Tipe EKC 223Danfoss EKC 223 Case Controller - barkod 2

Idéntifikasi

Danfoss EKC 224 Case Controller - Idéntifikasi

Aplikasi

Danfoss EKC 224 Case Controller - Aplikasi

Diménsi

Danfoss EKC 224 Case Controller - Dimensi

Pamasangan

Danfoss EKC 224 Case Controller - dipasang

Wiring diagram

Aplikasi  Wiring diagram
1 Danfoss EKC 224 Case Controller - Diagram Wiring 1
2 Danfoss EKC 224 Case Controller - Diagram Wiring 2
3 Danfoss EKC 224 Case Controller - Diagram Wiring 3
4 Danfoss EKC 224 Case Controller - Diagram Wiring 4

Catetan: Panyambungna kakuatan: ukuran kawat = 0.5 – 1.5 mm 2, max. tightening torsi = 0.4 Nm Low voltage panyambungna sinyal: ukuran kawat = 0.15 - 1.5 mm 2, max. tightening torsi = 0.2 Nm 2L na 3L kudu disambungkeun ka fase sarua.

Komunikasi data

Pamasangan Wiring
Danfoss EKC 224 Case Controller - Komunikasi data 1

EKC 22x controller bisa terpadu kana jaringan Modbus via RS-485 adaptor (EKA 206) ngagunakeun kabel panganteur (080N0327). Pikeun detil pamasangan mangga tingal pituduh pamasangan pikeun adaptor EKA 206 – RS485.

Danfoss EKC 224 Case Controller - Komunikasi data 2

data teknis

Fitur Katerangan
Tujuan kontrol Operasi kontrol sensing hawa cocog pikeun incorporation kana AC komérsial sarta aplikasi refrigeration
Pangwangunan kontrol kontrol incorporated
Sasayogian tanaga 084B4055 – 115 V AC / 084B4056 – 230 V AC 50/60 Hz, galvanik terasing vol lowtage suplai kakuatan diatur
kakuatan dipeunteun Kurang ti 0.7 W
Input Input sénsor, Input digital, Tombol Pemrograman Nyambung ka SELV énergi kawates <15 W
Jenis sensor anu diidinan NTC 5000 Ohm dina 25 °C, (Nilai Béta=3980 dina 25/100 °C - EKS 211)
NTC 10000 Ohm dina 25 °C, (Nilai Béta=3435 dina 25/85 °C - EKS 221)
PTC 990 Ohm dina 25 °C, (EKS 111)
Pt1000, (AKS 11, AKS 12, AKS 21)
Akurasi Rentang ukur: -40 – 105 °C (-40 – 221 °F)
akurasi controller:
± 1 K handap -35 °C, ± 0.5 K antara -35 - 25 °C,
± 1 K di luhur 25 °C
Jenis tindakan 1B (relay)
Kaluaran DO1 - Relay 1:
16 A, 16 (16) A, EN 60730-1
10 FLA / 60 LRA di 230 V, UL60730-1
16 FLA / 72 LRA di 115 V, UL60730-1
DO2 - Relay 2:
8 A, 2 FLA / 12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1
DO3 - Relay 3:
3 A, 2 FLA / 12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1
DO4 - Relay 4: 2 A
tampilan Tampilan LED, 3 digit, titik decimal sareng ikon multi-fungsi, skala °C + °F
kaayaan operasi -10 – 55 °C (14 – 131 °F), 90% Rh
Kaayaan neundeun -40 – 70 °C (-40 – +158 °F), 90% Rh
Panyalindungan Hareup: IP65 (Gasket terpadu)
Pungkur: IP00
Lingkungan Polusi gelar II, non-condensing
Overvoltage kategori II - 230 V Vérsi suplai - (ENEC, UL dipikawanoh)
III - 115 V Vérsi suplai - (UL dipikawanoh)
Résistansi kana panas sareng seuneu Kategori D (UL94-V0)
Suhu pikeun pernyataan tés tekanan bola Numutkeun Annex G (EN 60730-1)
kategori EMC Kategori I
Persetujuan Pangenal UL (AS & Kanada) (UL 60730-1)
CE (Diréktif LVD & EMC)
EAC (HANTU)
UKCA
UA
CMIM
ROHS2.0
persetujuan Hazloc pikeun refrigerants kaduruk (R290 / R600a).
R290 / R600a aplikasi tungtung pamakéan employing luyu jeung sarat IEC60079-15.

Operasi tampilan

Tombol di hareup tampilan bisa dioperasikeun ku pondok tur panjang (3s) pencét.

Danfoss EKC 224 Case Controller - Operasi tampilan

A Indikasi status: LEDs hurung dina modeu ECO/Peuting, cooling, defrost jeung kipas ngajalankeun.
B Indikasi alarem: Ikon alarem hurung upami aya alarm.
C Pencét pondok = Napigasi deui
Pencét panjang = Mimitian siklus pulldown. Pintonan bakal ditingalikeun
"Pod" pikeun mastikeun ngamimitian.
D Pencét pondok = Napigasi ka luhur
Pencét lila = Pindah controller ON/OFF (nyetél r12 switch utama dina posisi ON/OFF)
E Pencét pondok = Napigasi ka handap
Pencét lila = Mimitian siklus defrosting. Pintonan bakal nunjukkeun kode "-d-" pikeun mastikeun ngamimitian.
F Pencét pondok = Robah set point
Pencét panjang = Pindah ka ménu parameter

Danfoss EKC 224 Case Controller - Operasi tampilan 2

Ngareset pabrik

Controller tiasa disetél deui ka setélan pabrik nganggo prosedur ieu:

  1. Kakuatan OFF controller
  2. Tetep tombol panah "∧" jeung handap "∨" dipencet bari nyambungkeun deui vol suplaitage
  3. Nalika kode "Raray" dipintonkeun dina tampilan, pilih "enya"

Catetan: Setélan pabrik OEM bakal janten setélan pabrik Danfoss atanapi setélan pabrik anu ditetepkeun ku pangguna upami parantos dilakukeun. Pamaké tiasa nyimpen setelan na salaku setelan pabrik OEM via parameter o67.

Kodeu tampilan

Kode tampilan  Katerangan
-d- Siklus defrost keur lumangsung
Pod A siklus pulldown suhu geus dimimitian
lepat Suhu teu tiasa ditampilkeun kusabab kasalahan sensor
Ditémbongkeun dina luhureun tampilan: Nilai parameter geus ngahontal max. Wates
Ditémbongkeun di handap tampilan: Nilai parameter geus ngahontal mnt. Wates
Konci Kibor tampilan dikonci
Null Kibor tampilan geus teu dikonci
PS Kodeu aksés diperlukeun pikeun ngasupkeun ménu parameter
Kampak/Ext Alarm atawa kasalahan kode kedip-kedip kalawan temp normal. bacakeun sing tarik
Pareum Kontrol dieureunkeun sakumaha r12 switch utama disetel OFF
On Kontrol dimimitian nalika saklar utama r12 disetel ON (kode ditémbongkeun dina 3 detik)
Beungeut Controller direset kana setélan pabrik

Napigasi

Menu parameter diaksés ku mencét tombol "SET" pikeun 3 detik. Upami kode panyalindungan aksés "o05" parantos ditetepkeun, tampilan bakal naroskeun kodeu aksés ku nunjukkeun kodeu "PS". Sakali kodeu aksés geus disadiakeun ku pamaké, daptar parameter bakal diakses.

Danfoss EKC 224 Case Controller - Napigasi

Meunang mimiti alus

Kalayan prosedur ieu anjeun tiasa ngamimitian pangaturan gancang pisan:

  1. Pencét tombol "SET" kanggo 3 detik sareng aksés menu parameter (tampilan bakal nunjukkeun "di")
  2. Pencét tombol handap "∨" pikeun muka menu "tcfg" (tampilan bakal nunjukkeun "tcfg")
  3. Pencét tombol katuhu / ">" pikeun muka ménu konfigurasi (tampilan bakal nunjukkeun r12)
  4. Buka parameter "r12 Main switch" sareng ngeureunkeun kadali ku netepkeun OFF (Pencét SET)
  5. Buka "mode aplikasi o61" sareng pilih mode aplikasi anu diperyogikeun (Pencét SET)
  6. Buka "o06 Sensor type" tur pilih tipe sensor suhu dipaké (n5 = NTC 5 K, n10 = NTC 10 K, Pct. = PTC, Pt1 = Pt1000) - (Pencét "SET").
  7. Buka "O02 DI1 Konfigurasi" tur pilih fungsi pakait jeung input digital 1 (Mangga tingal daptar parameter) - (Pencét "SET").
  8. Buka "O37 DI2 Konfigurasi" tur pilih fungsi pakait jeung input digital 2 (Mangga tingal daptar parameter) - (Pencét "SET").
  9. Buka parameter "o62 Quick setting" sareng pilih prasetél anu cocog sareng aplikasi anu dianggo (punten tingal tabel prasetél di handap) - (Pencét "SET").
  10. Buka "alamat Jaringan o03" sareng setel alamat Modbus upami diperyogikeun.
  11. Arahkeun deui ka parameter "r12 Main switch" tur nyetel eta dina posisi "ON" pikeun ngamimitian kontrol.
  12. Ngaliwat sadaya daptar parameter sareng robih setélan pabrik upami diperyogikeun.

Pamilihan setélan gancang

Setélan gancang 1 2 3 4 5 6 7
Kabinet MT
def alam.
Eureun dina waktuna
Kabinet MT
El. def.
Eureun dina waktuna
Kabinet MT
El. def.
Eureun dina suhu
Kabinet LT
El. def.
Eureun dina suhu
Ruang MT
El. def.
Eureun dina waktuna
Ruang MT
El. def.
Eureun dina suhu
Kamar LT
El. def.
Eureun dina suhu
r00 Cut-kaluar 4 °C 2 °C 2 °C -24 °C 6 °C 3 °C -22 °C
r02 Max Cut-kaluar 6 °C 4 °C 4 °C -22 °C 8 °C 5 °C -20 °C
r03 Min Cut-kaluar 2 °C 0 °C 0 °C -26 °C 4 °C 1 °C -24 °C
A13 Kacida Hawa 10 °C 8 °C 8 °C -15 °C 10 °C 8 °C -15 °C
Al 4 Lowly Hawa -5 °C -5 °C -5 °C -30 °C 0 °C 0 °C -30 °C
d01 Def. Métode Alami Listrik Listrik Listrik Listrik Listrik Listrik
d03 Def.lnterval 6 jam 6 jam 6 jam 12 jam 8 jam 8 jam 12 jam
d10 DefStopSens. Waktos Waktos S5 sénsor 55 sénsor Waktos S5 sénsor S5 sénsor
o02 DI1 Konfigurasi. Panto fct. Panto fct. Panto fct.

konci programming

Programming controller sareng Mass Programming Key (EKA 201)

  1. Dayakeun pangontrol. Pastikeun controller disambungkeun ka mains.
  2. Sambungkeun EKA 201 ka controller ngagunakeun kabel panganteur controller masing-masing.
  3. EKA 201 bakal otomatis ngamimitian prosés program.

Danfoss EKC 224 Case Controller - konci Programming

Daptar parameter

Kodeu Manual téks pondok Min. Max. 2 Unit Urang Sunda/W EKC 224 Appl.
1 2 3 4
CFg Konfigurasi
r12 Saklar utama (-1 = jasa / 0 = OFF / 1 = 0N) -1 1 0 Urang Sunda/W * * * *
o61¹) Pamilihan mode aplikasi
(1) API: Cmp/Def/Fan/Lampu
(2) AP2: Cmp / Def / Fan / Alarm
(3)AP3: Cmp/ Al/F an/Cahaya
(4) AP4: Panas/Alarm/Lampu
1 4 Urang Sunda/W * * * *
o06¹) Pilihan tipe sénsor
(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1003, (3) Pct. = PTC 1000
0 3 2 Urang Sunda/W * * * *
o02¹) Konfigurasi Dell
(0) tina = henteu dianggo (1) SD = status, (2) fungsi doo-panto, (3) ngalakukeun = alarm panto, (4) SCH = switch utama,
(5) wengi = mode beurang / wengi, (6) rd = kapindahan rujukan (7) EAL = alarm éksternal, (8) def. = defrost,
(9) Pod = narik I ka handap, (10) Sc = sensor condenser
0 10 0 Urang Sunda/W * * * *
037¹) Konfigurasi DI2
(0) tina = henteu dianggo (1) SD = status, (2) fungsi doo-panto, (3) ngalakukeun = alarm panto, (4) SCH = switch utama,
(5) wengi = mode beurang / wengi, (6) kareta lesod = pamindahan refence (7) EAL = alarm éksternal, (8) def. = defrost,
(9) Pod = tarik ka handap
0 9 0 Urang Sunda/W * * * *
o62¹) Preset gancang parameter primér
0 = Teu dipaké
1 = MT, defrost alam, eureun dina waktu
2 = MT, El defrost, eureun dina waktu 3= MT, El defrost, eureun dina temp.
4 = LT, El defrost eureun dina temp.
5 = Kamar, MT, El defrost, eureun dina waktu 6 = Kamar, MT, El defrost, eureun dina temp.
7 = Kamar, LT, El defrost, eureun dina temp.
0 7 0 RIW * * *
o03¹) Alamat jaringan 0 247 0 Urang Sunda/W * * * *
r– Thermostat
r00 Setpoint suhu r03 r02 2.0 °C Urang Sunda/W * * * *
r01 Diferensial 0.1 20.0 2.0 K Urang Sunda/W * * * *
r02 Max. watesan setting setpoint r03 105.0 50.0 °C Urang Sunda/W * * * *
r03 Min. watesan setting setpoint –40.0 r02 –35.0 °C Urang Sunda/W * * * *
r04 Penyesuaian pamaca suhu tampilan –10.0 10.0 0.0 K Urang Sunda/W * * * *
r05 Unit suhu rC / °F) 0/C 1 / F 0/C Urang Sunda/W * * * *
r09 Koreksi sinyal ti sensor Sair –20.0 20.0 0.0 °C Urang Sunda/W * * * *
r12 Saklar utama (-1 = jasa / 0 = OFF / 1 = 0N) -1 1 0 Urang Sunda/W * * * *
r13 Kapindahan tina rujukan salila operasi peuting –50.0 50.0 0.0 K Urang Sunda/W * * *
r40 Pamindahan rujukan termostat –50.0 20.0 0.0 K Urang Sunda/W * * * *
r96 Durasi tarik-handap 0 960 0 min Urang Sunda/W * * *
r97 Suhu wates tarik-handap –40.0 105.0 0.0 °C Urang Sunda/W * * *
A- Setélan alarem
A03 Tunda pikeun alarm suhu (pondok) 0 240 30 min Urang Sunda/W * * * *
Al2 Tunda pikeun alarm suhu nalika pulldown (panjang) 0 240 60 min Urang Sunda/W * * * *
A13 wates alarem tinggi –40.0 105.0 8.0 °C Urang Sunda/W * * * *
A14 wates alarem low –40.0 105.0 –30.0 °C Urang Sunda/W * * * *
A27 Alarm reureuh Dll 0 240 30 min Urang Sunda/W * * * *
A28 Alarm reureuh DI2 0 240 30 min Urang Sunda/W * * * *
A37 Wates alarem pikeun alarm suhu condenser 0.0 200.0 80.0 °C Urang Sunda/W * * *
A54 Wates pikeun condenser block alarm jeung comp. Eureun 0.0 200.0 85.0 °C Urang Sunda/W * * *
A72 Voltage panyalindungan ngaktipkeun 0/No 1/Leres 0/No Urang Sunda/W * * *
A73 Minimum cut-di voltage 0 270 0 Volt Urang Sunda/W * * *
A74 Minimum cut-out voltage 0 270 0 Volt Urang Sunda/W * * *
A75 Maksimum cut-di voltage 0 270 270 Volt Urang Sunda/W * * *
d— Defrost
d01 Métode defrost
(0) non = Euweuh, (1) henteu = Alam, (2) E1 = Listrik, (3) gas = Gas panas
0 3 2 Urang Sunda/W * * *
d02 Defrost suhu eureun 0.0 50.0 6.0 °C Urang Sunda/W * * *
d03 Interval antara defrost dimimitian 0 240 8 jam Urang Sunda/W * * *
d04 Max. durasi defrost 0 480 30 min Urang Sunda/W * * *
d05 kapur offset pikeun mimiti defrost munggaran dina ngamimitian-up 0 240 0 min Urang Sunda/W * * *
d06 Waktu ngeclak 0 60 0 min Urang Sunda/W * * *
d07 Reureuh pikeun kipas ngamimitian sanggeus defrost 0 60 0 min Urang Sunda/W * * *
d08 Suhu mimiti kipas -40.0 50.0 -5.0 °C Urang Sunda/W * * *
d09 Operasi kipas salila defrost 0/Pareuman 1/ Dina 1/Dina Urang Sunda/W * * *
d10" Sénsor defrost (0=waktu, 1=Sair, 2=55) 0 2 0 Urang Sunda/W * * *
d18 Max. komp. runtime antara dua defrosts 0 96 0 jam Urang Sunda/W * * *
d19 Defrost on paménta - 55 hawa diwenangkeun variasi salila ibun ngawangun-up.
Dina tutuwuhan sentral pilih 20 K (=pareum)
0.0 20.0 20.0 K Urang Sunda/W * * *
d30 Defrost reureuh sanggeus pull-down (0 = OFF) 0 960 0 min Urang Sunda/W * * *
F— Kipas angin
F1 Kipas di eureun tina compressor
(0) FFC = Follow comp., (1) Foo = ON, (2) FPL = Kipas pulsing
0 2 1 Urang Sunda/W * * *
F4 Suhu eureun kipas (55) -40.0 50.0 50.0 °C Urang Sunda/W * * *
F7 Kipas pulsing ON siklus 0 180 2 min Urang Sunda/W * *
F8 Kipas pulsing siklus OFF 0 180 2 min Urang Sunda/W * * *
c— Kompresor
c01 Min. Dina waktosna 0 30 1 min Urang Sunda/W * * *
c02 Min. Pareum-waktos 0 30 2 min Urang Sunda/W * * *
c04 Kompresor OFF reureuh di panto muka 0 900 0 sek Urang Sunda/W * * *
c70 Pilihan pameuntasan nol 0/No 1/Leres 1/Leres Urang Sunda/W * * *
o— Rupa-rupa
o01 Tunda kaluaran nalika ngamimitian 0 600 10 sek Urang Sunda/W * * * *
o2" Konfigurasi DI1
(0) OFF = henteu dianggo (1) Sdc = status, (2) doo = fungsi panto, (3) doA = alarm panto, (4) SCH = switch utama
(5) nig = mode beurang / wengi, (6) rFd = kapindahan rujukan, (7) EAL = alarm éksternal, (8) dEF = clefrost,
(9) Pud = narik ka handap, (10) Sc = sensor condenser
0 10 0 Urang Sunda/W * * * *
o3" Alamat jaringan 0 247 0 Urang Sunda/W * * * *
5 Kodeu aksés 0 999 0 Urang Sunda/W * * * *
006″ Pilihan tipe sénsor
(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2)Pt = Pt1000, (3) Ptc = PTC 1000
0 3 2 Urang Sunda/W * * * *
o15 Resolusi tampilan
(0) 0.1, (1)0.5, (2)1.0
0 2 0 Urang Sunda/W * * * *
o16 Max. kapur sayaga sanggeus koordinasi defrost 0 360 20 min Urang Sunda/W * * *
o37'. Dl? konfigurasi
(0) tina = henteu dianggo (1) Karung = status, (2) doo = fungsi panto, (3) ngalakukeun = alarm panto, (4) SCH = switch utama,
(5) wengi = mode beurang / wengi, (6) rd = ref Terence kapindahan, (7) EAL = alarm éksternal, (8) def. = def lumpat,
(9) Pod = narik kuring ka handap
0 9 0 Urang Sunda/W * * * *
o38 Konfigurasi fungsi lampu
(0) on = salawasna on, (1) Dan = beurang / peuting
(2) doo = dumasar kana aksi panto, (3) jaring = Jaringan
0 3 1 Urang Sunda/W * * *
o39 Kontrol cahaya via jaringan (ngan upami o38=3(.NET)) 0/Pareuman 1/ Dina 1/Dina Urang Sunda/W * * *
061″ Pamilihan mode aplikasi
(1) API: Cmp/Def/Fan/Lampu
(2) AP2: Cmp / Def / kipas / A 6 pasisian
(3) AP3: Cmp/Al/Kipas/Lampu
(4) AP4: Panas / Alarm / Lampu
1 4 1 Urang Sunda/W * * * *
o62 urang Preset gancang parameter primér 0= Teu dipaké
1= MT, defrost alam, eureun dina waktu 2 = MT, El defrost, eureun dina waktu 3= MT, El defrost, eureun dina temp. 4 = LT, El defrost eureun dina temp
5 = Kamar, MT, El defrost, eureun dina waktu 6 = Kamar, MT, El defrost, eureun dina temp. 7 = Kamar, LT, El defrost, eureun dina temp.
0 7 0 Urang Sunda/W * * *
67 Ganti setélan pabrik Controllers sareng setélan ayeuna 0/No 1/Leres 0/No Urang Sunda/W * * * *
91 Témbongkeun dina defrost
(0) Hawa = Suhu Sari / (1) Fret = suhu beku / (2) -drvds ditampilkeun
0 2 2 Urang Sunda/W * * *
P— Polaritasna
P75 Balikkeun relay alarem (1) = Balikkeun aksi relay 0 1 0 Urang Sunda/W * * *
P76 Aktipkeun konci keyboard 0/No 1/Leres 0/No Urang Sunda/W * * * *
anjeun— Palayanan
u00 kaayaan kontrol 50: Normal, 51: Kutil sanggeus defrosting. 52: Min ON timer, 53: Min OFF timer, 54: Netes sering 510: r12 Main switch disetel OFF, 511: Thermostat cut-out 514: Defrosting, $15: Fan reureuh, 517: Panto muka, 520: cooling darurat, 525 : Kontrol manual, 530: Pulldown cycle, 532: Power up reureuh, S33: Pemanasan 0 33 0 R * * * *
u01 Suhu hawa Sari -100.0 200.0 0.0 °C R  * * * *
u09 S5 suhu évaporator -100.0 200.0 0.0 °C R * * * *
u10 Status input DI1 0/Pareuman 1/ Dina 0/Pareuman R * * * *
u13 Kaayaan peuting 0/Pareuman 1/ Dina 0/Pareuman R * * * *
u37 Status input DI2 0/Pareuman 1/ Dina 0/Pareuman R * * * *
u28 Rujukan thermostat sabenerna -100.0 200.0 0.0 R * * * *
u58 Compressor / garis Cairan klep solenoid 0/Pareuman 1/ Dina 0/Pareuman R * * *
u59 Relay kipas 0/Pareuman 1/ Dina 0/Pareuman R * * *
u60 Relay defrost 0/Pareuman 1/ Dina 0/Pareuman R * *
u62 Relay alarem 0/Pareuman 1/ Dina 0/Pareuman R * * *
u63 Relay cahaya 0/Pareuman 1/ Dina 0/Pareuman R * * *
LSO Pembacaan versi firmware R * * * *
u82 Kodeu Controller No. R * * * *
u84 Relay panas 0/Pareuman 1/ Dina 0/Pareuman R *
U09 Suhu Kondensor Sc -100.0 200.0 0.0 R * * *

1) Parameter ngan bisa dirobah lamun parameter r12 Main switch dina posisi OFF.

Kodeu alarem

Dina kaayaan alarem, tampilan bakal silih ganti antara pamacaan suhu hawa saleresna sareng pamacaan kodeu alarem alarm aktip.

Kodeu Alarem Katerangan Alarm jaringan
E29 Kasalahan sensor sari Sensor suhu hawa cacad atanapi sambungan listrik leungit - Kasalahan Sari
E27 Kasalahan sensor def S5 Evaporator sensor cacad atawa sambungan listrik leungit - Kasalahan S5
E30 kasalahan sensor SC Sensor Sac Condenser cacad atanapi sambungan listrik leungit - Kasalahan Sac
A01 Alarm suhu luhur Suhu hawa dina kabinét teuing tinggi - Alarm tinggi
A02 Alarm suhu rendah Suhu hawa dina kabinét rendah teuing - Low t. Alarem
A99 Alarm High Volt Pasokan voltage luhur teuing (perlindungan kompresor) - High Voltage
AA1 Alarm Low Volt Pasokan voltage rendah teuing (perlindungan kompresor) - Low Voltage
A61 Alarm kondensor Suhu kondensor luhur teuing - pariksa aliran hawa - Alarm Cond
A80 Cond. blok alarem Suhu kondensor luhur teuing - Reset manual alarm diperlukeun - Cond Diblokir
A04 Alarem panto Panto geus muka lila teuing - Alarem panto
A15 DI Alarm Alarm éksternal ti input DI - Alarm DI
A45 Alarm sayaga Kontrol geus dieureunkeun ku "r12 Main switch" - Modeu sayaga

1) The condenser block alarem bisa ngareset ku netepkeun r12 Main switch OFF na ON deui atawa ku powering handap controller.

Danfoss A / S
Solusi Iklim « danfoss.com « +45 7488 2222

Inpormasi naon waé, kalebet, tapi henteu dugi ka inpormasi ngeunaan pilihan produk, aplikasi atanapi panggunaanana, desain produk, beurat, dimensi, kapasitas atanapi data téknis anu sanés dina manual produk, déskripsi katalog, pariwara, jsb. , sacara lisan, éléktronik, online atanapi via download, bakal dianggap informatif, sarta ngan mengikat lamun jeung extent, rujukan eksplisit dijieun dina cutatan atawa konfirmasi urutan. Danfoss teu tiasa nampi tanggung jawab naon waé pikeun kamungkinan kasalahan dina katalog, brosur, pidéo sareng bahan sanés.
Danfoss ngagaduhan hak pikeun ngarobih produkna tanpa aya bewara. Ieu ogé lumaku pikeun produk anu dipesen tapi henteu dikirimkeun upami parobihan sapertos kitu tiasa dilakukeun tanpa parobihan bentuk, pas atanapi fungsi produk.
Sadaya merek dagang dina bahan ieu milik Danfoss A/S atawa pausahaan grup Danfoss. Danfoss sareng logo Danfoss mangrupikeun mérek dagang Danfoss A/S. Sadaya hak disimpen.

AN432635050585en-000201
© Danfoss | Solusi Iklim | 2023.05

Dokumén / Sumberdaya

Danfoss EKC 223 Case Controller [pdf] Pituduh instalasi