daviteq LogoLevel Indicating
Controller LFC128-2
USER GUIDE FOR LEVEL INDICATING CONTROLLER LFC128-2
LFC128-2-MN-EN-01 JUN-2020

LFC128-2 Назорати намоиши сатҳи пешрафта

Ин ҳуҷҷат барои маҳсулоти зерин татбиқ карда мешавад

SKU LFC128-2 HW Вер. 1.0 FW Вер. 1.1
Рамзи адад LFC128-2 Level Indicating Controller, 4AI/DI, 4DI, 4xRelay, 1xPulse Output, 2 x RS485/ModbusRTU-Slave Communication

Функсияҳо Сабти тағирот

HW Вер. FW Вер. Рӯзи нашр Функсияҳо Тағйир
1.0 1.1 JUN-2020

Муқаддима

LFC128-2 is an advanced level display controller. The product integrates Modbus RTU interface to help PLC / SCADA / BMS and any IoT port can connect to monitor. LFC128-2 has a simple yet powerful design with 4 AI / DI, 4 DI, 4 Relays, 1 Pulse pulse output, 2 RS485 Slave ModbusRTU allowing them to connect with multiple devices easily. With advanced technology that provides high stability and reliability, many functions, easy installation with touch screen and friendly interface helps visually monitor level.

daviteq LFC128 2 Advanced Level Display Controller

Мушаххасоти

Вурудҳои рақамӣ 04 x Ports, opto-coupler, 4.7 kohms input resisrtance, 5000V rms isolation, Logic 0 (0-1VDC), Logic 1 (5-24VDC), Functions: logic status 0/1 or Pulse counting (32 bit counter with max 4kHz pulse)
Вурудоти аналогӣ 04 x Ports, select between 0-10VDC input or 0-20mA input, 12 bit Resolution, can be configured as Digital input by DIP switch (max 10VDC input) The AI1 port is a 0-10 VDC / 4-20 mA level sensor connection port
Натиҷаи реле 04 x Ports, electro-mechanical Relays, SPDT, contact rating 24VDC/2A or 250VAC/5A, LED indicators
Натиҷаи импулс 01 x Ports, open-collector, opto-isolation, max 10mA and 80VDC, On/off control, Pulser (max 2.5Khz, max 65535 Pulses) or PWM (max 2.5Khz)
Муошират 02 x ModbusRTU-Slave, RS485, speed 9600 or 19200, LED indicator
Тугмаи барқароркунӣ For resetting 02 x RS485 Slave port to default setting (9600, None parity, 8 bit)
Навъи экран Шишаи ламсӣ
Таъмини нерӯ 9..36VDC
Истеъмол 200mA @ 24VDC supply
Навъи васлкунӣ Монтажи панел
Блоки терминал pitch 5.0mm, rating 300VAC, wire size 12-24AWG
Ҳарорати корӣ / намӣ 0..60 degC / 95%RH non-condensing
Андоза H93xW138xD45
Вазни холис 390 грамм

Суратҳои маҳсулот

daviteq LFC128 2 Advanced Level Display Controller  - Picturesdaviteq LFC128 2 Advanced Level Display Controller  - Pictures 1

Принсипи амалиёт

daviteq LFC128 2 Advanced Level Display Controller  - Pictures 2

5.1 Муоширати Modbus

daviteq LFC128 2 Advanced Level Display Controller  - communication

02 x RS485/ModbusRTU-Slave
Протокол: Modbus RTU
Адрес: ш. 1 – 247, 0 is the Broadcast address
Меъёри интиқол: 9600, 19200
Баробарӣ: ҳеҷ, тоқ, ҳатто

  • Status indicator LED:
  • Led on: modbus communication OK
  • Led blinking: received data but modbus communication incorrect, due to wrong Modbus configuration: address, baudrate
  • Led off: LFC128-2 received no data, check the connection

Memmap ба қайд гирифта мешавад
READ uses command 03, WRITE uses command 16
Конфигуратсияи пешфарз:

  • Адрес: 1
  • Baudrate slave 1: 9600
  • Parity slave 1: none
  • Baudrate slave 2: 9600
  • Parity slave 2: none
Бақайдгирии Modbus Hex adr # of registersdaviteq LFC128 2 Advanced Level Display Controller  - Icon Тавсифи Диапазон Пешфарз Формат Амвол Шарҳ
0 0 2 маълумот дар бораи дастгоҳ LFC1 сатр Хондан
8 8 1 DI1       DI2: digital status 0-1 uint8 Хондан H_byte: DI1 L_byte: DI2
9 9 1 DI3       DI4: digital status 0-1 uint8 Хондан H_byte: DI3 L_byte: DI4
10 A 1 AI1      AI2: digital status 0-1 uint8 Хондан H_byte: AI1 L_byte: AI2
11 B 1 AI3      AI4: digital status 0-1 uint8 Хондан H_byte: AI3 L_byte: AI4
12 C 1 AI1: analog value uint16 Хондан
13 D 1 AI2: analog value uint16 Хондан
14 E 1 AI3: analog value uint16 Хондан
15 F 1 AI4: analog value uint16 Хондан
16 10 2 AI1: scaled value шино кардан Хондан
18 12 2 AI2: scaled value шино кардан Хондан
20 14 2 AI3: scaled value шино кардан Хондан
22 16 2 AI4: scaled value шино кардан Хондан
24 18 1 эстафетаи 1 0-1 uint16 Хондан
25 19 1 эстафетаи 2 0-1 uint16 Хондан
26 1A 1 эстафетаи 3 0-1 uint16 Хондан
27 1B 1 эстафетаи 4 0-1 uint16 Хондан
28 1C 1 open collector ctrl 0-3 uint16 Хондан/навиштан 0: off 1: on 2: pwm, pulse continuously 3: pulse, when enough pulse number, ctrl = 0
30 1E 2 counter DI1 uint32 Хондан/навиштан counter writable, erasable
32 20 2 counter DI2 uint32 Хондан/навиштан counter writable, erasable
34 22 2 counter DI3 uint32 Хондан/навиштан counter writable, erasable
36 24 2 counter DI4 uint32 Хондан/навиштан counter writable, erasable
38 26 2 counter AI1 uint32 Хондан/навиштан counter writable, erasable, max frequency 10Hz
40 28 2 counter AI2 uint32 Хондан/навиштан counter writable, erasable, max frequency 10Hz
42 2A 2 counter AI3 uint32 Хондан/навиштан counter writable, erasable, max frequency 10Hz
44 2C 2 counter AI4 uint32 Хондан/навиштан counter writable, erasable, max frequency 10Hz
46 2E 2 DI1: time on uint32 Хондан/навиштан сек
48 30 2 DI2: time on uint32 Хондан/навиштан сек
50 32 2 DI3: time on uint32 Хондан/навиштан сек
52 34 2 DI4: time on uint32 Хондан/навиштан сек
54 36 2 AI1: time on uint32 Хондан/навиштан сек
56 38 2 AI2: time on uint32 Хондан/навиштан сек
58 3A 2 AI3: time on uint32 Хондан/навиштан сек
60 3C 2 AI4: time on uint32 Хондан/навиштан сек
62 3E 2 DI1: time off uint32 Хондан/навиштан сек
64 40 2 DI2: time off uint32 Хондан/навиштан сек
66 42 2 DI3: time off uint32 Хондан/навиштан сек
68 44 2 DI4: time off uint32 Хондан/навиштан сек
70 46 2 AI1: time off uint32 Хондан/навиштан сек
72 48 2 AI2: time off uint32 Хондан/навиштан сек
74 4A 2 AI3: time off uint32 Хондан/навиштан сек
76 4C 2 AI4: time off uint32 Хондан/навиштан сек
128 80 2 counter DI1 uint32 Хондан counter cannot write, erase
130 82 2 counter DI2 uint32 Хондан counter cannot write, erase
132 84 2 counter DI3 uint32 Хондан counter cannot write, erase
134 86 2 counter DI4 uint32 Хондан counter cannot write, erase
136 88 2 counter AI1 uint32 Хондан counter cannot write, erase; max frequency 10Hz
138 8A 2 counter AI2 uint32 Хондан counter cannot write, erase; max frequency 10Hz
140 8C 2 counter AI3 uint32 Хондан counter cannot write, erase; max frequency 10Hz
142 8E 2 counter AI4 uint32 Хондан counter cannot write, erase; max frequency 10Hz
256 100 1 modbus address slave 1-247 1 uint16 Хондан/навиштанdaviteq LFC128 2 Advanced Level Display Controller  - Icon
257 101 1 modbus baudrate slave 1 0-1 0 uint16 Хондан/навиштанdaviteq LFC128 2 Advanced Level Display Controller  - Icon 0: 9600, 1: 19200
258 102 1 modbus parity slave 1 0-2 0 uint16 Хондан/навиштанdaviteq LFC128 2 Advanced Level Display Controller  - Icon 0: ҳеҷ, 1: тоқ, 2: ҷуфт

5.2 Тугмаи Reset
When holding the reset button for 4 seconds, LFC 128-2 will reset the default configuration to 02 x RS485 / Modbus
RTU-Slave.
Default Modbus RTU Configuration:

  • Адрес: 1
  • Меъёри интиқол: 9600
  • Паритет: нест

5.3 Вуруди рақамӣ

daviteq LFC128 2 Advanced Level Display Controller  - Digital Input

Мушаххасот:

  • 04 channels DI, isolated
  • Input Resistance: 4.7 kΏ
  • Изолятсия ҷилдиtagд: 5000Vrms
  • Logic level 0: 0-1V
  • Logic level 1: 5-24V
  • Функсия:
  • Read logic 0/1
  • Ҳисобкунаки набз

5.3.1 Read the logical state 0/1
Logic value in Modbus Memory Map: 0-1
Registers to store logic values in the Modbus Memory Map:

  • DI1__DI2: digital status: stores the logical state of channel 1 and channel 2.
    H_byte: DI1
    L_byte: DI2
  • DI3__DI4: digital status: store the logical state of channel 3 and channel 4.
    H_byte: DI3
    L_byte: DI4

5.3.2 Pulse Counter
Counter value in Modbus Memory Map, when adding the number exceeds the threshold, it will automatically return: 0 4294967295 (32bits)
The register that stores Counter value in the Modbus Memory Map cannot be erased:

  • Counter DI1: stores the logic state of channel 1
  • Counter DI2: stores the logic state of channel 2
  • Counter DI3: store the logic state of channel 3
  • Counter DI4: stores the logic state of channel 4
    The register that stores Counter value in the Modbus Memory Map cannot be erased:
  • None reset counter DI1: stores the logic state of channel 1
  • None reset counter DI2: stores the logic state of channel 2
  • None reset counter DI3: stores the logic state of channel 3
  • None reset counter DI4: stores the logic state of channel 4

Pulse Counter Mode:
Low-speed pulse count less than 10Hz with filter, anti-jamming:

  • Set register “counter DI1: filter time” = 500-2000: Channel 1 counts pulses less than 10Hz
  • Set register “counter DI2: filter time” = 500-2000: Channel 2 counts pulses less than 10Hz
  • Set register “counter DI3: filter time” = 500-2000: Channel 3 counts pulses less than 10Hz
  • Set register “counter DI4: filter time” = 500-2000: Channel 4 counts pulses less than 10Hz
  • High-speed pulse count with max 2KHz frequency without filter:
  • Set register “counter DI1: filter time” = 1: channel 1 counts pulses with Fmax = 2kHz
  • Set register “counter DI2: filter time” = 1: channel 2 counts pulses with Fmax = 2kHz
  • Set register “counter DI3: filter time” = 1: channel 3 counts pulses with Fmax = 2kHz
  • Set register “counter DI4: filter time” = 1: channel 4 counts pulses with Fmax = 2kHz

5.4 Вуруди аналогӣ

daviteq LFC128 2 Advanced Level Display Controller  - Analog Input

04 AI channels, no isolation (AI1 is a 4-20mA / 0-5 VDC / 0-10 VDC level sensor input )

daviteq LFC128 2 Advanced Level Display Controller  - Analog Input 1

Use DIP SW to configure Analog input: 0-10V, 0-20mA

daviteq LFC128 2 Advanced Level Display Controller  - Analog Input 2

Арзиш Type of AI
0 0-10 В
1 0-20 мА

Навъи вуруд:

  • Андоза ҷtage: 0-10В
  • Measure current: 0-20mA
  • The configuration for AI reads the same logical state as DI, but it is not isolated with a pulse range of 0-24V

Импеданси вуруд:

  • Андоза ҷtage: 320 kΏ
  • Measure the current: 499 Ώ

5.4.1 Read the Analog value
Ҳалли 12 бит
Non-Linearity: 0.1%
Analog value in Modbus Memory Map: 0-3900
Analog value register in the Modbus Memory Map:

  • AI1 analog value: store the Analog value of channel 1
  • AI2 analog value: stores the Analog value of channel 2
  • AI3 analog value: store the Analog value of channel 3
  • AI4 analog value: store the Analog value of channel 4

5.4.2 AI configuration works as DI
Изолятсия нест
AI Configure AI to read the same logic state as DI with pulse amplitude from 0-24V
There are 2 counter threshold AIx: logic threshold 0 and counter AIx: threshold logic 1 in the modbus table: 0-4095

  • Analog Analog value of AI <counter AIx: threshold logic 0: is considered Logic 0 status of AI
  • Analog Analog value of AI> counter AIx: threshold logic 1: is considered to be Logic 1 state of AI
  • Counter AIx: threshold logic 0 = <Analog value of AI <= counter AIx: threshold logic 1: is considered to be the constant logic state

Logic Logical status value of AI in Modbus Memory Map table: 0-1
The register stores logical values in Modbus Memory Map:

  • AI1___AI2: digital status: stores the logical state of channel 1 and channel 2.
    H_byte: AI1
    L_byte: AI2
  • AI3___AI4: digital status: stores the logical state of channel 1 and channel 2.
    H_byte: AI3
    L_byte: AI4

5.4.3 Pulse Counter AI max 10Hz
Counter value in Modbus Memory Map, when adding the number beyond the threshold, it will automatically return: 0 4294967295 (32bits)
The register that stores Counter value in the Modbus Memory Map cannot be erased:

  • Counter AI1: stores the logic state of channel 1
  • Counter AI2: save logic state of channel 2
  • Counter AI3: save logic state of channel 3
  • Counter AI4: save logic state of channel 4
    The register that stores Counter value in the Modbus Memory Map cannot be erased:
  • None reset counter AI1: stores the logic state of channel 1
  • None reset counter AI2: stores the logic state of channel 2
  • None reset counter AI3: stores the logic state of channel 3
  • None reset counter AI4: save logic state of channel 4

5.5 Эстафета

daviteq LFC128 2 Advanced Level Display Controller  - Relay

04 channel Relay SPDT NO / NC
Contact rating: 2A / 24VDC, 0.5A / 220VAC
There are status LEDs:

  • Led on: Close Contact
  • Led off: Open Contact
Default Relay Register Status of relays when resetting power supplies
3 Operate according to the Alarm configuration

Танзимоти ҳушдор:

  • HIHI : Relay 4 On
  • HI : Relay 3 On
  • LO : Relay 2 On
  • LOLO: Relay 1 On

5.6 Натиҷаи пулс

daviteq LFC128 2 Advanced Level Display Controller  - Output

01 isolated open-collector channel
Opto-coupler: Source current Imax = 10mA, Vceo = 80V
Функсияҳо: On / Off, pulse generator, PWM
5.6.1 On/Off Function
Set the Open-collector register in the Modbus Memory Map table:

  • Set Open-collector register: 1 => Pulse Output ON
  • Set Open-collector register: 0 => Pulse Output OFF

5.6.2 Pulse generator
Pulse output transmits a maximum of 65535 pulses, with Fmax 2.5kHz
Configure the following registers in the Modbus Memory Map table:

  • Set register “open collector: pulse number”: 0-65535 => Pulse Number = 65535: broadcast 65535 pulses
  • Set register “open collector: time cycle”: (0-65535) x0.1ms => Time Cycle = 4: Fmax 2.5kHz
  • Set register “open collector: time on”: (0-65535) x0.1ms => Time On: is the logic time 1 of the pulse
  • Set the register “open collector ctrl” = 3 => configure the Pulse Output to generate a pulse and start to pulse, generate a sufficient number of pulses in the “open collector: pulse number” register => stop pulse generator and register ” open collector ctrl ”= 0

5.6.3 PWM
Max frequency 2.5kHz
Configure the following registers in the Modbus Memory Map table:

  • Set the register “open collector ctrl” = 2 => configure Pulse Output PWM function
  • Set register “open collector: time cycle”: (0-65535) x0.1ms => Time Cycle = 4: Fmax 2.5kHz
  • Set register “open collector: time on”: (0-65535) x0.1ms => Time On: is the logic time 1 of the pulse

Насбкунӣ

6.1 Усули насб

daviteq LFC128 2 Advanced Level Display Controller  - method6.2 Wiring with Level Sensor

daviteq LFC128 2 Advanced Level Display Controller  - method 1

Конфигуратсия

7.1 Экрани асосӣ

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen

ЭКРАН: Switch to 2nd screen with more detailed information
Ҳушдор: Show Level Alert
ХОНА: Бозгашт ба экрани асосӣ
ТОНФИГ. (Default Password: a): Go to Setting Screen
7.2 Setting screen (Default Password: a)
7.2.1 Экрани 1

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen 1] '

ADC: Raw signal value of channel AI1
Level (Unit): The level corresponds to the ADC signal after configuration
Decimal Places Level:Decimal number of digits after the dot of Level 0-3 (00000, 1111.1, 222.22, 33.333)
Unit level: level units, 0-3 (0: mm, 1: cm, 2: m, 3: inch)
Дар 1: Enter the ADC value after putting 4 mA / 0 VDC into AI1 for calibration at 0 level
Миқёси 1: The level value displayed corresponds to the value entered in In 1 (usually 0)
Дар 2: Enter the ADC value after putting 20 mA / 10 VDC into AI1 for calibration at Full level
Миқёси 2: The level value displayed corresponds to the value entered in In 2
Span Level: Maximum value of Level (Span Level ≥ Scale 2)
Decimal Places Volume: Decimal number of digits after the dot of Volume 0-3 (00000, 1111.1, 222.22, 33.333)
Unit Volume: units of volume 0-3 (0: lit, 1: cm, 2: m3, 3:%)
7.2.2 Экрани 2

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen 2

Level Hi Hi Set point (Unit): High High level of Alarm Level
Level Hi Hi Hys (Unit): High High level hysteresis of Alarm Level
Level Hi Set point (Unit): High level of Alarm Level
Level Hi Hys (Unit): High level hysteresis of Alarm Level
Level Lo Set point (Unit): Low level of Alarm Level
Level Lo Hys (Unit): Low level hysteresis of Alarm Level
Level Lo Lo Set point (Unit): Low Low level of Alarm Level
Level Lo Lo Hys (Unit): Low Low level hysteresis of Alarm Level
Ҳолати зангдор: 0: Level, 1: Volume
Span Volume(Unit): Maximum value of the volume
7.2.3 Экрани 3

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen 3

Volume Hi Hi Set point (Unit): High High volume of Alarm Volume
Volume Hi Hi Hys (Unit): High High volume hysteresis of Alarm Volume
Volume Hi Set point (Unit): High volume of Alarm Volume
Volume Hi Hys (Unit): High volume hysteresis of Alarm Volume
Volume Lo Set point (Unit): Low volume of Alarm Volume
Volume Lo Hys (Unit): Low volume hysteresis of Alarm Volume
Volume Lo Lo Set point (Unit): Low Low volume of Alarm Volume
Volume Lo Lo Hys (Unit): Low Low volume hysteresis of Alarm Volume
Run Total: Run the total function. 0-1 (0: No 1: Yes)
7.2.4 Экрани 4

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen 4

Filling (Unit): Total function: total put into tank
Consumption (Unit): Total function: total consumption of the tank
Decimal Places Total: Decimal number of parameters Filling, Consumption, NRT Filling, NRT Consumption on display page (not the setting page)
Delta Total (Unit): Hysteresis level of the total function
Суроғаи Modbus: Modbus address of LFC128-2, 1-247
Modbus Baurate S1: 0-1 (0 : 9600 , 1 : 19200)
Modbus Parity S1: 0-2 (0: none, 1: odd, 2: even)
Modbus Baurate S2: 0-1 (0 : 9600 , 1 : 19200)
Modbus Parity S2: 0-2 (0: none, 1: odd, 2: even)
Num of Points: Number of points in the table to convert from level to volume, 1-166
7.2.5 Экрани 5

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen 5

Point 1 Level (Level Unit): Level at Point 1
Point 1 Volume (Volume Unit): The corresponding volume at Point 1
Point 166 Level (Level Unit): Fuel level at Point 166
Point 166 Volume (Volume Unit): The corresponding volume at Point 166
7.2.6 Экрани 6

daviteq LFC128 2 Advanced Level Display Controller  - Home Screen 6

Рамз: Password to enter the Setting page, 8 ASCII characters
Tank Name: Tank name displayed on the main screen

Мушкилкушо

Не. Падидаҳо Сабаб Ҳалли
1 Modbus failed to communicate Modbus LED Status: LED is off: received no data LED is blinking: the Modbus configuration is not the correct Check the connection Check the Modbus configuration: Address, Baud Rate, Parity
2 Timeout Modbus Noise appears on the line Configure Baudrate 9600 and use a twisted pair cable with anti-jamming protection
3 Сенсор ҷудо карда шудааст Sensor and LFC128 lost connection Checking connection Check sensor type (LFC128-2 only connects to 0-10VDC / 4- 20mA analog sensor type) Check the switch to see if it is turned on correctly Check that the sensor connector is correct AI1
4 Linearization table error Error of conversion table from level to volume Check the configuration of the conversion table from level to volume

Дастгирии тамосҳо

Истеҳсолкунанда
Ширкати Daviteq Technologies Inc
№11 Street 2G, Nam Hung Vuong Res., An Lac Ward, Binh Tan Dist., Хошимин, Ветнам.
Tel: +84-28-6268.2523/4 (ext.122)
Почтаи электронӣ: info@daviteq.com
www.daviteq.com

Ҳуҷҷатҳо / Сарчашмаҳо

daviteq LFC128-2 Advanced Level Display Controller [pdf] Дастури дастур
LFC128-2, LFC128-2 Advanced Level Display Controller, Advanced Level Display Controller, Level Display Controller, Display Controller