ENGO-LOGO

Hoʻomalu ʻo ENGO iā EFAN-24 PWM Fan Speed ​​Controller

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-PRODUCT

Nā kikoʻī

  • Palekana: MODBUS RTU
  • Ke Ana Hoʻohālike: EFAN-24
  • ʻImi Kūkākūkā: RS485
  • Ka helu wahi helu: 1-247
  • Nui ʻikepili: 32-bit

Nā ʻōlelo hoʻohana huahana

  • Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
  • Failure to adhere to instructions may void the manufacturer’s responsibility.
  • The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
  • Network Connection: RS-485 serial interface
  • Data Configuration: Address, speed, and format are determined by hardware
  • Data Access: Full access to the controller’s ladder program data
  • Ka nui o ka ʻikepili: 2 bytes no ka papa inoa ʻikepili MODBUS
  • Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
  • Unconfigured controllers should not be connected to the network to avoid operational issues.

ʻIke nui

ʻIke nui e pili ana i MODBUS RTU
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-1

ʻAʻole hiki ke hoʻopili ʻia ma mua o ʻelua mau uea i kēlā me kēia pahu, e hōʻoia ana e hoʻohana ʻia kahi hoʻonohonoho "Daisy Chain" (ma ka series) a i ʻole "laina pololei" (pololei). ʻAʻole ʻoluʻolu ʻia ka hoʻohui ʻana i ka hōkū a i ʻole ka pūnaewele (wehe), no ka mea, hiki i ka noʻonoʻo ʻana i loko o ke kaula ke hoʻopōʻino i ka ʻikepili.ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-2

Hoʻonohonoho

  • Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
  • The manufacturer will not be held responsible for any conduct not following the instructions.

NĀ MEA:

There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.

ʻO ka hana pūnaewele MODBUS RTU - Ke ʻano kauā

Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:

  • Network connection via RS-485 serial interface.
  • Address, communication speed, and byte format are determined by hardware configuration.
  • Hāʻawi i ke komo i nā mea a pau tags and data used in the controller’s ladder program.
  • Helu kauā 8-bit
  • Nui ʻikepili 32-bit (1 helu helu = 32-bit hoʻihoʻi ʻikepili)
  • Each MODBUS data register has a size of 2 bytes.

NĀ MEA:

  • Before the controller is connected to the RS-485 network, it must first be properly configured.
  • The communication settings are configured in the service parameters of the regulator (device).

NĀ MEA:

  • Connecting unconfigured controllers to the RS-485 network will result in improper operation.
  • Kuleana kope - Hiki ke hana hou ʻia a hoʻolaha ʻia kēia palapala me ka ʻae pololei o Engo Controls a hāʻawi wale ʻia i nā poʻe i ʻae ʻia a i ʻole nā ​​​​hui me ka ʻike loea i koi ʻia.

hoʻonohonoho kamaʻilio

Nā hoʻonohonoho kamaʻilio RS-485

Pxx Hana Waiwai wehewehe Paʻamau waiwai
Addr MODBUS Slave wahi helu mea hana (ID). 1 – 247 MODBUS Slave wahi helu mea hana (ID). 1
 

BAUD

 

Baud

4800  

Pākuʻi Bit (Baud)

 

9600

9600
19200
38400
 

PARI

 

Parity bit - hoʻonohonoho i ka parity data no ka ʻike hewa

ʻAʻohe ʻAʻohe  

ʻAʻohe

ʻOiai ʻOiai
ʻAno ʻē ʻAno ʻē
KUMU StopBit 1 1 hooki iki 1
2 2 hooki iki

Kākoʻo i nā code hana penei:

  • 03 – reading n registers (Holding Registers)
  • 04 – reading n registers (Input Registers)
  • 06 – Write 1 register (Holding Register)

Hoʻopaʻa inoa INPUT - heluhelu wale nō

Heluhelu Komo wehewehe Laulā waiwai ʻO ke ʻano Paʻamau
Dek Hex
0 0x0000 R (#03) Engo MODBUS Model ID 1-247 Kauā MODBUS (ID) 1
1 0x0001 R (#03) Paʻa-Paʻa 0x0001-0x9999 0x1110=1.1.10 (BCD code)
 

2

 

0x0002

 

R (#03)

 

Working-state

0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling

0b00001000 = Idle, sensor error

3 0x0003 R (#03) Waiwai o ka mea ike wela hui, °C 50 – 500 N-> temp=N/10 °C
 

5

 

0x0005

 

R (#03)

 

Value of the External temperature sensor S1, °C

 

50 – 500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

6

 

0x0006

 

R (#03)

 

Value of the External temperature sensor S2, °C

 

50 – 500

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

 

7

 

 

0x0007

 

 

R (#03)

 

 

Kūlana pā

 

 

0b00000000 –

0b00001111

0b00000000= OFF

0b00000001= I Fan stage haahaa 0b00000010= II Fan stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF

0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high

8 0x0008 R (#03) Valve 1 stat 0 – 1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

9 0x0009 R (#03) Valve 2 state 0 – 1000 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

10 0x000A R (#03) Humidity measurement (with 5% indication accuracy) 0 – 100 N-> humidity=N %

HOLDING kakau inoa - no ka heluhelu a me ke kakau

Heluhelu Komo wehewehe Laulā waiwai ʻO ke ʻano Paʻamau
Dek Hex
0 0x0000 R/W (#04) Engo MODBUS Model ID 1-247 Kauā MODBUS (ID) 1
 

 

234

 

 

0x00EA

 

 

R/W (#06)

 

 

ʻAno Fancoil

 

 

1 – 6

1 = 2 pipe – only heating 2 = 2 pipe – only cooling

3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling

6 = 4 paipu – ka hoʻomehana ʻana ma lalo o ka papahele a me ka hoʻoluʻu ʻana e ka fancoil

 

 

0

 

 

 

 

 

 

 

 

235

 

 

 

 

 

 

 

 

0x00EB

 

 

 

 

 

 

 

 

R/W (#06)

 

 

 

 

 

 

 

 

S1-COM hoʻonohonoho hoʻokomo (nā ʻāpana hoʻonohonoho -P01)

0 ʻAʻole hoʻokomo. E hoʻololi i waena o ka hoʻomehana a me ka hoʻoluʻu me nā pihi.  

 

 

 

 

 

 

 

0

 

1

Input used to change heating/cooling via external contact connected to S1-COM:

– S1-COM open –> HEAT mode

- S1-COM pōkole -> ʻano COOL

 

 

2

Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.

Hoʻololi ka mea hoʻoponopono ma waena o ka hoʻomehana

a me nā ʻano hoʻoluʻu e pili ana i ka wela paipu i hoʻonohonoho ʻia ma nā ʻāpana P17 a me P18.

 

 

3

Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode

– The pipe sensor will not allow the fan to run.

The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18.

4 ʻO ka hoʻouluʻana o ka meaʻike papahele i ka hoʻonohonoho hoʻomehana honua.
 

 

236

 

 

0x00EC

 

 

R/W (#06)

 

S2-COM hoʻonohonoho hoʻokomo (nā ʻāpana hoʻonohonoho -P02)

0 Ua pio ka hookomo  

 

0

1 ʻO ka sensor noho (ke wehe ʻia nā mea pili, hoʻāla i ke ʻano ECO)
2 ʻIke wela waho
 

237

 

0x00ED

 

R/W (#06)

ʻO ke ʻano ECO hiki ke koho ʻia (nā ʻāpana hoʻonohonoho -P07) 0 NO – Disabled  

0

1 YES – Active
238 0x00EE R/W (#06) ʻO ka waiwai wela o ke ʻano ECO no ka hoʻomehana (nā ʻāpana hoʻonohonoho -P08) 50 – 450 N-> temp=N/10 °C 150
239 0x00EF R/W (#06) ʻO ka waiwai wela o ke ʻano ECO no ka hoʻoluʻu (nā ʻāpana hoʻonohonoho -P09) 50 – 450 N-> temp=N/10 °C 300
 

 

 

240

 

 

 

0x00F0

 

 

 

R/W (#06)

ΔT of 0- 10V valve operation

This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size

of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17)

 

 

 

1-20

 

 

 

N-> temp=N/10 °C

 

 

 

10

 

 

241

 

 

0x00F1

 

 

R/W (#06)

Pehi ma ka wela no ka hoʻomehana ʻana

The fan will start working if the temperature in the room drops below the preset

by the value of the parameter (Installer parameters -P15)

 

 

0 – 50

 

 

N-> temp=N/10 °C

 

 

50

Heluhelu Komo wehewehe Laulā waiwai ʻO ke ʻano Paʻamau
Dek Hex
 

242

 

0x00F2

 

R/W (#06)

Hoʻoponopono algorithm

(TPI or hysteresis) for the heating valve (Installer parameters -P18)

 

0 – 20

0 = TPI

1 = ±0,1C

2 = ±0,2C…

N-> temp=N/10 °C (±0,1…±2C)

 

5

 

 

 

 

 

243

 

 

 

 

 

0x00F3

 

 

 

 

 

R/W (#06)

FAN delta algorithm for cooling

The parameter determines the width of the temperature range in which the fan operates in cooling mode.

If the room temperature increases, then:

1. When a small value of Delta FAN,

the faster the response of the fan to a change in temperature

temperature – faster the increase in speed.

 

2. When large value of Delta FAN, the slower fan increases speed.

(Nā palena hoʻokomo -P16)

 

 

 

 

 

5 – 50

 

 

 

 

 

N-> temp=N/10 °C

 

 

 

 

 

20

 

 

244

 

 

0x00F4

 

 

R/W (#06)

Pehi ma ka mahana no ka hoʻomaloʻo.

The fan will start working if the temperature in the room rises above the

setpoint by the value of the parameter. (Installer parameters -P19)

 

 

0 – 50

 

 

N-> temp=N/10 °C

 

 

50

245 0x00F5 R/W (#06) ʻO ka waiwai Hysteresis no ka pahu hoʻomaha (nā ʻāpana hoʻonohonoho -P20) 1 – 20 N-> temp=N/10 °C (±0,1…±2C) 5
 

 

246

 

 

0x00F6

 

 

R/W (#06)

Wahi make o ka hoʻololi ʻana i ka hoʻomehana/hoʻoluʻu

In a 4-pipe system.The difference between the Set temperature and the room temperature,

at which the controller will automatically change the heating/cooling operation mode.

(Nā palena hoʻokomo -P21)

 

 

5 – 50

 

 

N-> temp=N/10 °C

 

 

20

 

 

247

 

 

0x00F7

 

 

R/W (#06)

ʻO ka hoʻololi ʻana i ka waiwai mai ka hoʻomehana ʻana i ka hoʻoluʻu

– ʻōnaehana 2-paipu.

In a 2-pipe system, below this value, the system switches to cooling mode

and allows the fan to start. (Installer parameters -P22)

 

 

270 – 400

 

 

N-> temp=N/10 °C

 

 

300

 

 

248

 

 

0x00F8

 

 

R/W (#06)

The value of the switching temperature from cooling to heating, 2-pipe system.

In a 2-pipe system, above this value, the system switches to heating mode

and allows the fan to start. (Installer parameters -P23)

 

 

100 – 250

 

 

N-> temp=N/10 °C

 

 

100

 

 

249

 

 

0x00F9

 

 

R/W (#06)

Hoʻopaneʻe ʻo ON.

A parameter used in 4-pipe systems with automatic switching between heating and cooling.

This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24)

 

 

0 – 15 min

 

 

0

 

 

250

 

 

0x00FA

 

 

R/W (#06)

Ka wela o ka papahele kiʻekiʻe

To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value.

(Nā palena hoʻokomo -P25)

 

 

50 – 450

 

 

N-> temp=N/10 °C

 

 

350

 

 

251

 

 

0x00FB

 

 

R/W (#06)

Ka wela wela o ka papahele

To protect the floor, heating will be switched on, when the floor sensor temperature drops

below the minimum value. (Installer parameters -P26)

 

 

50 – 450

 

 

N-> temp=N/10 °C

 

 

150

254 0x00FE R/W (#06) PIN code no nā hoʻonohonoho hoʻonohonoho (Nā Kūlana Hoʻokomo -P28) 0 – 1 0 = ua pio

1 = PIN (First default code 0000)

0
Heluhelu Komo wehewehe Laulā waiwai ʻO ke ʻano Paʻamau
Dek Hex
255 0x00FF R/W (#06) Ke koi nei i kahi code PIN no ka wehe ʻana i nā kī (nā mea hoʻonohonoho hoʻonohonoho -P29) 0 – 1 0 = NIE

1 = TAK

0
 

256

 

0x0100

 

R/W (#06)

ʻO ka hana pā (nā ʻāpana hoʻonohonoho -FAN)  

0 – 1

0 = NO – Inactive – output contacts for fan control are completely disabled

1 = ʻAe

 

1

257 0x0101 R/W (#06) Hoʻopau i ka mana - hoʻopau i ka mea hoʻoponopono 0,1 0=OFF

1=ON

1
 

258

 

0x0102

 

R/W (#06)

 

ʻAno hana

 

0,1,3

0=Manual 1=Schedule

3=FROST – anti-freeze mode

 

0

 

 

 

260

 

 

 

0x0104

 

 

 

R/W (#06)

 

 

 

Hoʻonohonoho ʻana i ka wikiwiki o ka pā

0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear

0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear

262 0x0106 R/W (#06) Laka kī 0,1 0 = wehe ʻia 1 = laka 0
263 0x0107 R/W (#06) Hōʻike ʻōlinolino (nā ʻāpana hoʻonohonoho -P27) 0-100 N-> Olino =N% 30
268 0x010C. R/W (#06) Clock – minutes 0-59 Nā minuke 0
269 0x010D R/W (#06) Clock – hours 0-23 Nā hola 0
270 0x010E R/W (#06) Clock – Day of the week (1=Monday) 1~7 La o ka pule 3
273 0x0111 R/W (#06) Set the temperature in schedule mode 50-450 N-> temp=N/10 °C 210
274 0x0112 R/W (#06) Set temperature in manual mode 50-450 N-> temp=N/10 °C 210
275 0x0113 R/W (#06) Set the temperature in FROST mode 50 N-> temp=N/10 °C 50
279 0x0117 R/W (#06) ʻO ka mahana hoʻonohonoho kiʻekiʻe 50-450 N-> temp=N/10 °C 350
280 0x0118 R/W (#06) ʻO ka mahana hoʻonohonoho liʻiliʻi 50-450 N-> temp=N/10 °C 50
284 0x011C. R/W (#06) Accuracy of displayed temperature 1, 5 N-> temp=N/10 °C 1
285 0x011D R/W (#06) Hoʻoponopono i ka wela i hōʻike ʻia -3.0… 3.0°C in steps of 0.5 0
288 0x0120 R/W (#06) Selection of system type – heating/cooling (dependent on the setting of input S1) 0,1 0 = Pumehana

1 = Hooluu

0
291 0x0123 R/W (#06) Minimum fan speed (Installer Parameters-P10) 0-100 N-> wikiwiki=N % 10
292 0x0124 R/W (#06) Maximum fan speed (Installer Parameters-P11) 0-100 N-> wikiwiki=N % 90
293 0x0125 R/W (#06) Speed of fan 1st gear in manual mode (Installer parameters-P12) 0-100 N-> wikiwiki=N % 30
294 0x0126 R/W (#06) Speed of fan 2nd gear in manual mode (Installer parameters-P13) 0-100 N-> wikiwiki=N % 60
295 0x0127 R/W (#06) Speed of fan 3rd gear in manual mode (Installer parameters-P14) 0-100 N-> wikiwiki=N % 90

FAQ

  • Q: What are the default communication settings for the EFAN-24 controller?
  • A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
  • Q: How can I access different data registers in the MODBUS RTU network?
  • A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.

Palapala / Punawai

Hoʻomalu ʻo ENGO iā EFAN-24 PWM Fan Speed ​​Controller [pdf] Palapala Aʻo
EFAN-230B, EFAN-230W, EFAN-24 PWM Pākuʻi Kipi, EFAN-24, PWM Pākuʻi Paʻa, Pepa Pepa, Pepa Paʻa

Nā kuhikuhi

Waiho i kahi manaʻo

ʻAʻole e paʻi ʻia kāu leka uila. Hōʻailona ʻia nā kahua i makemake ʻia *