °C | 50 |
284 | 0x011C | R/W (#06) | Accuracy of displayed temperature | 1, 5 | N-> temp = N/10 °C | 1 |
285 | 0x011D | R/W (#06) | Koreksyon tanperati ki parèt la | -3.0... 3.0°C | in steps of 0.5 | 0 |
288 | 0x0120 | R/W (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = Chofaj
1 = Refwadisman |
0 |
291 | 0x0123 | R/W (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 | N -> vitès=N % | 10 |
292 | 0x0124 | R/W (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 | N -> vitès=N % | 90 |
293 | 0x0125 | R/W (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 | N -> vitès=N % | 30 |
294 | 0x0126 | R/W (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 | N -> vitès=N % | 60 |
295 | 0x0127 | R/W (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 | N -> vitès=N % | 90 |
FAQ
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.