WEINTEK logo

WEINTEK cMT Series

G01/G02

Itọsọna olumulo

WEINTEK cMT-G01 Gateway Mod Bus TCP - 1

Ori 1. Pariview

1.1. Sipesifikesonu

WEINTEK cMT-G01 Gateway Mod Bus TCP - 2      WEINTEK cMT-G01 Gateway Mod Bus TCP - 3

IIoT ẹnu-ọna

Awọn ẹya ara ẹrọ

  • Supports OPC UA
  • Supports MQTT
  • Supports MODBUS TCP/IP Gateway
  • Compact Design and DIN-rail Mountable
  • Fan-less Cooling System
  • Built-in 256 MB Flash Memory
  • Supports MPI 187.5K
  • Built-in Power Isolator
  • cMT-G02 supports WiFi
Awoṣe cMT-G01 cMT-G02
Iranti Filaṣi 256 MB
Àgbo 256 MB
isise 32 bits RISC Cortex-A8 600MHz
Ibudo I/O SD kaadi Iho N/A
USB Gbalejo N/A
Onibara USB  N/A
Àjọlò 10/100/1000 Base-T x 1 WiFi IEEE 802.11 b/g/n
10/100 Ipilẹ-T x 1 10/100 Ipilẹ-T x 1
Isọwọsare ibudo COM1: RS-232 2W, COM2: RS-485 2W/4W, COM3: RS-485 2W
RS-485 Built-in Isolation N/A
CAN akero N/A
HDMI N/A
Ijade ohun N/A
Iṣawọle fidio N/A
RTC Ti a ṣe sinu
Agbara Agbara titẹ sii 24± 20% VDC 10.5 ~ 28VDC
Iyasọtọ agbara Ti a ṣe sinu
Agbara agbara 230mA @ 24VDC 230mA @ 12VDC; 115mA @ 24VDC
Voltage Resistance 500VAC (iṣẹju 1)
Iyapa Resistance Exceed 50M at 500VDC
Ifarada Gbigbọn 10 si 25Hz (X, Y, itọsọna Z 2G iṣẹju 30)
Sipesifikesonu PCB Aso Bẹẹni
Apade Ṣiṣu
Awọn iwọn WxHxD 109 x 81 x 27 mm
Iwọn Isunmọ. 0.14 kg
Oke 35 mm DIN iṣinipopada iṣagbesori
Ayika Eto Idaabobo IP20
Ibi ipamọ otutu -20° ~ 60°C (-4° ~ 140°F)
Awọn iwọn otutu ti nṣiṣẹ 0° ~ 50°C (32° ~ 122°F)
Ọriniinitutu ibatan 10% ~ 90% (ti kii ṣe ifunmọ)
Iwe-ẹri CE CE ti samisi
UL cULus Akojọ Application in progress
Software EasyBuilder Pro V5.06.01 EasyBuilder Pro V6.00.01
1.2. Awọn iwọn

cMT-G01

WEINTEK cMT-G01 Gateway Mod Bus TCP - 4            WEINTEK cMT-G01 Gateway Mod Bus TCP - 5

Iwaju View                         Apa View

WEINTEK cMT-G01 Gateway Mod Bus TCP - 6                            WEINTEK cMT-G01 Gateway Mod Bus TCP - 7

Oke View                        Isalẹ View

a LAN 2 Port (10M/100M)
b LAN 1 Port (10M/100M/1G)
c COM1: RS-232 2W
COM2: RS-485 2W/4W
COM3: RS-485 2W
d Asopọ agbara
e Aiyipada Bọtini

cMT-G02

WEINTEK cMT-G01 Gateway Mod Bus TCP - 8     WEINTEK cMT-G01 Gateway Mod Bus TCP - 9         WEINTEK cMT-G01 Gateway Mod Bus TCP - 10

Iwaju View               Apa View

WEINTEK cMT-G01 Gateway Mod Bus TCP - 11                WEINTEK cMT-G01 Gateway Mod Bus TCP - 12              WEINTEK cMT-G01 Gateway Mod Bus TCP - 13

Oke View        Isalẹ View             Eriali

a WiFi
b LAN 1 Port (10M/100M)
c COM1: RS-232 2W
COM2: RS-485 2W/4W
COM3: RS-485 2W
d Asopọ agbara
e Aiyipada Bọtini
1.3. Connector pin designations

COM1 RS-232, COM2 RS-485 2W/4W, COM3 RS-485 2W 9 Pin, Male, D-sub

PIN# COM1 RS-232 COM2 RS-485 COM3 RS-485 
2W 4W
1 Data +
2 RxD
3 TXD
4 Data-
5 GND
6 Data + RX+
7 Data- RX-
8 TX+
9 TX-
1.4. Restoring factory default

Press and hold on the Default button on the unit for more than 15 seconds to restore factory default.
The IP setting will be restored to default:
cMT-G01:
Ethernet 1: DHCP
Ethernet 2: 192.168.100.1

cMT-G02
WiFi: DHCP
Ethernet: DHCP

Please note that the projects and data stored in the unit are all cleared after pressing the Default button.

1.5. LED Atọka

LED indicators show the status of IIoT Gateway.

cMT-G01

WEINTEK cMT-G01 Gateway Mod Bus TCP - 14

Aami Àwọ̀ Itumo
WEINTEK cMT-G01 Gateway Mod Bus TCP - 15 Buluu LAN 1 Communication Status
WEINTEK cMT-G01 Gateway Mod Bus TCP - 16 Buluu LAN 2 Communication Status
WEINTEK cMT-G01 Gateway Mod Bus TCP - 17 ọsan Ipo agbara
WEINTEK cMT-G01 Gateway Mod Bus TCP - 18 Alawọ ewe Helps the operator to find the cMT-G01. Triggering system register LB-11959 can turn this indicator on/off. Blink LED function in Web/Download interface can also control this indicator.

cMT-G02

WEINTEK cMT-G01 Gateway Mod Bus TCP - 19

Aami Àwọ̀ Itumo
WEINTEK cMT-G01 Gateway Mod Bus TCP - 15 Buluu LAN Communication Status
WEINTEK cMT-G01 Gateway Mod Bus TCP - 17 ọsan Ipo agbara
WEINTEK cMT-G01 Gateway Mod Bus TCP - 18 Alawọ ewe Helps the operator to find the cMT-G02. Triggering system register LB-11959 can turn this indicator on/off. Blink LED function in Web/Download interface can also control this indicator.

Akiyesi: The second LED indicator from the left is reserved.

1.6. Batiri

IIoT Gateway requires a CR1220 lithium battery to keep the RTC running.

1.7. Asopọ agbara

Agbara: The unit can be powered by DC power only, the voltage range is compatible with most controller DC systems. The power conditioning circuitry inside the unit is accomplished by a switching power supply. The peak starting current can be as high as 500mA.

cMT-G01 voltage range: 24±20% VDC
cMT-G02 voltage range: 10.5~28 VDC

WEINTEK cMT-G01 Gateway Mod Bus TCP - 20

Akiyesi: So laini DC rere pọ si ebute '+' ati ilẹ DC si ebute '-'.

Chapter2. cMT-G01/G02 System Setting

Connect cMT-G01/G02 via Ethernet cable, and then configure system settings by using web ni wiwo.

2.1. Wa fun cMT-G01/G02’s IP address

Launch UtilityManagerEX, select a cMT Series model, and then select a function from Reboot, Download, or Upload. The cMT Series HMI model or cMT-G01/G02 can be found in the IP/HMI Name groupbox by using the model’s IP address, even if the PC or laptop is not on the same network. UtilityManagerEX can find and change cMT-G01/G02’s IP address. The following settings can be carried out after obtaining the IP address.

2.2. Set in internet browser

Open internet browser (IE, Chrome, or Firefox), and enter cMT-G01/G02’s IP address (for example: 192.168.100.1) to configure cMT-G01/G02.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 21

The default IP: Ethernet 1: DHCP, Ethernet 2: 192.168.100.1
cMT-G01/G02 system information is shown in the Login page.

Aami Apejuwe 
WEINTEK cMT-G01 Gateway Mod Bus TCP - 22 Displays HMI name.
WEINTEK cMT-G01 Gateway Mod Bus TCP - 23 Displays system date.
WEINTEK cMT-G01 Gateway Mod Bus TCP - 24 Ṣe afihan akoko eto.
2.3. Eto Eto

The following part introduces cMT-G01/G02 system settings.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 25

Three levels of privileges can be found:
[System Setting]: Controls all the settings
[Update]: Controls limited items.
[History]: Downloads history data (Recipes and Event Logs).

2.3.1. Nẹtiwọọki

Configure Ethernet ports: IP, Mask, Gateway, and DNS.

cMT-G01 has two Ethernet ports. The default IP address of Ethernet 1 is DHCP, and the static IP address of Ethernet 2 is 192.168.100.1.

cMT-G02 has one Ethernet port, and is assigned from DHCP by default.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 26

2.3.2. WiFi (cMT-G02)

Enable/Disable WiFi and related settings: search for AP, configuring IP, Mask, Gateway, and DNS.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 27

2.3.3. Ọjọ / Aago

Set RTC date and time. Select [Sync. with host] and then click [Save] to synchronize cMT-G01/G02 time with the computer time.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 28

2.3.4. HMI Name

Enter a name to identify the unit.
[Identification light]: The green LED indicator WEINTEK cMT-G01 Gateway Mod Bus TCP - 18 of the unit will flash three times when this button is clicked, helping user to find the unit.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 29

2.3.5. Itan

This tab offers settings related to historical data.
[Clear]: Clears history data.
[Backup]: Downloads history data in the unit to this computer.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 30

2.3.6. Imeeli

This tab offers settings related to email.
[SMTP]: Configure email server and relevant settings.
[Contacts]: Set email contacts in this tab.
[Update Email Contacts]: Import the email contacts built using Administrator Tools.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 31

2.3.7. Project Management

This tab offers settings related to project management.
[Restart Project]: Restart cMT-G01/G02 project.
[Update Project]: Upload the project’s *.cxob file to cMT-G01/G02.
[Backup Project]: Backup the project file to this computer.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 32

2.3.8. System Password

Set login password and the password for transferring project file.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 33

2.3.9. Enhanced Security

The account setting in this tab can determine the accounts that can log in OPC UA.
[Accounts]: Add user or change user password and operable classes.
[Import User Account]: Import the user accounts built in Administrator Tools.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 34

2.3.10. EasyAccess 2.0

This tab shows Hardware Key, EasyAccess 2.0 activate status, and proxy settings.
For more information on EasyAccess 2.0, please see EasyAccess 2.0 User Manual.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 35

2.3.11. OPA UA

Configure OPC UA settings. Please see Chapter 6 in this manual for more information.

2.3.12. Ibaraẹnisọrọ

This tab displays the communication parameters of the device connected to cMT-G01/G02. The parameters can be changed.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 36

Parameter list for the device connected via Serial Port.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 37

Parameter list for the device connected via Ethernet Port.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 38

Chapter3. Updating Web Package and OS

cMT-G01/G02 Web Package and OS can be updated through Ethernet. Launch Utility ManagerEX, select [cMT Series] » [Maintenance] » [cMT-G01 OS Upgrade].

WEINTEK cMT-G01 Gateway Mod Bus TCP - 39

3.1 Nmu imudojuiwọn Web Package
  1. Select an HMI to update OS.
  2. Yan [Web package] and browse for the source file.
  3. Click [Update].

WEINTEK cMT-G01 Gateway Mod Bus TCP - 40

3.2 Updating OS

1. Select an HMI to update OS.
2. Select [OS], a Warning message shows, please read this message carefully before you click [OK].

WEINTEK cMT-G01 Gateway Mod Bus TCP - 41

3. If you click [OK], the cMT-G01 OS Update window opens again, browse for the source file, and then click [Update].

WEINTEK cMT-G01 Gateway Mod Bus TCP - 42

4. The message window below opens, please do not turn off the power while upgrading.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 43

5. When finished, cMT-G01 OS Update window shows “finished”.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 44

Chapter4. How to create a cMT-G01/G02 project

This chapter explains how to create a project when cMT-G01/G02 is used as an OPC UA Server, and how to set the addresses used to communicate with OPC UA Clients. The basic steps are:

  1. Add a driver into Device List in EasyBuilder Pro.
  2. Enable OPC UA Server and designate communication address.
  3. Download the project to HMI.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 45

The following explains how to set up OPC UA Server in the project.

4.1. Create a new project

Step 1. Launch EasyBuilder Pro and select a cMT-G01/G02.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 46

Step 2. Add a PLC into the Device List.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 47

Step 3. Click [IIoT] » [OPC UA Server], and select [Enable] check box to enable OPC UA Server.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 48

Step 4. Click [Tags] of the device and then click [New Tag] to add tags monitored using OPC UA.
When finished, click [OK] to leave.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 49

Step 5. Find the created tags in OPC UA Server window. Larger quantity of tags can be exported as csv/excel file and then imported for editing.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 50

4.2. Download project to cMT-G01/G02

The format of the project file run on cMT-G01/G02 is *.cxob. In EasyBuilder Pro, click [Project] » [Compile] to compile the project into *.cxob format. When finish compiling, you can download the project to cMT-G01/G02 by two ways.
Way 1: Download using EasyBuilder Pro. Click [Project] » [Download], and set HMI IP address. The project can be downloaded via Ethernet.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 51

Way 2: Download using website. Open internet browser (IE, Chrome, Firefox), enter cMT-G01/G02 IP address (for example: 192.168.100.1), click System Setting, enter password, and then configure cMT-G01/G02 settings. Go to [Project Management] page and open [Upload Project] tab to download the project file from the computer to cMT-G01/G02.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 52

4.3. Monitoring OPC UA Client

After downloading the project file to HMI, use OPC UA Client software to connect with cMT-G01/G02 to monitor PLC data.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 53

Note: The above is a screenshot of UaExport settings window, for more information on OPC UA Client software settings, please see software’s manual.

4.4. On-line/Off-line Simulation

Running On-line or Off-line simulation in EasyBuilder Pro helps you examine OPC UA Tag settings. In On-line simulation, cMT Diagnoser can read from / write to PLC. Please note that On-line simulation is limited to 10 minutes.
Step 1. In EasyBuilder Pro click [Project] » [On-line Simulation] / [Off-line Simulation] to open cMT Diagnoser window.
Step 2. Add the tags to be previewed into the Monitor list on the right side.
Step 3. In On-line Simulation, data in PLC tags will also change.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 54

Chapter5. Functions supported by cMT-G01/G02

Chapter6. OPC UA Web Atọka Iṣakoso

6.1. Ifihan

cMT-G01/G02 provides a web-based tool for convenient access to OPC UA configurations.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 55

Open cMT-G01/G02’s webpage by entering its IP address into the address bar of a web browser. At the entry page, log in with System setting’s password. Factory default of the password is 111111.
(Suggested resolution: 1024×768 or higher)

WEINTEK cMT-G01 Gateway Mod Bus TCP - 56

Navigate to the OPC UA configuration page from the context menu on the left.
The OPC UA configuration page consists of a Startup/Shutdown control with status bar and tabbed windows including: Server settings, Edit node, Certificates, Discovery, and Advanced.

Usage of each window tab:

Taabu Apejuwe
Eto olupin Configure server settings such as port, name, security, user authentication……etc.
Edit node Ṣakoso awọn tags used by OPC UA server.
Awọn iwe-ẹri Manage certificates used by OPC UA server.
Awari Manage list of discovery server.
To ti ni ilọsiwaju Advanced options and features.
6.2. Startup / Shut Down

WEINTEK cMT-G01 Gateway Mod Bus TCP - 57

WEINTEK cMT-G01 Gateway Mod Bus TCP - 58

Use the toggle button to start up or shut down the OPC UA server. If there is active client connection, when shutting down, the server will wait for a few seconds before closing off completely.

In addition, both the toggle button and a line of text also indicate the status of the server. The status is refreshed approximately every 10 seconds. An icon on the right WEINTEK cMT-G01 Gateway Mod Bus TCP - 59 indicates that the status is being refreshed.

Opin ipari URL is also displayed for user’s reference.

*Whenever a page refresh is desired, use the menu on the left. Avoid using the browser’s refresh button to reload a tab as you may be asked to enter the password to log in again.

6.3. Server Settings

The Server settings page shows general configurations of the OPC UA server.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 60

Gbogboogbo Išẹ
Ibudo Access port of the OPC UA server
Orukọ olupin Server name of the OPC UA server
Eto imulo aabo Supported security policies. At least one must be selected.
Supported Policy: None, Basic128Rsa15, Basic256, Basic256sha256
Mode: Sign, Sign & Encrypt
Aṣayan Automatically Trust all client certificates: by enabling this option, the OPC UA server will trust the certificate from any client connection. 

OPC UA server must be configured with at least one user authentication mode as listed in the following table.

Ijeri Awọn apejuwe
Alailorukọ Allow anonymous client connection. At least one of Browse, Read, or Write modes must be selected.
User name & Password  Allow user authentication with username and password. Each access mode, browse, read, and write can be assigned to a user class. User classes are configured in the Enhanced Security mode on the web interface or in EasyBuilder Pro.
Iwe-ẹri User authentication with X.509 certificate

After completing settings, click the Save button to save the changes. OPC UA server will shut down momentarily and then restart for the changes to take effect.

6.4. Edit Node

WEINTEK cMT-G01 Gateway Mod Bus TCP - 61

In this page, the user can view ati ṣakoso awọn tags currently available in the OPC UA server. New nodes and groups can be added, while existing nodes and groups can be edited or deleted. For ease of navigation, detail information of the currently selected node/group is displayed on the right. After completing settings, it is necessary to click the Save button to save the changes. OPC UA server will shut down momentarily and then restart for the changes to take effect. Changes will be lost if one exits this page without saving.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 62

Note that all modifications can only be made for existing drivers. It is not possible to change or add other drivers that are not already available. It is also not possible to edit the nodes used by tag PLCs*.

*Tag PLCs are characterized by their use of name tags as device memory address as opposed to using device name with indices. Examples ti tag PLCs include: BACnet, Rockwell Free Tag Names , Siemens S7-1200,…etc.

6.5. Awọn iwe-ẹri

In this page, the user can manage certificates and revocation lists of the OPC UA server. Use the dropdown menu to access each page.

If “Allow anonymous client connection” (in the Server settings tab ) option is not active, OPC UA server will reject all client connections and place their certificates in the untrusted list. User may manually “trust” them in this page. Use the reload button WEINTEK cMT-G01 Gateway Mod Bus TCP - 59 to repopulate the list of certificates if necessary.

Similarly, currently trusted certificates can be manually rejected on the same page.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 63

Oju-iwe Apejuwe
Trusted Clients Lists of trusted/rejected client certificates on the server.
Supported operation: Trust/Reject, Remove, Import, Export.
Trusted Users Lists of trusted/rejected user certificates on the server. Supported operation: Trust/Reject, Remove, Import, Export.
Ti ara Server’s own certificate.
Supported operation: Update, Remove.
When updating own certificate, matching certificate and Private Key must be uploaded together; otherwise, update will fail.
A self-signed, 20-year validity certificate will be generated automatically if own certificate is absent when server starts up.
Trusted Client Issuers List of trusted client issuer certificates.
Supported operation: Import, Remove, Export.
Trusted User Issues List of trusted client issuer certificates.
Supported operation: Import, Remove, Export.
Certificate Revocation List Certificate revocation lists for client, user, client issuer, and user issuer.
Supported operation: Import, Remove, Export
6.6. Awari

OPC UA server can register itself with Local Discovery Servers. In this page, the user can maintain the list of discovery servers that OPC UA server will register with during startup. Should the discovery server be unavailable during server shutdown, the shutdown process will be slightly delayed.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 64

After completing settings, click the Save button to save the changes. OPC UA server will shut down momentarily and then restart for the changes to take effect.

6.7. To ti ni ilọsiwaju

Additional settings can be configured in the Advanced tab. The user can set the trace logging level and specific startup behavior of the OPC UA server. Furthermore, the trace log can be downloaded.

WEINTEK cMT-G01 Gateway Mod Bus TCP - 65

After completing settings, click the Save button to save the changes. OPC UA server will shut down momentarily and then restart for the changes to take effect.

UM017003E_20200924