Level Indicating
Controller LFC128-2
USER GUIDE FOR LEVEL INDICATING CONTROLLER LFC128-2
LFC128-2-MN-EN-01 JUN-2020
LFC128-2 Advanced Level Display Controller
ເອກະສານນີ້ຖືກນຳໃຊ້ສຳລັບຜະລິດຕະພັນຕໍ່ໄປນີ້
SKU | LFC128-2 | HW Ver. | 1.0 | FW Ver. | 1.1 |
ລະຫັດລາຍການ | LFC128-2 | Level Indicating Controller, 4AI/DI, 4DI, 4xRelay, 1xPulse Output, 2 x RS485/ModbusRTU-Slave Communication | |||
ບັນທຶກການປ່ຽນແປງຫນ້າທີ່
HW Ver. | FW Ver. | ວັນທີປ່ອຍ | ຟັງຊັນ ປ່ຽນແປງ |
1.0 | 1.1 | JUN-2020 | |
ແນະນຳ
LFC128-2 is an advanced level display controller. The product integrates Modbus RTU interface to help PLC / SCADA / BMS and any IoT port can connect to monitor. LFC128-2 has a simple yet powerful design with 4 AI / DI, 4 DI, 4 Relays, 1 Pulse pulse output, 2 RS485 Slave ModbusRTU allowing them to connect with multiple devices easily. With advanced technology that provides high stability and reliability, many functions, easy installation with touch screen and friendly interface helps visually monitor level.
ຂໍ້ມູນຈໍາເພາະ
ການປ້ອນຂໍ້ມູນດິຈິຕອນ | 04 x Ports, opto-coupler, 4.7 kohms input resisrtance, 5000V rms isolation, Logic 0 (0-1VDC), Logic 1 (5-24VDC), Functions: logic status 0/1 or Pulse counting (32 bit counter with max 4kHz pulse) |
ຂໍ້ມູນຂາເຂົ້າ | 04 x Ports, select between 0-10VDC input or 0-20mA input, 12 bit Resolution, can be configured as Digital input by DIP switch (max 10VDC input) The AI1 port is a 0-10 VDC / 4-20 mA level sensor connection port |
Relay Output | 04 x Ports, electro-mechanical Relays, SPDT, contact rating 24VDC/2A or 250VAC/5A, LED indicators |
ກໍາມະຈອນຜົນຜະລິດ | 01 x Ports, open-collector, opto-isolation, max 10mA and 80VDC, On/off control, Pulser (max 2.5Khz, max 65535 Pulses) or PWM (max 2.5Khz) |
ການສື່ສານ | 02 x ModbusRTU-Slave, RS485, speed 9600 or 19200, LED indicator |
ປຸ່ມຣີເຊັດ | For resetting 02 x RS485 Slave port to default setting (9600, None parity, 8 bit) |
ປະເພດຫນ້າຈໍ | ຫນ້າຈໍສໍາຜັດ |
ການສະຫນອງພະລັງງານ | 9..36VDC |
ການບໍລິໂພກ | 200mA @ 24VDC supply |
ປະເພດການຕິດຕັ້ງ | ການຕິດຕັ້ງແຜງ |
ຕັນຢູ່ປາຍຍອດ | pitch 5.0mm, rating 300VAC, wire size 12-24AWG |
ອຸນຫະພູມເຮັດວຽກ / ຄວາມຊຸ່ມຊື່ນ | 0..60 degC / 95%RH non-condensing |
ຂະໜາດ | H93xW138xD45 |
ນ້ຳໜັກສຸດທິ | 390 ກຣາມ |
ຮູບພາບຜະລິດຕະພັນ
ຫຼັກການປະຕິບັດງານ
5.1 ການສື່ສານ Modbus
02 x RS485/ModbusRTU-Slave
ອະນຸສັນຍາ: Modbus RTU
ທີ່ຢູ່: 1 – 247, 0 is the Broadcast address
ອັດຕາ Baud: ໑໕ , ໒໑
ຄວາມສະເີພາບ: ບໍ່ມີ, ຄີກ, ເຖິງແມ່ນວ່າ
- Status indicator LED:
- Led on: modbus communication OK
- Led blinking: received data but modbus communication incorrect, due to wrong Modbus configuration: address, baudrate
- Led off: LFC128-2 received no data, check the connection
ລົງທະບຽນ Memmap
READ uses command 03, WRITE uses command 16
ການຕັ້ງຄ່າເລີ່ມຕົ້ນ:
- ທີ່ຢູ່: 1
- Baudrate slave 1: 9600
- Parity slave 1: none
- Baudrate slave 2: 9600
- Parity slave 2: none
ລົງທະບຽນ Modbus | Hex adr | # of registers![]() |
ລາຍລະອຽດ | ຊ່ວງ | ຄ່າເລີ່ມຕົ້ນ | ຮູບແບບ | ຊັບສິນ | ຄໍາເຫັນ |
0 | 0 | 2 | ຂໍ້ມູນອຸປະກອນ | LFC1 | ສາຍ | ອ່ານ | ||
8 | 8 | 1 | DI1 DI2: digital status | 0-1 | uint8 | ອ່ານ | H_byte: DI1 L_byte: DI2 | |
9 | 9 | 1 | DI3 DI4: digital status | 0-1 | uint8 | ອ່ານ | H_byte: DI3 L_byte: DI4 | |
10 | A | 1 | AI1 AI2: digital status | 0-1 | uint8 | ອ່ານ | H_byte: AI1 L_byte: AI2 | |
11 | B | 1 | AI3 AI4: digital status | 0-1 | uint8 | ອ່ານ | H_byte: AI3 L_byte: AI4 | |
12 | C | 1 | AI1: analog value | uint16 | ອ່ານ | |||
13 | D | 1 | AI2: analog value | uint16 | ອ່ານ | |||
14 | E | 1 | AI3: analog value | uint16 | ອ່ານ | |||
15 | F | 1 | AI4: analog value | uint16 | ອ່ານ | |||
16 | 10 | 2 | AI1: scaled value | ລອຍ | ອ່ານ | |||
18 | 12 | 2 | AI2: scaled value | ລອຍ | ອ່ານ | |||
20 | 14 | 2 | AI3: scaled value | ລອຍ | ອ່ານ | |||
22 | 16 | 2 | AI4: scaled value | ລອຍ | ອ່ານ | |||
24 | 18 | 1 | Relay 1 | 0-1 | uint16 | ອ່ານ | ||
25 | 19 | 1 | Relay 2 | 0-1 | uint16 | ອ່ານ | ||
26 | 1A | 1 | Relay 3 | 0-1 | uint16 | ອ່ານ | ||
27 | 1B | 1 | Relay 4 | 0-1 | uint16 | ອ່ານ | ||
28 | 1C | 1 | open collector ctrl | 0-3 | uint16 | ອ່ານ/ຂຽນ | 0: off 1: on 2: pwm, pulse continuously 3: pulse, when enough pulse number, ctrl = 0 | |
30 | 1E | 2 | counter DI1 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable | ||
32 | 20 | 2 | counter DI2 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable | ||
34 | 22 | 2 | counter DI3 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable | ||
36 | 24 | 2 | counter DI4 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable | ||
38 | 26 | 2 | counter AI1 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable, max frequency 10Hz | ||
40 | 28 | 2 | counter AI2 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable, max frequency 10Hz | ||
42 | 2A | 2 | counter AI3 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable, max frequency 10Hz | ||
44 | 2C | 2 | counter AI4 | uint32 | ອ່ານ/ຂຽນ | counter writable, erasable, max frequency 10Hz | ||
46 | 2E | 2 | DI1: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
48 | 30 | 2 | DI2: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
50 | 32 | 2 | DI3: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
52 | 34 | 2 | DI4: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
54 | 36 | 2 | AI1: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
56 | 38 | 2 | AI2: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
58 | 3A | 2 | AI3: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
60 | 3C | 2 | AI4: time on | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
62 | 3E | 2 | DI1: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
64 | 40 | 2 | DI2: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
66 | 42 | 2 | DI3: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
68 | 44 | 2 | DI4: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
70 | 46 | 2 | AI1: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
72 | 48 | 2 | AI2: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
74 | 4A | 2 | AI3: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
76 | 4C | 2 | AI4: time off | uint32 | ອ່ານ/ຂຽນ | ວິ | ||
128 | 80 | 2 | counter DI1 | uint32 | ອ່ານ | counter cannot write, erase | ||
130 | 82 | 2 | counter DI2 | uint32 | ອ່ານ | counter cannot write, erase | ||
132 | 84 | 2 | counter DI3 | uint32 | ອ່ານ | counter cannot write, erase | ||
134 | 86 | 2 | counter DI4 | uint32 | ອ່ານ | counter cannot write, erase | ||
136 | 88 | 2 | counter AI1 | uint32 | ອ່ານ | counter cannot write, erase; max frequency 10Hz | ||
138 | 8A | 2 | counter AI2 | uint32 | ອ່ານ | counter cannot write, erase; max frequency 10Hz | ||
140 | 8C | 2 | counter AI3 | uint32 | ອ່ານ | counter cannot write, erase; max frequency 10Hz | ||
142 | 8E | 2 | counter AI4 | uint32 | ອ່ານ | counter cannot write, erase; max frequency 10Hz | ||
256 | 100 | 1 | modbus address slave | 1-247 | 1 | uint16 | ອ່ານ/ຂຽນ![]() |
|
257 | 101 | 1 | modbus baudrate slave 1 | 0-1 | 0 | uint16 | ອ່ານ/ຂຽນ![]() |
0:9600, 1:19200 |
258 | 102 | 1 | modbus parity slave 1 | 0-2 | 0 | uint16 | ອ່ານ/ຂຽນ![]() |
0: none, 1: odd, 2: even |
5.2 ປຸ່ມຣີເຊັດ
When holding the reset button for 4 seconds, LFC 128-2 will reset the default configuration to 02 x RS485 / Modbus
RTU-Slave.
Default Modbus RTU Configuration:
- ທີ່ຢູ່: 1
- ອັດຕາ Baud: 9600
- Parity: ບໍ່ມີ
5.3 ການປ້ອນຂໍ້ມູນແບບດິຈິຕອລ
ຂໍ້ມູນຈໍາເພາະ:
- 04 channels DI, isolated
- Input Resistance: 4.7 kΏ
- ສະບັບແຍກtage: 5000Vrms
- Logic level 0: 0-1V
- Logic level 1: 5-24V
- ຟັງຊັນ:
- Read logic 0/1
- Pulse Counter
5.3.1 Read the logical state 0/1
Logic value in Modbus Memory Map: 0-1
Registers to store logic values in the Modbus Memory Map:
- DI1__DI2: digital status: stores the logical state of channel 1 and channel 2.
H_byte: DI1
L_byte: DI2 - DI3__DI4: digital status: store the logical state of channel 3 and channel 4.
H_byte: DI3
L_byte: DI4
5.3.2 Pulse Counter
Counter value in Modbus Memory Map, when adding the number exceeds the threshold, it will automatically return: 0 4294967295 (32bits)
The register that stores Counter value in the Modbus Memory Map cannot be erased:
- Counter DI1: stores the logic state of channel 1
- Counter DI2: stores the logic state of channel 2
- Counter DI3: store the logic state of channel 3
- Counter DI4: stores the logic state of channel 4
The register that stores Counter value in the Modbus Memory Map cannot be erased: - None reset counter DI1: stores the logic state of channel 1
- None reset counter DI2: stores the logic state of channel 2
- None reset counter DI3: stores the logic state of channel 3
- None reset counter DI4: stores the logic state of channel 4
Pulse Counter Mode:
Low-speed pulse count less than 10Hz with filter, anti-jamming:
- Set register “counter DI1: filter time” = 500-2000: Channel 1 counts pulses less than 10Hz
- Set register “counter DI2: filter time” = 500-2000: Channel 2 counts pulses less than 10Hz
- Set register “counter DI3: filter time” = 500-2000: Channel 3 counts pulses less than 10Hz
- Set register “counter DI4: filter time” = 500-2000: Channel 4 counts pulses less than 10Hz
- High-speed pulse count with max 2KHz frequency without filter:
- Set register “counter DI1: filter time” = 1: channel 1 counts pulses with Fmax = 2kHz
- Set register “counter DI2: filter time” = 1: channel 2 counts pulses with Fmax = 2kHz
- Set register “counter DI3: filter time” = 1: channel 3 counts pulses with Fmax = 2kHz
- Set register “counter DI4: filter time” = 1: channel 4 counts pulses with Fmax = 2kHz
5.4 ການປ້ອນຂໍ້ມູນແບບອະນາລັອກ
04 AI channels, no isolation (AI1 is a 4-20mA / 0-5 VDC / 0-10 VDC level sensor input )
Use DIP SW to configure Analog input: 0-10V, 0-20mA
ມູນຄ່າ | Type of AI |
0 | 0-10 V |
1 | 0-20 mA |
ປະເພດການປ້ອນຂໍ້ມູນ:
- ວັດແທກລະດັບtage: 0-10V
- Measure current: 0-20mA
- The configuration for AI reads the same logical state as DI, but it is not isolated with a pulse range of 0-24V
Input impedance:
- ວັດແທກລະດັບtage: 320 kΏ
- Measure the current: 499 Ώ
5.4.1 Read the Analog value
ຄວາມລະອຽດ 12 ບິດ
Non-Linearity: 0.1%
Analog value in Modbus Memory Map: 0-3900
Analog value register in the Modbus Memory Map:
- AI1 analog value: store the Analog value of channel 1
- AI2 analog value: stores the Analog value of channel 2
- AI3 analog value: store the Analog value of channel 3
- AI4 analog value: store the Analog value of channel 4
5.4.2 AI configuration works as DI
ບໍ່ມີການໂດດດ່ຽວ
AI Configure AI to read the same logic state as DI with pulse amplitude from 0-24V
There are 2 counter threshold AIx: logic threshold 0 and counter AIx: threshold logic 1 in the modbus table: 0-4095
- Analog Analog value of AI <counter AIx: threshold logic 0: is considered Logic 0 status of AI
- Analog Analog value of AI> counter AIx: threshold logic 1: is considered to be Logic 1 state of AI
- Counter AIx: threshold logic 0 = <Analog value of AI <= counter AIx: threshold logic 1: is considered to be the constant logic state
Logic Logical status value of AI in Modbus Memory Map table: 0-1
The register stores logical values in Modbus Memory Map:
- AI1___AI2: digital status: stores the logical state of channel 1 and channel 2.
H_byte: AI1
L_byte: AI2 - AI3___AI4: digital status: stores the logical state of channel 1 and channel 2.
H_byte: AI3
L_byte: AI4
5.4.3 Pulse Counter AI max 10Hz
Counter value in Modbus Memory Map, when adding the number beyond the threshold, it will automatically return: 0 4294967295 (32bits)
The register that stores Counter value in the Modbus Memory Map cannot be erased:
- Counter AI1: stores the logic state of channel 1
- Counter AI2: save logic state of channel 2
- Counter AI3: save logic state of channel 3
- Counter AI4: save logic state of channel 4
The register that stores Counter value in the Modbus Memory Map cannot be erased: - None reset counter AI1: stores the logic state of channel 1
- None reset counter AI2: stores the logic state of channel 2
- None reset counter AI3: stores the logic state of channel 3
- None reset counter AI4: save logic state of channel 4
5.5 Relay
04 channel Relay SPDT NO / NC
Contact rating: 2A / 24VDC, 0.5A / 220VAC
There are status LEDs:
- Led on: Close Contact
- Led off: Open Contact
Default Relay Register | Status of relays when resetting power supplies |
3 | Operate according to the Alarm configuration |
ການຕັ້ງຄ່າປຸກ:
- HIHI : Relay 4 On
- HI : Relay 3 On
- LO : Relay 2 On
- LOLO: Relay 1 On
5.6 Pulse Output
01 isolated open-collector channel
Opto-coupler: Source current Imax = 10mA, Vceo = 80V
ຟັງຊັນ: On / Off, pulse generator, PWM
5.6.1 On/Off Function
Set the Open-collector register in the Modbus Memory Map table:
- Set Open-collector register: 1 => Pulse Output ON
- Set Open-collector register: 0 => Pulse Output OFF
5.6.2 Pulse generator
Pulse output transmits a maximum of 65535 pulses, with Fmax 2.5kHz
Configure the following registers in the Modbus Memory Map table:
- Set register “open collector: pulse number”: 0-65535 => Pulse Number = 65535: broadcast 65535 pulses
- Set register “open collector: time cycle”: (0-65535) x0.1ms => Time Cycle = 4: Fmax 2.5kHz
- Set register “open collector: time on”: (0-65535) x0.1ms => Time On: is the logic time 1 of the pulse
- Set the register “open collector ctrl” = 3 => configure the Pulse Output to generate a pulse and start to pulse, generate a sufficient number of pulses in the “open collector: pulse number” register => stop pulse generator and register ” open collector ctrl ”= 0
5.6.3 PWM
Max frequency 2.5kHz
Configure the following registers in the Modbus Memory Map table:
- Set the register “open collector ctrl” = 2 => configure Pulse Output PWM function
- Set register “open collector: time cycle”: (0-65535) x0.1ms => Time Cycle = 4: Fmax 2.5kHz
- Set register “open collector: time on”: (0-65535) x0.1ms => Time On: is the logic time 1 of the pulse
ການຕິດຕັ້ງ
6.1 ວິທີການຕິດຕັ້ງ
6.2 Wiring with Level Sensor
ການຕັ້ງຄ່າ
7.1 ໜ້າ ຈໍເຮືອນ
ໜ້າ ຈໍ: Switch to 2nd screen with more detailed information
ຕາຕະລາງ: Show Level Alert
ບ້ານ: ກັບໄປທີ່ໜ້າຈໍຫຼັກ
ຕັ້ງຄ່າ. (Default Password: a): Go to Setting Screen
7.2 Setting screen (Default Password: a)
7.2.1 ໜ້າຈໍ 1
ADCs: Raw signal value of channel AI1
Level (Unit): The level corresponds to the ADC signal after configuration
Decimal Places Level:Decimal number of digits after the dot of Level 0-3 (00000, 1111.1, 222.22, 33.333)
Unit level: level units, 0-3 (0: mm, 1: cm, 2: m, 3: inch)
ໃນ 1: Enter the ADC value after putting 4 mA / 0 VDC into AI1 for calibration at 0 level
ຂະໜາດ 1: The level value displayed corresponds to the value entered in In 1 (usually 0)
ໃນ 2: Enter the ADC value after putting 20 mA / 10 VDC into AI1 for calibration at Full level
ຂະໜາດ 2: The level value displayed corresponds to the value entered in In 2
Span Level: Maximum value of Level (Span Level ≥ Scale 2)
Decimal Places Volume: Decimal number of digits after the dot of Volume 0-3 (00000, 1111.1, 222.22, 33.333)
Unit Volume: units of volume 0-3 (0: lit, 1: cm, 2: m3, 3:%)
7.2.2 ໜ້າຈໍ 2
Level Hi Hi Set point (Unit): High High level of Alarm Level
Level Hi Hi Hys (Unit): High High level hysteresis of Alarm Level
Level Hi Set point (Unit): High level of Alarm Level
Level Hi Hys (Unit): High level hysteresis of Alarm Level
Level Lo Set point (Unit): Low level of Alarm Level
Level Lo Hys (Unit): Low level hysteresis of Alarm Level
Level Lo Lo Set point (Unit): Low Low level of Alarm Level
Level Lo Lo Hys (Unit): Low Low level hysteresis of Alarm Level
ໂມດແຈ້ງເຕືອນ: 0: Level, 1: Volume
Span Volume(Unit): Maximum value of the volume
7.2.3 ໜ້າຈໍ 3
Volume Hi Hi Set point (Unit): High High volume of Alarm Volume
Volume Hi Hi Hys (Unit): High High volume hysteresis of Alarm Volume
Volume Hi Set point (Unit): High volume of Alarm Volume
Volume Hi Hys (Unit): High volume hysteresis of Alarm Volume
Volume Lo Set point (Unit): Low volume of Alarm Volume
Volume Lo Hys (Unit): Low volume hysteresis of Alarm Volume
Volume Lo Lo Set point (Unit): Low Low volume of Alarm Volume
Volume Lo Lo Hys (Unit): Low Low volume hysteresis of Alarm Volume
Run Total: Run the total function. 0-1 (0: No 1: Yes)
7.2.4 ໜ້າຈໍ 4
Filling (Unit): Total function: total put into tank
Consumption (Unit): Total function: total consumption of the tank
Decimal Places Total: Decimal number of parameters Filling, Consumption, NRT Filling, NRT Consumption on display page (not the setting page)
Delta Total (Unit): Hysteresis level of the total function
ທີ່ຢູ່ Modbus: Modbus address of LFC128-2, 1-247
Modbus Baurate S1: 0-1 (0 : 9600 , 1 : 19200)
Modbus Parity S1: 0-2 (0: none, 1: odd, 2: even)
Modbus Baurate S2: 0-1 (0 : 9600 , 1 : 19200)
Modbus Parity S2: 0-2 (0: none, 1: odd, 2: even)
Num of Points: Number of points in the table to convert from level to volume, 1-166
7.2.5 ໜ້າຈໍ 5
Point 1 Level (Level Unit): Level at Point 1
Point 1 Volume (Volume Unit): The corresponding volume at Point 1
Point 166 Level (Level Unit): Fuel level at Point 166
Point 166 Volume (Volume Unit): The corresponding volume at Point 166
7.2.6 ໜ້າຈໍ 6
ລະຫັດຜ່ານ: Password to enter the Setting page, 8 ASCII characters
Tank Name: Tank name displayed on the main screen
ການແກ້ໄຂບັນຫາ
ບໍ່. | ປະກົດການ | ເຫດຜົນ | ວິທີແກ້ໄຂ |
1 | Modbus failed to communicate | Modbus LED Status: LED is off: received no data LED is blinking: the Modbus configuration is not the correct | Check the connection Check the Modbus configuration: Address, Baud Rate, Parity |
2 | Timeout Modbus | Noise appears on the line | Configure Baudrate 9600 and use a twisted pair cable with anti-jamming protection |
3 | ເຊັນເຊີຕັດການເຊື່ອມຕໍ່ | Sensor and LFC128 lost connection | Checking connection Check sensor type (LFC128-2 only connects to 0-10VDC / 4- 20mA analog sensor type) Check the switch to see if it is turned on correctly Check that the sensor connector is correct AI1 |
4 | Linearization table error | Error of conversion table from level to volume | Check the configuration of the conversion table from level to volume |
ຕິດຕໍ່ພົວພັນສະຫນັບສະຫນູນ
ຜູ້ຜະລິດ
Daviteq Technologies Inc
No.11 Street 2G, Nam Hung Vuong Res., An Lac Ward, Binh Tan Dist., Ho Chi Minh, Vietnam.
Tel: +84-28-6268.2523/4 (ext.122)
ອີເມວ: info@daviteq.com
www.daviteq.com
ເອກະສານ / ຊັບພະຍາກອນ
![]() |
daviteq LFC128-2 Advanced Level Display Controller [pdf] ຄູ່ມືການສອນ LFC128-2, LFC128-2 Advanced Level Display Controller, Advanced Level Display Controller, Level Display Controller, Display Controller |