ENGO Controls EFAN-24 PWM Fan Speed Controller
Nkọwapụta
- Protocol: MODBUS RTU
- Ụdị njikwa: EFAN-24
- Njikọ njikọ: RS485
- Ọnụ adreesị: 1-247
- Nha data: 32-bit
Ntuziaka ojiji ngwaahịa
- Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
- Failure to adhere to instructions may void the manufacturer’s responsibility.
- The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
- Network Connection: RS-485 serial interface
- Data Configuration: Address, speed, and format are determined by hardware
- Data Access: Full access to the controller’s ladder program data
- Data Size: 2 bytes per MODBUS data register
- Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
- Unconfigured controllers should not be connected to the network to avoid operational issues.
ozi izugbe
Ozi izugbe gbasara MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.
Enweghị ike ijikọ ihe karịrị wires abụọ na njedebe nke ọ bụla, na-ahụ na a na-eji nhazi "Daisy Chain" (na usoro) ma ọ bụ "ahịrị kwụ ọtọ" (direct) nhazi. A naghị atụ aro njikọ kpakpando ma ọ bụ netwọk (emeghe), n'ihi na ntụgharị uche n'ime eriri nwere ike ịkpata nrụrụ data.
Nhazi
- Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
- The manufacturer will not be held responsible for any conduct not following the instructions.
IHE:
There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.
Ọrụ netwọk MODBUS RTU – Ọnọdụ ohu
Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:
- Network connection via RS-485 serial interface.
- Address, communication speed, and byte format are determined by hardware configuration.
- Na-enye ohere ịnweta mmadụ niile tags and data used in the controller’s ladder program.
- 8-bit adreesị ohu
- Nha data 32-bit (adreesị 1 = nloghachi data 32-bit)
- Each MODBUS data register has a size of 2 bytes.
IHE:
- Before the controller is connected to the RS-485 network, it must first be properly configured.
- The communication settings are configured in the service parameters of the regulator (device).
IHE:
- Connecting unconfigured controllers to the RS-485 network will result in improper operation.
- Nwebiisinka - Enwere ike ịmegharị ma kesaa akwụkwọ a naanị site na ikikere nke njikwa Engo yana enwere ike ịnye naanị ndị ikike ma ọ bụ ụlọ ọrụ nwere nka nka chọrọ.
ntọala nkwurịta okwu
Ntọala nkwukọrịta RS-485
Pxx | Ọrụ | Uru | Nkọwa | Ọdabara uru |
Adikwa | MODBUS Adreesị ngwaọrụ ohu (ID). | 1-247 | MODBUS Adreesị ngwaọrụ ohu (ID). | 1 |
BAUD |
Baud |
4800 |
Bitrate (Baud) |
9600 |
9600 | ||||
19200 | ||||
38400 | ||||
PARI |
Parity bit – na-esetịpụ nha data maka nchọpụta njehie |
Ọ dịghị | Ọ dịghị |
Ọ dịghị |
Ọbụna | Ọbụna | |||
Odi | Odi | |||
KWỤSỊ | StopBit | 1 | 1 nkwụsịtụ | 1 |
2 | 2 nkwụsịtụ |
Na-akwado koodu ọrụ ndị a:
- 03 – reading n registers (Holding Registers)
- 04 – reading n registers (Input Registers)
- 06 – Write 1 register (Holding Register)
Ndebanye aha INPUT - naanị gụọ
Adreesị | Nweta | Nkọwa | Oke uru | pụtara | Ọdabara | |
Dec | Hex | |||||
0 | 0x0000 | R (#03) | Engo MODBUS Model ID | 1-247 | MODBUS Ohu (ID) | 1 |
1 | 0x0001 | R (#03) | Firmware-ụdị | 0x0001-0x9999 | 0x1110=1.1.10 (koodu BCD) | |
2 |
0x0002 |
R (#03) |
Working-state |
0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling
0b00001000 = Idle, sensor error |
||
3 | 0x0003 | R (#03) | Uru nke Integrated okpomọkụ ihe mmetụta, Celsius C | 50-500 | N-> temp=N/10 Celsius | |
5 |
0x0005 |
R (#03) |
Value of the External temperature sensor S1, °C |
50-500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
6 |
0x0006 |
R (#03) |
Value of the External temperature sensor S2, °C |
50-500 |
0 = Open (sensor break)/ contact open
1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C |
|
7 |
0x0007 |
R (#03) |
Steeti fan |
0b00000000 – 0b00001111 |
0b00000000= OFF
0b00000001= I Fan stage ala 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF 0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high |
|
8 | 0x0008 | R (#03) | Valve 1 stat | 0-1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
9 | 0x0009 | R (#03) | Valve 2 state | 0-1000 | 0 = OFF (valve closed)
1000 = ON / 100% (valve open) |
|
10 | 0x000A | R (#03) | Humidity measurement (with 5% indication accuracy) | 0-100 | N-> humidity=N % |
JIDE ndekọ – maka ịgụ na ide
Adreesị | Nweta | Nkọwa | Oke uru | pụtara | Ọdabara | |
Dec | Hex | |||||
0 | 0x0000 | R/W (#04) | Engo MODBUS Model ID | 1-247 | MODBUS Ohu (ID) | 1 |
234 |
0x00EA |
R/W (#06) |
Ụdị Fancoil |
1-6 |
1 = 2 pipe – only heating 2 = 2 pipe – only cooling
3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling 6 = 4 ọkpọkọ - kpo oku n'okpuru ala & jụrụ oyi site na fancoil |
0 |
235 |
0x00EB |
R/W (#06) |
S1-COM input configuration (Installer Parameters -P01) |
0 | Ntinye anaghị arụ ọrụ. Gbanwee n'etiti kpo oku na oyi na bọtịnụ. |
0 |
1 |
Input used to change heating/cooling via external contact connected to S1-COM:
– S1-COM open –> HEAT mode - S1-COM dị mkpụmkpụ -> ọnọdụ dị jụụ |
|||||
2 |
Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.
Onye njikwa na-agbanwe n'etiti kpo oku na ụdị jụrụ oyi dabere na ọkpọkọ okpomoku etinyere na paramita P17 na P18. |
|||||
3 |
Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode
– The pipe sensor will not allow the fan to run. The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18. |
|||||
4 | Ịkwalite ihe mmetụta ala na nhazi ikpo ọkụ nke ala. | |||||
236 |
0x00EC |
R/W (#06) |
S2-COM input configuration (Installer Parameters -P02) |
0 | Agbanyụrụ ntinye |
0 |
1 | Ihe mmetụta obibi (mgbe emepere kọntaktị, rụọ ọrụ ECO mode) | |||||
2 | Ihe mmetụta okpomọkụ nke mpụga | |||||
237 |
0x00ED |
R/W (#06) |
Ụdị ECO nwere ike ịhọrọ (Prameters installer -P07) | 0 | NO – Disabled |
0 |
1 | YES – Active | |||||
238 | 0x00EE | R/W (#06) | Uru ọnọdụ okpomọkụ nke ECO maka ikpo ọkụ (Permier installer -P08) | 50-450 | N-> temp=N/10 Celsius | 150 |
239 | 0x00EF | R/W (#06) | Uru ọnọdụ okpomọkụ nke ECO maka jụrụ oyi (Permier Installer -P09) | 50-450 | N-> temp=N/10 Celsius | 300 |
240 |
0x00F0 |
R/W (#06) |
ΔT of 0- 10V valve operation
This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17) |
1-20 |
N-> temp=N/10 Celsius |
10 |
241 |
0x00F1 |
R/W (#06) |
Fan on temperature for heating
The fan will start working if the temperature in the room drops below the preset by the value of the parameter (Installer parameters -P15) |
0-50 |
N-> temp=N/10 Celsius |
50 |
Adreesị | Nweta | Nkọwa | Oke uru | pụtara | Ọdabara | |||
Dec | Hex | |||||||
242 |
0x00F2 |
R/W (#06) |
Algọridim njikwa
(TPI or hysteresis) for the heating valve (Installer parameters -P18) |
0-20 |
0 = TPI
1 = ±0,1C 2 = ±0,2C… N-> temp=N/10 °C (±0,1…±2C) |
5 |
||
243 |
0x00F3 |
R/W (#06) |
FAN delta algorithm for cooling
The parameter determines the width of the temperature range in which the fan operates in cooling mode. If the room temperature increases, then: 1. When a small value of Delta FAN, the faster the response of the fan to a change in temperature temperature – faster the increase in speed.
2. When large value of Delta FAN, the slower fan increases speed. (Primate installer -P16) |
5-50 |
N-> temp=N/10 Celsius |
20 |
||
244 |
0x00F4 |
R/W (#06) |
Fan na okpomọkụ maka jụrụ oyi.
The fan will start working if the temperature in the room rises above the setpoint by the value of the parameter. (Installer parameters -P19) |
0-50 |
N-> temp=N/10 Celsius |
50 |
||
245 | 0x00F5 | R/W (#06) | Uru hysteresis maka valvụ jụrụ oyi (paramita ihe ntinye -P20) | 1-20 | N-> temp=N/10 °C (±0,1…±2C) | 5 | ||
246 |
0x00F6 |
R/W (#06) |
Mpaghara nwụrụ anwụ nke ịgbanwee kpo oku/ajụjụ oyi
In a 4-pipe system.The difference between the Set temperature and the room temperature, at which the controller will automatically change the heating/cooling operation mode. (Primate installer -P21) |
5-50 |
N-> temp=N/10 Celsius |
20 |
||
247 |
0x00F7 |
R/W (#06) |
Uru okpomọkụ na-agbanwe site na kpo oku gaa na jụrụ oyi
- 2-pipe usoro. In a 2-pipe system, below this value, the system switches to cooling mode and allows the fan to start. (Installer parameters -P22) |
270-400 |
N-> temp=N/10 Celsius |
300 |
||
248 |
0x00F8 |
R/W (#06) |
The value of the switching temperature from cooling to heating, 2-pipe system.
In a 2-pipe system, above this value, the system switches to heating mode and allows the fan to start. (Installer parameters -P23) |
100-250 |
N-> temp=N/10 Celsius |
100 |
||
249 |
0x00F9 |
R/W (#06) |
Na-ajụ oyi na igbu oge.
A parameter used in 4-pipe systems with automatic switching between heating and cooling. This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24) |
0 - 15 nkeji |
0 |
|||
250 |
0x00FA |
R/W (#06) |
Okpomọkụ ala kachasị elu
To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value. (Primate installer -P25) |
50-450 |
N-> temp=N/10 Celsius |
350 |
||
251 |
0x00FB |
R/W (#06) |
Okpomọkụ ala kacha nta
To protect the floor, heating will be switched on, when the floor sensor temperature drops below the minimum value. (Installer parameters -P26) |
50-450 |
N-> temp=N/10 Celsius |
150 |
||
254 | 0x00FE | R/W (#06) | Koodu PIN maka ntọala installer (Prameters installer -P28) | 0-1 | 0 = nkwarụ
1 = PIN (First default code 0000) |
0 |
Adreesị | Nweta | Nkọwa | Oke uru | pụtara | Ọdabara | |
Dec | Hex | |||||
255 | 0x00FF | R/W (#06) | Na-achọ koodu PIN iji kpọghee igodo (Installer Parameters -P29) | 0-1 | 0 = NIE
1 = TAK |
0 |
256 |
0x0100 |
R/W (#06) |
Ịrụ ọrụ fan (paramise installer -FAN) |
0-1 |
0 = NO – Inactive – output contacts for fan control are completely disabled
1 = EE |
1 |
257 | 0x0101 | R/W (#06) | Gbanyụọ ma ọ bụ gbanyụọ - ịgbanyụ onye nhazi | 0,1 | 0 = Gbanyụọ
1 = Gbanye |
1 |
258 |
0x0102 |
R/W (#06) |
Ụdị ọrụ |
0,1,3 |
0=Manual 1=Schedule
3=FROST – anti-freeze mode |
0 |
260 |
0x0104 |
R/W (#06) |
Ntọala ọsọ fan |
0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear
0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear |
||
262 | 0x0106 | R/W (#06) | Mkpọchi igodo | 0,1 | 0= akpọchiri akpọchi 1= akpọchiri akpọchi | 0 |
263 | 0x0107 | R/W (#06) | Gosipụta nchapụta (Prameters -P27) | 0-100 | N-> ihie =N% | 30 |
268 | 0C | R/W (#06) | Clock – minutes | 0-59 | Nkeji | 0 |
269 | 0x010D | R/W (#06) | Clock – hours | 0-23 | Oge awa | 0 |
270 | 0x010E | R/W (#06) | Clock – Day of the week (1=Monday) | 1-7 | Ụbọchị nke izu | 3 |
273 | 0x0111 | R/W (#06) | Set the temperature in schedule mode | 50-450 | N-> temp=N/10 Celsius | 210 |
274 | 0x0112 | R/W (#06) | Set temperature in manual mode | 50-450 | N-> temp=N/10 Celsius | 210 |
275 | 0x0113 | R/W (#06) | Set the temperature in FROST mode | 50 | N-> temp=N/10 Celsius | 50 |
279 | 0x0117 | R/W (#06) | Okpomọkụ setpoint kacha | 50-450 | N-> temp=N/10 Celsius | 350 |
280 | 0x0118 | R/W (#06) | Okpomọkụ setpoint kacha nta | 50-450 | N-> temp=N/10 Celsius | 50 |
284 | 0C | R/W (#06) | Accuracy of displayed temperature | 1, 5 | N-> temp=N/10 Celsius | 1 |
285 | 0x011D | R/W (#06) | Ndozi okpomọkụ gosipụtara | -3.0… 3.0°C | in steps of 0.5 | 0 |
288 | 0x0120 | R/W (#06) | Selection of system type – heating/cooling (dependent on the setting of input S1) | 0,1 | 0 = ikpo ọkụ
1 = Ịjụ oyi |
0 |
291 | 0x0123 | R/W (#06) | Minimum fan speed (Installer Parameters-P10) | 0-100 | N-> speed=N % | 10 |
292 | 0x0124 | R/W (#06) | Maximum fan speed (Installer Parameters-P11) | 0-100 | N-> speed=N % | 90 |
293 | 0x0125 | R/W (#06) | Speed of fan 1st gear in manual mode (Installer parameters-P12) | 0-100 | N-> speed=N % | 30 |
294 | 0x0126 | R/W (#06) | Speed of fan 2nd gear in manual mode (Installer parameters-P13) | 0-100 | N-> speed=N % | 60 |
295 | 0x0127 | R/W (#06) | Speed of fan 3rd gear in manual mode (Installer parameters-P14) | 0-100 | N-> speed=N % | 90 |
FAQ
- Q: What are the default communication settings for the EFAN-24 controller?
- A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
- Q: How can I access different data registers in the MODBUS RTU network?
- A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.
Akwụkwọ / akụrụngwa
![]() |
ENGO Controls EFAN-24 PWM Fan Speed Controller [pdf] Akwụkwọ ntuziaka EFAN-230B, EFAN-230W, EFAN-24 PWM Fan Speed Controller, EFAN-24, PWM Fan Speed Controller, Fan Speed Controller, Speed Controller |