ENGO-LOGO

ENGO Controls EFAN-24 PWM Fan Speed Controller

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-PRODUCT

Nkọwapụta

  • Protocol: MODBUS RTU
  • Ụdị njikwa: EFAN-24
  • Njikọ njikọ: RS485
  • Ọnụ adreesị: 1-247
  • Nha data: 32-bit

Ntuziaka ojiji ngwaahịa

  • Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
  • Failure to adhere to instructions may void the manufacturer’s responsibility.
  • The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
  • Network Connection: RS-485 serial interface
  • Data Configuration: Address, speed, and format are determined by hardware
  • Data Access: Full access to the controller’s ladder program data
  • Data Size: 2 bytes per MODBUS data register
  • Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
  • Unconfigured controllers should not be connected to the network to avoid operational issues.

ozi izugbe

Ozi izugbe gbasara MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-1

Enweghị ike ijikọ ihe karịrị wires abụọ na njedebe nke ọ bụla, na-ahụ na a na-eji nhazi "Daisy Chain" (na usoro) ma ọ bụ "ahịrị kwụ ọtọ" (direct) nhazi. A naghị atụ aro njikọ kpakpando ma ọ bụ netwọk (emeghe), n'ihi na ntụgharị uche n'ime eriri nwere ike ịkpata nrụrụ data.ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-2

Nhazi

  • Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
  • The manufacturer will not be held responsible for any conduct not following the instructions.

IHE:

There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.

Ọrụ netwọk MODBUS RTU – Ọnọdụ ohu

Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:

  • Network connection via RS-485 serial interface.
  • Address, communication speed, and byte format are determined by hardware configuration.
  • Na-enye ohere ịnweta mmadụ niile tags and data used in the controller’s ladder program.
  • 8-bit adreesị ohu
  • Nha data 32-bit (adreesị 1 = nloghachi data 32-bit)
  • Each MODBUS data register has a size of 2 bytes.

IHE:

  • Before the controller is connected to the RS-485 network, it must first be properly configured.
  • The communication settings are configured in the service parameters of the regulator (device).

IHE:

  • Connecting unconfigured controllers to the RS-485 network will result in improper operation.
  • Nwebiisinka - Enwere ike ịmegharị ma kesaa akwụkwọ a naanị site na ikikere nke njikwa Engo yana enwere ike ịnye naanị ndị ikike ma ọ bụ ụlọ ọrụ nwere nka nka chọrọ.

ntọala nkwurịta okwu

Ntọala nkwukọrịta RS-485

Pxx Ọrụ Uru Nkọwa Ọdabara uru
Adikwa MODBUS Adreesị ngwaọrụ ohu (ID). 1-247 MODBUS Adreesị ngwaọrụ ohu (ID). 1
 

BAUD

 

Baud

4800  

Bitrate (Baud)

 

9600

9600
19200
38400
 

PARI

 

Parity bit – na-esetịpụ nha data maka nchọpụta njehie

Ọ dịghị Ọ dịghị  

Ọ dịghị

Ọbụna Ọbụna
Odi Odi
KWỤSỊ StopBit 1 1 nkwụsịtụ 1
2 2 nkwụsịtụ

Na-akwado koodu ọrụ ndị a:

  • 03 – reading n registers (Holding Registers)
  • 04 – reading n registers (Input Registers)
  • 06 – Write 1 register (Holding Register)

Ndebanye aha INPUT - naanị gụọ

Adreesị Nweta Nkọwa Oke uru pụtara Ọdabara
Dec Hex
0 0x0000 R (#03) Engo MODBUS Model ID 1-247 MODBUS Ohu (ID) 1
1 0x0001 R (#03) Firmware-ụdị 0x0001-0x9999 0x1110=1.1.10 (koodu BCD)
 

2

 

0x0002

 

R (#03)

 

Working-state

0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling

0b00001000 = Idle, sensor error

3 0x0003 R (#03) Uru nke Integrated okpomọkụ ihe mmetụta, Celsius C 50-500 N-> temp=N/10 Celsius
 

5

 

0x0005

 

R (#03)

 

Value of the External temperature sensor S1, °C

 

50-500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

6

 

0x0006

 

R (#03)

 

Value of the External temperature sensor S2, °C

 

50-500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

 

7

 

 

0x0007

 

 

R (#03)

 

 

Steeti fan

 

 

0b00000000 –

0b00001111

0b00000000= OFF

0b00000001= I Fan stage ala 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF

0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high

8 0x0008 R (#03) Valve 1 stat 0-1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

9 0x0009 R (#03) Valve 2 state 0-1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

10 0x000A R (#03) Humidity measurement (with 5% indication accuracy) 0-100 N-> humidity=N %

JIDE ndekọ – maka ịgụ na ide

Adreesị Nweta Nkọwa Oke uru pụtara Ọdabara
Dec Hex
0 0x0000 R/W (#04) Engo MODBUS Model ID 1-247 MODBUS Ohu (ID) 1
 

 

234

 

 

0x00EA

 

 

R/W (#06)

 

 

Ụdị Fancoil

 

 

1-6

1 = 2 pipe – only heating 2 = 2 pipe – only cooling

3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling

6 = 4 ọkpọkọ - kpo oku n'okpuru ala & jụrụ oyi site na fancoil

 

 

0

 

 

 

 

 

 

 

 

235

 

 

 

 

 

 

 

 

0x00EB

 

 

 

 

 

 

 

 

R/W (#06)

 

 

 

 

 

 

 

 

S1-COM input configuration (Installer Parameters -P01)

0 Ntinye anaghị arụ ọrụ. Gbanwee n'etiti kpo oku na oyi na bọtịnụ.  

 

 

 

 

 

 

 

0

 

1

Input used to change heating/cooling via external contact connected to S1-COM:

– S1-COM open –> HEAT mode

- S1-COM dị mkpụmkpụ -> ọnọdụ dị jụụ

 

 

2

Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.

Onye njikwa na-agbanwe n'etiti kpo oku

na ụdị jụrụ oyi dabere na ọkpọkọ okpomoku etinyere na paramita P17 na P18.

 

 

3

Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode

– The pipe sensor will not allow the fan to run.

The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18.

4 Ịkwalite ihe mmetụta ala na nhazi ikpo ọkụ nke ala.
 

 

236

 

 

0x00EC

 

 

R/W (#06)

 

S2-COM input configuration (Installer Parameters -P02)

0 Agbanyụrụ ntinye  

 

0

1 Ihe mmetụta obibi (mgbe emepere kọntaktị, rụọ ọrụ ECO mode)
2 Ihe mmetụta okpomọkụ nke mpụga
 

237

 

0x00ED

 

R/W (#06)

Ụdị ECO nwere ike ịhọrọ (Prameters installer -P07) 0 NO – Disabled  

0

1 YES – Active
238 0x00EE R/W (#06) Uru ọnọdụ okpomọkụ nke ECO maka ikpo ọkụ (Permier installer -P08) 50-450 N-> temp=N/10 Celsius 150
239 0x00EF R/W (#06) Uru ọnọdụ okpomọkụ nke ECO maka jụrụ oyi (Permier Installer -P09) 50-450 N-> temp=N/10 Celsius 300
 

 

 

240

 

 

 

0x00F0

 

 

 

R/W (#06)

ΔT of 0- 10V valve operation

This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size

of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17)

 

 

 

1-20

 

 

 

N-> temp=N/10 Celsius

 

 

 

10

 

 

241

 

 

0x00F1

 

 

R/W (#06)

Fan on temperature for heating

The fan will start working if the temperature in the room drops below the preset

by the value of the parameter (Installer parameters -P15)

 

 

0-50

 

 

N-> temp=N/10 Celsius

 

 

50

Adreesị Nweta Nkọwa Oke uru pụtara Ọdabara
Dec Hex
 

242

 

0x00F2

 

R/W (#06)

Algọridim njikwa

(TPI or hysteresis) for the heating valve (Installer parameters -P18)

 

0-20

0 = TPI

1 = ±0,1C

2 = ±0,2C…

N-> temp=N/10 °C (±0,1…±2C)

 

5

 

 

 

 

 

243

 

 

 

 

 

0x00F3

 

 

 

 

 

R/W (#06)

FAN delta algorithm for cooling

The parameter determines the width of the temperature range in which the fan operates in cooling mode.

If the room temperature increases, then:

1. When a small value of Delta FAN,

the faster the response of the fan to a change in temperature

temperature – faster the increase in speed.

 

2. When large value of Delta FAN, the slower fan increases speed.

(Primate installer -P16)

 

 

 

 

 

5-50

 

 

 

 

 

N-> temp=N/10 Celsius

 

 

 

 

 

20

 

 

244

 

 

0x00F4

 

 

R/W (#06)

Fan na okpomọkụ maka jụrụ oyi.

The fan will start working if the temperature in the room rises above the

setpoint by the value of the parameter. (Installer parameters -P19)

 

 

0-50

 

 

N-> temp=N/10 Celsius

 

 

50

245 0x00F5 R/W (#06) Uru hysteresis maka valvụ jụrụ oyi (paramita ihe ntinye -P20) 1-20 N-> temp=N/10 °C (±0,1…±2C) 5
 

 

246

 

 

0x00F6

 

 

R/W (#06)

Mpaghara nwụrụ anwụ nke ịgbanwee kpo oku/ajụjụ oyi

In a 4-pipe system.The difference between the Set temperature and the room temperature,

at which the controller will automatically change the heating/cooling operation mode.

(Primate installer -P21)

 

 

5-50

 

 

N-> temp=N/10 Celsius

 

 

20

 

 

247

 

 

0x00F7

 

 

R/W (#06)

Uru okpomọkụ na-agbanwe site na kpo oku gaa na jụrụ oyi

- 2-pipe usoro.

In a 2-pipe system, below this value, the system switches to cooling mode

and allows the fan to start. (Installer parameters -P22)

 

 

270-400

 

 

N-> temp=N/10 Celsius

 

 

300

 

 

248

 

 

0x00F8

 

 

R/W (#06)

The value of the switching temperature from cooling to heating, 2-pipe system.

In a 2-pipe system, above this value, the system switches to heating mode

and allows the fan to start. (Installer parameters -P23)

 

 

100-250

 

 

N-> temp=N/10 Celsius

 

 

100

 

 

249

 

 

0x00F9

 

 

R/W (#06)

Na-ajụ oyi na igbu oge.

A parameter used in 4-pipe systems with automatic switching between heating and cooling.

This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24)

 

 

0 - 15 nkeji

 

 

0

 

 

250

 

 

0x00FA

 

 

R/W (#06)

Okpomọkụ ala kachasị elu

To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value.

(Primate installer -P25)

 

 

50-450

 

 

N-> temp=N/10 Celsius

 

 

350

 

 

251

 

 

0x00FB

 

 

R/W (#06)

Okpomọkụ ala kacha nta

To protect the floor, heating will be switched on, when the floor sensor temperature drops

below the minimum value. (Installer parameters -P26)

 

 

50-450

 

 

N-> temp=N/10 Celsius

 

 

150

254 0x00FE R/W (#06) Koodu PIN maka ntọala installer (Prameters installer -P28) 0-1 0 = nkwarụ

1 = PIN (First default code 0000)

0
Adreesị Nweta Nkọwa Oke uru pụtara Ọdabara
Dec Hex
255 0x00FF R/W (#06) Na-achọ koodu PIN iji kpọghee igodo (Installer Parameters -P29) 0-1 0 = NIE

1 = TAK

0
 

256

 

0x0100

 

R/W (#06)

Ịrụ ọrụ fan (paramise installer -FAN)  

0-1

0 = NO – Inactive – output contacts for fan control are completely disabled

1 = EE

 

1

257 0x0101 R/W (#06) Gbanyụọ ma ọ bụ gbanyụọ - ịgbanyụ onye nhazi 0,1 0 = Gbanyụọ

1 = Gbanye

1
 

258

 

0x0102

 

R/W (#06)

 

Ụdị ọrụ

 

0,1,3

0=Manual 1=Schedule

3=FROST – anti-freeze mode

 

0

 

 

 

260

 

 

 

0x0104

 

 

 

R/W (#06)

 

 

 

Ntọala ọsọ fan

0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear

0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear

262 0x0106 R/W (#06) Mkpọchi igodo 0,1 0= akpọchiri akpọchi 1= akpọchiri akpọchi 0
263 0x0107 R/W (#06) Gosipụta nchapụta (Prameters -P27) 0-100 N-> ihie =N% 30
268 0C R/W (#06) Clock – minutes 0-59 Nkeji 0
269 0x010D R/W (#06) Clock – hours 0-23 Oge awa 0
270 0x010E R/W (#06) Clock – Day of the week (1=Monday) 1-7 Ụbọchị nke izu 3
273 0x0111 R/W (#06) Set the temperature in schedule mode 50-450 N-> temp=N/10 Celsius 210
274 0x0112 R/W (#06) Set temperature in manual mode 50-450 N-> temp=N/10 Celsius 210
275 0x0113 R/W (#06) Set the temperature in FROST mode 50 N-> temp=N/10 Celsius 50
279 0x0117 R/W (#06) Okpomọkụ setpoint kacha 50-450 N-> temp=N/10 Celsius 350
280 0x0118 R/W (#06) Okpomọkụ setpoint kacha nta 50-450 N-> temp=N/10 Celsius 50
284 0C R/W (#06) Accuracy of displayed temperature 1, 5 N-> temp=N/10 Celsius 1
285 0x011D R/W (#06) Ndozi okpomọkụ gosipụtara -3.0… 3.0°C in steps of 0.5 0
288 0x0120 R/W (#06) Selection of system type – heating/cooling (dependent on the setting of input S1) 0,1 0 = ikpo ọkụ

1 = Ịjụ oyi

0
291 0x0123 R/W (#06) Minimum fan speed (Installer Parameters-P10) 0-100 N-> speed=N % 10
292 0x0124 R/W (#06) Maximum fan speed (Installer Parameters-P11) 0-100 N-> speed=N % 90
293 0x0125 R/W (#06) Speed of fan 1st gear in manual mode (Installer parameters-P12) 0-100 N-> speed=N % 30
294 0x0126 R/W (#06) Speed of fan 2nd gear in manual mode (Installer parameters-P13) 0-100 N-> speed=N % 60
295 0x0127 R/W (#06) Speed of fan 3rd gear in manual mode (Installer parameters-P14) 0-100 N-> speed=N % 90

FAQ

  • Q: What are the default communication settings for the EFAN-24 controller?
  • A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
  • Q: How can I access different data registers in the MODBUS RTU network?
  • A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.

Akwụkwọ / akụrụngwa

ENGO Controls EFAN-24 PWM Fan Speed Controller [pdf] Akwụkwọ ntuziaka
EFAN-230B, EFAN-230W, EFAN-24 PWM Fan Speed Controller, EFAN-24, PWM Fan Speed Controller, Fan Speed Controller, Speed Controller

Ntụaka

Hapụ ikwu

Agaghị ebipụta adreesị ozi-e gị. Akara mpaghara achọrọ akara *