ENGO- लोगो

ENGO कंट्रोल्स EFAN-24 PWM फॅन स्पीड कंट्रोलर

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-PRODUCT

तपशील

  • प्रोटोकॉल: MODBUS RTU
  • कंट्रोलर मॉडेल: EFAN-24
  • कम्युनिकेशन इंटरफेस: RS485
  • पत्ता श्रेणी: १-२४७
  • डेटा आकार: ३२-बिट

उत्पादन वापर सूचना

  • Configuration of the EFAN-24 controller must be carried out by a qualified person with appropriate authorization and technical knowledge, following country and EU standards and regulations.
  • Failure to adhere to instructions may void the manufacturer’s responsibility.
  • The controller can operate as a slave in a MODBUS RTU network with specific features and communication requirements. Ensure proper wiring configuration to avoid data corruption.
  • Network Connection: RS-485 serial interface
  • Data Configuration: Address, speed, and format are determined by hardware
  • Data Access: Full access to the controller’s ladder program data
  • डेटा आकार: प्रति MODBUS डेटा रजिस्टर २ बाइट्स
  • Before connecting the controller to the RS-485 network, ensure proper configuration of communication settings, including address, baud rate, parity, and stop bits.
  • Unconfigured controllers should not be connected to the network to avoid operational issues.

सामान्य माहिती

MODBUS RTU बद्दल सामान्य माहिती
The MODBUS RTU structure uses a master-slave system to exchange messages. It allows a maximum of 247 slaves, but only one master. The master controls the operation of the network, and only it sends the request. Slaves do not undertake transmissions on their own. Each communication begins with the master requesting the Slave, which responds to the master with what it has been asked. The master (computer) communicates with slaves (controllers) in two-wire RS-485 mode. This uses data lines A+ and B- for data exchange, which MUST be one twisted pair.

ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-1

प्रत्येक टर्मिनलला दोनपेक्षा जास्त वायर जोडता येणार नाहीत, जेणेकरून "डेझी चेन" (मालिकेत) किंवा "सरळ रेषा" (थेट) कॉन्फिगरेशन वापरले जाईल. तारा किंवा नेटवर्क (ओपन) कनेक्शनची शिफारस केलेली नाही, कारण केबलमधील परावर्तनांमुळे डेटा करप्ट होऊ शकतो.ENGO-Controls-EFAN-24-PWM-Fan-Speed-Controller-FIG-2

कॉन्फिगरेशन

  • Configuration must be carried out by a qualified person with the appropriate authorization and technical knowledge, following the standards and regulations of the country and the EU.
  • The manufacturer will not be held responsible for any conduct not following the instructions.

लक्ष द्या:

There may be additional protection requirements for the entire installation and configuration, which the installer/programmer is responsible for maintaining.

MODBUS RTU नेटवर्क ऑपरेशन - स्लेव्ह मोड

Engo’s MODBUS controller has the following features when operating as a slave in a MODBUS RTU network:

  • Network connection via RS-485 serial interface.
  • Address, communication speed, and byte format are determined by hardware configuration.
  • सर्वांना प्रवेश देते tags and data used in the controller’s ladder program.
  • 8-बिट गुलाम पत्ता
  • 32-बिट डेटा आकार (1 पत्ता = 32-बिट डेटा रिटर्न)
  • Each MODBUS data register has a size of 2 bytes.

लक्ष द्या:

  • Before the controller is connected to the RS-485 network, it must first be properly configured.
  • The communication settings are configured in the service parameters of the regulator (device).

लक्ष द्या:

  • Connecting unconfigured controllers to the RS-485 network will result in improper operation.
  • कॉपीराइट – हे दस्तऐवज केवळ एंगो कंट्रोल्सच्या स्पष्ट परवानगीनेच पुनरुत्पादित आणि वितरित केले जाऊ शकते आणि आवश्यक तांत्रिक कौशल्य असलेल्या अधिकृत व्यक्ती किंवा कंपन्यांनाच प्रदान केले जाऊ शकते.

संप्रेषण सेटिंग्ज

RS-485 संप्रेषण सेटिंग्ज

Pxx कार्य मूल्य वर्णन डीफॉल्ट मूल्य
एडीआर MODBUS स्लेव्ह डिव्हाइस पत्ता (आयडी). ८७८ - १०७४ MODBUS स्लेव्ह डिव्हाइस पत्ता (आयडी). 1
 

BAUD

 

बॉड

4800  

बिटरेट (बॉड)

 

9600

9600
19200
38400
 

पारी

 

पॅरिटी बिट - त्रुटी शोधण्यासाठी डेटा पॅरिटी सेट करते

काहीही नाही काहीही नाही  

काहीही नाही

अगदी अगदी
विषम विषम
थांबा स्टॉपबिट 1 1 स्टॉप बिट 1
2 2 स्टॉप बिट

खालील फंक्शन कोडना समर्थन देते:

  • 03 – reading n registers (Holding Registers)
  • 04 – reading n registers (Input Registers)
  • 06 – Write 1 register (Holding Register)

INPUT नोंदणी – फक्त वाचा

पत्ता प्रवेश वर्णन मूल्य श्रेणी म्हणजे डीफॉल्ट
डिसें हेक्स
0 0x0000 R (#03) Engo MODBUS Model ID 1-247 मॉडबस स्लेव्ह (आयडी) 1
1 0x0001 R (#03) फर्मवेअर-आवृत्ती 0x0001-0x9999 0x1110=1.1.10 (BCD कोड)
 

2

 

0x0002

 

R (#03)

 

Working-state

0b00000010=Idle, switch OFF 0b00000000=Idle, room meet temperature 0b10000001=Heating 0b10001000=Cooling

0b00001000 = Idle, sensor error

3 0x0003 R (#03) एकात्मिक तापमान सेन्सरचे मूल्य, °C ८७८ - १०७४ N-> तापमान = N/10 °C
 

5

 

0x0005

 

R (#03)

 

Value of the External temperature sensor S1, °C

 

८७८ - १०७४

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

6

 

0x0006

 

R (#03)

 

Value of the External temperature sensor S2, °C

 

८७८ - १०७४

0 = Open (sensor break)/ contact open

1 =Closed (sensor short circuit )/ contact closed N-> temp=N/10 °C

 

 

7

 

 

0x0007

 

 

R (#03)

 

 

पंख्याची अवस्था

 

 

0b00000000 –

0b00001111

0b00000000= OFF

0b00000001= I Fan stage कमी 0b00000010= II पंखा stage medium 0b00000100= III Fan state high 0b00001000= Auto – OFF

0b00001001= Auto – I low 0b00001010= Auto – II medium 0b00001100= Auto – III high

8 0x0008 R (#03) Valve 1 stat ८७८ - १०७४ 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

9 0x0009 R (#03) Valve 2 state ८७८ - १०७४ 0 = OFF (valve closed)

1000 = ON / 100% (valve open)

10 0x000A R (#03) Humidity measurement (with 5% indication accuracy) ८७८ - १०७४ N-> humidity=N %

होल्डिंग रजिस्टर्स – वाचन आणि लेखनासाठी

पत्ता प्रवेश वर्णन मूल्य श्रेणी म्हणजे डीफॉल्ट
डिसें हेक्स
0 0x0000 R/W (#04) Engo MODBUS Model ID 1-247 मॉडबस स्लेव्ह (आयडी) 1
 

 

234

 

 

0x00EA

 

 

R/W (#06)

 

 

फॅनकॉइल प्रकार

 

 

८७८ - १०७४

1 = 2 pipe – only heating 2 = 2 pipe – only cooling

3 = 2 pipe – heating & cooling 4 = 2 pipe – underfloor heating 5 = 4 pipe – heating & cooling

६ = ४ पाईप - फॅनकॉइलद्वारे अंडरफ्लोर हीटिंग आणि कूलिंग

 

 

0

 

 

 

 

 

 

 

 

235

 

 

 

 

 

 

 

 

0x00EB

 

 

 

 

 

 

 

 

R/W (#06)

 

 

 

 

 

 

 

 

S1-COM इनपुट कॉन्फिगरेशन (इंस्टॉलर पॅरामीटर्स -P01)

0 इनपुट निष्क्रिय आहे. बटणे वापरून गरम करणे आणि थंड करणे यामध्ये बदल करा.  

 

 

 

 

 

 

 

0

 

1

Input used to change heating/cooling via external contact connected to S1-COM:

– S1-COM open –> HEAT mode

– S1-COM शॉर्टेड –> कूल मोड

 

 

2

Input used to AUTOMATICALLY change heating/cooling based on PIPE TEMPERATURE in a 2-pipe system.

कंट्रोलर हीटिंग दरम्यान स्विच करतो

आणि P17 आणि P18 पॅरामीटर्समध्ये सेट केलेल्या पाईप तापमानावर आधारित कूलिंग मोड.

 

 

3

Allow fan operation dependent on the temperature measurement on the pipe. For example, if the temperature on the pipe is too low, and the controller is in heating mode

– The pipe sensor will not allow the fan to run.

The change of heating/cooling is done manually, using the buttons. Values for fan control based on pipe temperature are set in parameters P17 and P18.

4 फ्लोअर हीटिंग कॉन्फिगरेशनमध्ये फ्लोअर सेन्सरचे सक्रियकरण.
 

 

236

 

 

0x00EC

 

 

R/W (#06)

 

S2-COM इनपुट कॉन्फिगरेशन (इंस्टॉलर पॅरामीटर्स -P02)

0 इनपुट अक्षम केले  

 

0

1 ऑक्युपन्सी सेन्सर (जेव्हा संपर्क उघडले जातात, तेव्हा ECO मोड सक्रिय करा)
2 बाह्य तापमान सेन्सर
 

237

 

0x00ED

 

R/W (#06)

निवडण्यायोग्य ECO मोड (इंस्टॉलर पॅरामीटर्स -P07) 0 NO – Disabled  

0

1 YES – Active
238 0x00EE R/W (#06) हीटिंगसाठी ECO मोड तापमान मूल्य (इंस्टॉलर पॅरामीटर्स -P08) ८७८ - १०७४ N-> तापमान = N/10 °C 150
239 0x00EF R/W (#06) कूलिंगसाठी ECO मोड तापमान मूल्य (इंस्टॉलर पॅरामीटर्स -P09) ८७८ - १०७४ N-> तापमान = N/10 °C 300
 

 

 

240

 

 

 

0x00F0

 

 

 

R/W (#06)

ΔT of 0- 10V valve operation

This parameter is responsible for the modulated 0- 10V output of the valve. – In heating mode: If the room temperature drops, the valve opens proportionally to the delta size. – In cooling mode: If the room temperature increases, the valve opens in proportion to the size

of the delta. The valve opening starts from the room set temperature. (Installer parameters -P17)

 

 

 

1-20

 

 

 

N-> तापमान = N/10 °C

 

 

 

10

 

 

241

 

 

0x00F1

 

 

R/W (#06)

गरम करण्यासाठी तापमानावर पंखा

The fan will start working if the temperature in the room drops below the preset

by the value of the parameter (Installer parameters -P15)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

50

पत्ता प्रवेश वर्णन मूल्य श्रेणी म्हणजे डीफॉल्ट
डिसें हेक्स
 

242

 

0x00F2

 

R/W (#06)

नियंत्रण अल्गोरिदम

(TPI or hysteresis) for the heating valve (Installer parameters -P18)

 

८७८ - १०७४

0 = TPI

1 = ±0,1C

2 = ±0,2C…

N-> temp=N/10 °C (±0,1…±2C)

 

5

 

 

 

 

 

243

 

 

 

 

 

0x00F3

 

 

 

 

 

R/W (#06)

FAN delta algorithm for cooling

The parameter determines the width of the temperature range in which the fan operates in cooling mode.

If the room temperature increases, then:

1. When a small value of Delta FAN,

the faster the response of the fan to a change in temperature

temperature – faster the increase in speed.

 

2. When large value of Delta FAN, the slower fan increases speed.

(इंस्टॉलर पॅरामीटर्स -P16)

 

 

 

 

 

८७८ - १०७४

 

 

 

 

 

N-> तापमान = N/10 °C

 

 

 

 

 

20

 

 

244

 

 

0x00F4

 

 

R/W (#06)

थंड होण्यासाठी तापमानावर पंखा.

The fan will start working if the temperature in the room rises above the

setpoint by the value of the parameter. (Installer parameters -P19)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

50

245 0x00F5 R/W (#06) कूलिंग व्हॉल्व्हसाठी हिस्टेरेसिस मूल्य (इंस्टॉलर पॅरामीटर्स -P20) ८७८ - १०७४ N-> temp=N/10 °C (±0,1…±2C) 5
 

 

246

 

 

0x00F6

 

 

R/W (#06)

स्विचिंग हीटिंग/कूलिंगचा डेड झोन

In a 4-pipe system.The difference between the Set temperature and the room temperature,

at which the controller will automatically change the heating/cooling operation mode.

(इंस्टॉलर पॅरामीटर्स -P21)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

20

 

 

247

 

 

0x00F7

 

 

R/W (#06)

गरम करण्यापासून थंड करण्यापर्यंत तापमानाचे स्विचिंग मूल्य

- २-पाईप सिस्टम.

In a 2-pipe system, below this value, the system switches to cooling mode

and allows the fan to start. (Installer parameters -P22)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

300

 

 

248

 

 

0x00F8

 

 

R/W (#06)

The value of the switching temperature from cooling to heating, 2-pipe system.

In a 2-pipe system, above this value, the system switches to heating mode

and allows the fan to start. (Installer parameters -P23)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

100

 

 

249

 

 

0x00F9

 

 

R/W (#06)

कूलिंग चालू होण्यास विलंब.

A parameter used in 4-pipe systems with automatic switching between heating and cooling.

This avoids too frequent switching between heating and cooling modes and oscillation of the room temperature. (Installer parameters -P24)

 

 

0 - 15 मि

 

 

0

 

 

250

 

 

0x00FA

 

 

R/W (#06)

कमाल मजला तापमान

To protect the floor, heating will be turned off when the floor sensor temperature rises above the maximum value.

(इंस्टॉलर पॅरामीटर्स -P25)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

350

 

 

251

 

 

0x00FB

 

 

R/W (#06)

किमान मजला तापमान

To protect the floor, heating will be switched on, when the floor sensor temperature drops

below the minimum value. (Installer parameters -P26)

 

 

८७८ - १०७४

 

 

N-> तापमान = N/10 °C

 

 

150

254 0x00FE R/W (#06) इंस्टॉलर सेटिंग्जसाठी पिन कोड (इंस्टॉलर पॅरामीटर्स -P28) ८७८ - १०७४ 0 = अक्षम

1 = PIN (First default code 0000)

0
पत्ता प्रवेश वर्णन मूल्य श्रेणी म्हणजे डीफॉल्ट
डिसें हेक्स
255 0x00FF R/W (#06) कळा अनलॉक करण्यासाठी पिन कोड आवश्यक आहे (इंस्टॉलर पॅरामीटर्स -P29) ८७८ - १०७४ 0 = NIE

1 = TAK

0
 

256

 

0x0100

 

R/W (#06)

पंखा ऑपरेशन (इंस्टॉलर पॅरामीटर्स -FAN)  

८७८ - १०७४

0 = NO – Inactive – output contacts for fan control are completely disabled

१ = होय

 

1

257 0x0101 R/W (#06) पॉवर चालू/बंद - रेग्युलेटर बंद करणे 0,1 0 = बंद

1 = चालू

1
 

258

 

0x0102

 

R/W (#06)

 

ऑपरेशन मोड

 

0,1,3

0=Manual 1=Schedule

3=FROST – anti-freeze mode

 

0

 

 

 

260

 

 

 

0x0104

 

 

 

R/W (#06)

 

 

 

फॅन गती सेटिंग

0b000000= OFF – fan off 0b00000001= I (low) fan gear 0b000010= II (medium) fan gear 0b00000100= III (high) fan gear

0b00001000= Automatic fan speed – OFF 0b00001001= Automatic fan speed – 1st gear 0b00001010= Automatic fan speed – 2nd gear 0b00001100= Automatic fan speed – 3rd gear

262 0x0106 R/W (#06) चावी लॉक 0,1 ०=अनलॉक केलेले १=लॉक केलेले 0
263 0x0107 R/W (#06) डिस्प्ले ब्राइटनेस (इंस्टॉलर पॅरामीटर्स -P27) 0-100 N-> ब्राइटनेस = N% 30
268 0x010 सी R/W (#06) Clock – minutes 0-59 मिनिटे 0
269 0x010D R/W (#06) Clock – hours 0-23 तास 0
270 0x010E R/W (#06) Clock – Day of the week (1=Monday) 1~7 आठवड्याचा दिवस 3
273 0x0111 R/W (#06) Set the temperature in schedule mode 50-450 N-> तापमान = N/10 °C 210
274 0x0112 R/W (#06) Set temperature in manual mode 50-450 N-> तापमान = N/10 °C 210
275 0x0113 R/W (#06) Set the temperature in FROST mode 50 N-> तापमान = N/10 °C 50
279 0x0117 R/W (#06) कमाल सेटपॉइंट तापमान 50-450 N-> तापमान = N/10 °C 350
280 0x0118 R/W (#06) किमान सेटपॉइंट तापमान 50-450 N-> तापमान = N/10 °C 50
284 0x011 सी R/W (#06) Accuracy of displayed temperature 1, 5 N-> तापमान = N/10 °C 1
285 0x011D R/W (#06) प्रदर्शित तापमानात सुधारणा -3.0… 3.0° से in steps of 0.5 0
288 0x0120 R/W (#06) Selection of system type – heating/cooling (dependent on the setting of input S1) 0,1 0 = गरम करणे

1 = थंड करणे

0
291 0x0123 R/W (#06) Minimum fan speed (Installer Parameters-P10) 0-100 N-> वेग = N % 10
292 0x0124 R/W (#06) Maximum fan speed (Installer Parameters-P11) 0-100 N-> वेग = N % 90
293 0x0125 R/W (#06) Speed of fan 1st gear in manual mode (Installer parameters-P12) 0-100 N-> वेग = N % 30
294 0x0126 R/W (#06) Speed of fan 2nd gear in manual mode (Installer parameters-P13) 0-100 N-> वेग = N % 60
295 0x0127 R/W (#06) Speed of fan 3rd gear in manual mode (Installer parameters-P14) 0-100 N-> वेग = N % 90

वारंवार विचारले जाणारे प्रश्न

  • Q: What are the default communication settings for the EFAN-24 controller?
  • A: The default settings include a slave device address of 1, the baud rate of 9600, no parity bit, and one stop bit.
  • Q: How can I access different data registers in the MODBUS RTU network?
  • A: Use the appropriate function codes such as #03 for reading holding registers or #06 for writing a single register. Each register has specific data values related to controller parameters.