Téknik
Isukan
Guide instalasi
Kasus controller
Tipe EKC 223
Idéntifikasi
Aplikasi
Diménsi
Pamasangan
Wiring diagram
Aplikasi | Wiring diagram |
1 | ![]() |
2 | ![]() |
3 | ![]() |
4 | ![]() |
Catetan: Panyambungna kakuatan: ukuran kawat = 0.5 – 1.5 mm 2, max. tightening torsi = 0.4 Nm Low voltage panyambungna sinyal: ukuran kawat = 0.15 - 1.5 mm 2, max. tightening torsi = 0.2 Nm 2L na 3L kudu disambungkeun ka fase sarua.
Komunikasi data
Pamasangan | Wiring |
![]() EKC 22x controller bisa terpadu kana jaringan Modbus via RS-485 adaptor (EKA 206) ngagunakeun kabel panganteur (080N0327). Pikeun detil pamasangan mangga tingal pituduh pamasangan pikeun adaptor EKA 206 – RS485. |
![]() |
data teknis
Fitur | Katerangan |
Tujuan kontrol | Operasi kontrol sensing hawa cocog pikeun incorporation kana AC komérsial sarta aplikasi refrigeration |
Pangwangunan kontrol | kontrol incorporated |
Sasayogian tanaga | 084B4055 – 115 V AC / 084B4056 – 230 V AC 50/60 Hz, galvanik terasing vol lowtage suplai kakuatan diatur |
kakuatan dipeunteun | Kurang ti 0.7 W |
Input | Input sénsor, Input digital, Tombol Pemrograman Nyambung ka SELV énergi kawates <15 W |
Jenis sensor anu diidinan | NTC 5000 Ohm dina 25 °C, (Nilai Béta=3980 dina 25/100 °C - EKS 211) NTC 10000 Ohm dina 25 °C, (Nilai Béta=3435 dina 25/85 °C - EKS 221) PTC 990 Ohm dina 25 °C, (EKS 111) Pt1000, (AKS 11, AKS 12, AKS 21) |
Akurasi | Rentang ukur: -40 – 105 °C (-40 – 221 °F) |
akurasi controller: ± 1 K handap -35 °C, ± 0.5 K antara -35 - 25 °C, ± 1 K di luhur 25 °C |
|
Jenis tindakan | 1B (relay) |
Kaluaran | DO1 - Relay 1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA di 230 V, UL60730-1 16 FLA / 72 LRA di 115 V, UL60730-1 |
DO2 - Relay 2: 8 A, 2 FLA / 12 LRA, UL60730-1 8 A, 2 (2 A), EN60730-1 |
|
DO3 - Relay 3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1 |
|
DO4 - Relay 4: 2 A | |
tampilan | Tampilan LED, 3 digit, titik decimal sareng ikon multi-fungsi, skala °C + °F |
kaayaan operasi | -10 – 55 °C (14 – 131 °F), 90% Rh |
Kaayaan neundeun | -40 – 70 °C (-40 – +158 °F), 90% Rh |
Panyalindungan | Hareup: IP65 (Gasket terpadu) Pungkur: IP00 |
Lingkungan | Polusi gelar II, non-condensing |
Overvoltage kategori | II - 230 V Vérsi suplai - (ENEC, UL dipikawanoh) III - 115 V Vérsi suplai - (UL dipikawanoh) |
Résistansi kana panas sareng seuneu | Kategori D (UL94-V0) Suhu pikeun pernyataan tés tekanan bola Numutkeun Annex G (EN 60730-1) |
kategori EMC | Kategori I |
Persetujuan | Pangenal UL (AS & Kanada) (UL 60730-1) CE (Diréktif LVD & EMC) EAC (HANTU) UKCA UA CMIM ROHS2.0 persetujuan Hazloc pikeun refrigerants kaduruk (R290 / R600a). R290 / R600a aplikasi tungtung pamakéan employing luyu jeung sarat IEC60079-15. |
Operasi tampilan
Tombol di hareup tampilan bisa dioperasikeun ku pondok tur panjang (3s) pencét.
A | Indikasi status: LEDs hurung dina modeu ECO/Peuting, cooling, defrost jeung kipas ngajalankeun. |
B | Indikasi alarem: Ikon alarem hurung upami aya alarm. |
C | Pencét pondok = Napigasi deui Pencét panjang = Mimitian siklus pulldown. Pintonan bakal ditingalikeun "Pod" pikeun mastikeun ngamimitian. |
D | Pencét pondok = Napigasi ka luhur Pencét lila = Pindah controller ON/OFF (nyetél r12 switch utama dina posisi ON/OFF) |
E | Pencét pondok = Napigasi ka handap Pencét lila = Mimitian siklus defrosting. Pintonan bakal nunjukkeun kode "-d-" pikeun mastikeun ngamimitian. |
F | Pencét pondok = Robah set point Pencét panjang = Pindah ka ménu parameter |
Ngareset pabrik
Controller tiasa disetél deui ka setélan pabrik nganggo prosedur ieu:
- Kakuatan OFF controller
- Tetep tombol panah "∧" jeung handap "∨" dipencet bari nyambungkeun deui vol suplaitage
- Nalika kode "Raray" dipintonkeun dina tampilan, pilih "enya"
Catetan: Setélan pabrik OEM bakal janten setélan pabrik Danfoss atanapi setélan pabrik anu ditetepkeun ku pangguna upami parantos dilakukeun. Pamaké tiasa nyimpen setelan na salaku setelan pabrik OEM via parameter o67.
Kodeu tampilan
Kode tampilan | Katerangan |
-d- | Siklus defrost keur lumangsung |
Pod | A siklus pulldown suhu geus dimimitian |
lepat | Suhu teu tiasa ditampilkeun kusabab kasalahan sensor |
— | Ditémbongkeun dina luhureun tampilan: Nilai parameter geus ngahontal max. Wates |
— | Ditémbongkeun di handap tampilan: Nilai parameter geus ngahontal mnt. Wates |
Konci | Kibor tampilan dikonci |
Null | Kibor tampilan geus teu dikonci |
PS | Kodeu aksés diperlukeun pikeun ngasupkeun ménu parameter |
Kampak/Ext | Alarm atawa kasalahan kode kedip-kedip kalawan temp normal. bacakeun sing tarik |
Pareum | Kontrol dieureunkeun sakumaha r12 switch utama disetel OFF |
On | Kontrol dimimitian nalika saklar utama r12 disetel ON (kode ditémbongkeun dina 3 detik) |
Beungeut | Controller direset kana setélan pabrik |
Menu parameter diaksés ku mencét tombol "SET" pikeun 3 detik. Upami kode panyalindungan aksés "o05" parantos ditetepkeun, tampilan bakal naroskeun kodeu aksés ku nunjukkeun kodeu "PS". Sakali kodeu aksés geus disadiakeun ku pamaké, daptar parameter bakal diakses.
Meunang mimiti alus
Kalayan prosedur ieu anjeun tiasa ngamimitian pangaturan gancang pisan:
- Pencét tombol "SET" kanggo 3 detik sareng aksés menu parameter (tampilan bakal nunjukkeun "di")
- Pencét tombol handap "∨" pikeun muka menu "tcfg" (tampilan bakal nunjukkeun "tcfg")
- Pencét tombol katuhu / ">" pikeun muka ménu konfigurasi (tampilan bakal nunjukkeun r12)
- Buka parameter "r12 Main switch" sareng ngeureunkeun kadali ku netepkeun OFF (Pencét SET)
- Buka "mode aplikasi o61" sareng pilih mode aplikasi anu diperyogikeun (Pencét SET)
- Buka "o06 Sensor type" tur pilih tipe sensor suhu dipaké (n5 = NTC 5 K, n10 = NTC 10 K, Pct. = PTC, Pt1 = Pt1000) - (Pencét "SET").
- Buka "O02 DI1 Konfigurasi" tur pilih fungsi pakait jeung input digital 1 (Mangga tingal daptar parameter) - (Pencét "SET").
- Buka "O37 DI2 Konfigurasi" tur pilih fungsi pakait jeung input digital 2 (Mangga tingal daptar parameter) - (Pencét "SET").
- Buka parameter "o62 Quick setting" sareng pilih prasetél anu cocog sareng aplikasi anu dianggo (punten tingal tabel prasetél di handap) - (Pencét "SET").
- Buka "alamat Jaringan o03" sareng setel alamat Modbus upami diperyogikeun.
- Arahkeun deui ka parameter "r12 Main switch" tur nyetel eta dina posisi "ON" pikeun ngamimitian kontrol.
- Ngaliwat sadaya daptar parameter sareng robih setélan pabrik upami diperyogikeun.
Pamilihan setélan gancang
Setélan gancang | 1 | 2 | 3 | 4 | 5 | 6 | 7 |
Kabinet MT def alam. Eureun dina waktuna |
Kabinet MT El. def. Eureun dina waktuna |
Kabinet MT El. def. Eureun dina suhu |
Kabinet LT El. def. Eureun dina suhu |
Ruang MT El. def. Eureun dina waktuna |
Ruang MT El. def. Eureun dina suhu |
Kamar LT El. def. Eureun dina suhu |
|
r00 Cut-kaluar | 4 °C | 2 °C | 2 °C | -24 °C | 6 °C | 3 °C | -22 °C |
r02 Max Cut-kaluar | 6 °C | 4 °C | 4 °C | -22 °C | 8 °C | 5 °C | -20 °C |
r03 Min Cut-kaluar | 2 °C | 0 °C | 0 °C | -26 °C | 4 °C | 1 °C | -24 °C |
A13 Kacida Hawa | 10 °C | 8 °C | 8 °C | -15 °C | 10 °C | 8 °C | -15 °C |
Al 4 Lowly Hawa | -5 °C | -5 °C | -5 °C | -30 °C | 0 °C | 0 °C | -30 °C |
d01 Def. Métode | Alami | Listrik | Listrik | Listrik | Listrik | Listrik | Listrik |
d03 Def.lnterval | 6 jam | 6 jam | 6 jam | 12 jam | 8 jam | 8 jam | 12 jam |
d10 DefStopSens. | Waktos | Waktos | S5 sénsor | 55 sénsor | Waktos | S5 sénsor | S5 sénsor |
o02 DI1 Konfigurasi. | Panto fct. | Panto fct. | Panto fct. |
konci programming
Programming controller sareng Mass Programming Key (EKA 201)
- Dayakeun pangontrol. Pastikeun controller disambungkeun ka mains.
- Sambungkeun EKA 201 ka controller ngagunakeun kabel panganteur controller masing-masing.
- EKA 201 bakal otomatis ngamimitian prosés program.
Daptar parameter
Kodeu | Manual téks pondok | Min. | Max. | 2 | Unit | Urang Sunda/W | EKC 224 Appl. | |||
1 | 2 | 3 | 4 | |||||||
CFg | Konfigurasi | |||||||||
r12 | Saklar utama (-1 = jasa / 0 = OFF / 1 = 0N) | -1 | 1 | 0 | Urang Sunda/W | * | * | * | * | |
o61¹) | Pamilihan mode aplikasi (1) API: Cmp/Def/Fan/Lampu (2) AP2: Cmp / Def / Fan / Alarm (3)AP3: Cmp/ Al/F an/Cahaya (4) AP4: Panas/Alarm/Lampu |
1 | 4 | Urang Sunda/W | * | * | * | * | ||
o06¹) | Pilihan tipe sénsor (0) n5 = NTC 5k, (1) n10 = NTC 10k, (2) Pt = Pt1003, (3) Pct. = PTC 1000 |
0 | 3 | 2 | Urang Sunda/W | * | * | * | * | |
o02¹) | Konfigurasi Dell (0) tina = henteu dianggo (1) SD = status, (2) fungsi doo-panto, (3) ngalakukeun = alarm panto, (4) SCH = switch utama, (5) wengi = mode beurang / wengi, (6) rd = kapindahan rujukan (7) EAL = alarm éksternal, (8) def. = defrost, (9) Pod = narik I ka handap, (10) Sc = sensor condenser |
0 | 10 | 0 | Urang Sunda/W | * | * | * | * | |
037¹) | Konfigurasi DI2 (0) tina = henteu dianggo (1) SD = status, (2) fungsi doo-panto, (3) ngalakukeun = alarm panto, (4) SCH = switch utama, (5) wengi = mode beurang / wengi, (6) kareta lesod = pamindahan refence (7) EAL = alarm éksternal, (8) def. = defrost, (9) Pod = tarik ka handap |
0 | 9 | 0 | Urang Sunda/W | * | * | * | * | |
o62¹) | Preset gancang parameter primér 0 = Teu dipaké 1 = MT, defrost alam, eureun dina waktu 2 = MT, El defrost, eureun dina waktu 3= MT, El defrost, eureun dina temp. 4 = LT, El defrost eureun dina temp. 5 = Kamar, MT, El defrost, eureun dina waktu 6 = Kamar, MT, El defrost, eureun dina temp. 7 = Kamar, LT, El defrost, eureun dina temp. |
0 | 7 | 0 | RIW | * | * | * | ||
o03¹) | Alamat jaringan | 0 | 247 | 0 | Urang Sunda/W | * | * | * | * | |
r– | Thermostat | |||||||||
r00 | Setpoint suhu | r03 | r02 | 2.0 | °C | Urang Sunda/W | * | * | * | * |
r01 | Diferensial | 0.1 | 20.0 | 2.0 | K | Urang Sunda/W | * | * | * | * |
r02 | Max. watesan setting setpoint | r03 | 105.0 | 50.0 | °C | Urang Sunda/W | * | * | * | * |
r03 | Min. watesan setting setpoint | –40.0 | r02 | –35.0 | °C | Urang Sunda/W | * | * | * | * |
r04 | Penyesuaian pamaca suhu tampilan | –10.0 | 10.0 | 0.0 | K | Urang Sunda/W | * | * | * | * |
r05 | Unit suhu rC / °F) | 0/C | 1 / F | 0/C | Urang Sunda/W | * | * | * | * | |
r09 | Koreksi sinyal ti sensor Sair | –20.0 | 20.0 | 0.0 | °C | Urang Sunda/W | * | * | * | * |
r12 | Saklar utama (-1 = jasa / 0 = OFF / 1 = 0N) | -1 | 1 | 0 | Urang Sunda/W | * | * | * | * | |
r13 | Kapindahan tina rujukan salila operasi peuting | –50.0 | 50.0 | 0.0 | K | Urang Sunda/W | * | * | * | |
r40 | Pamindahan rujukan termostat | –50.0 | 20.0 | 0.0 | K | Urang Sunda/W | * | * | * | * |
r96 | Durasi tarik-handap | 0 | 960 | 0 | min | Urang Sunda/W | * | * | * | |
r97 | Suhu wates tarik-handap | –40.0 | 105.0 | 0.0 | °C | Urang Sunda/W | * | * | * | |
A- | Setélan alarem | |||||||||
A03 | Tunda pikeun alarm suhu (pondok) | 0 | 240 | 30 | min | Urang Sunda/W | * | * | * | * |
Al2 | Tunda pikeun alarm suhu nalika pulldown (panjang) | 0 | 240 | 60 | min | Urang Sunda/W | * | * | * | * |
A13 | wates alarem tinggi | –40.0 | 105.0 | 8.0 | °C | Urang Sunda/W | * | * | * | * |
A14 | wates alarem low | –40.0 | 105.0 | –30.0 | °C | Urang Sunda/W | * | * | * | * |
A27 | Alarm reureuh Dll | 0 | 240 | 30 | min | Urang Sunda/W | * | * | * | * |
A28 | Alarm reureuh DI2 | 0 | 240 | 30 | min | Urang Sunda/W | * | * | * | * |
A37 | Wates alarem pikeun alarm suhu condenser | 0.0 | 200.0 | 80.0 | °C | Urang Sunda/W | * | * | * | |
A54 | Wates pikeun condenser block alarm jeung comp. Eureun | 0.0 | 200.0 | 85.0 | °C | Urang Sunda/W | * | * | * | |
A72 | Voltage panyalindungan ngaktipkeun | 0/No | 1/Leres | 0/No | Urang Sunda/W | * | * | * | ||
A73 | Minimum cut-di voltage | 0 | 270 | 0 | Volt | Urang Sunda/W | * | * | * | |
A74 | Minimum cut-out voltage | 0 | 270 | 0 | Volt | Urang Sunda/W | * | * | * | |
A75 | Maksimum cut-di voltage | 0 | 270 | 270 | Volt | Urang Sunda/W | * | * | * | |
d— | Defrost | |||||||||
d01 | Métode defrost (0) non = Euweuh, (1) henteu = Alam, (2) E1 = Listrik, (3) gas = Gas panas |
0 | 3 | 2 | Urang Sunda/W | * | * | * | ||
d02 | Defrost suhu eureun | 0.0 | 50.0 | 6.0 | °C | Urang Sunda/W | * | * | * | |
d03 | Interval antara defrost dimimitian | 0 | 240 | 8 | jam | Urang Sunda/W | * | * | * | |
d04 | Max. durasi defrost | 0 | 480 | 30 | min | Urang Sunda/W | * | * | * | |
d05 | kapur offset pikeun mimiti defrost munggaran dina ngamimitian-up | 0 | 240 | 0 | min | Urang Sunda/W | * | * | * | |
d06 | Waktu ngeclak | 0 | 60 | 0 | min | Urang Sunda/W | * | * | * | |
d07 | Reureuh pikeun kipas ngamimitian sanggeus defrost | 0 | 60 | 0 | min | Urang Sunda/W | * | * | * | |
d08 | Suhu mimiti kipas | -40.0 | 50.0 | -5.0 | °C | Urang Sunda/W | * | * | * | |
d09 | Operasi kipas salila defrost | 0/Pareuman | 1/ Dina | 1/Dina | Urang Sunda/W | * | * | * | ||
d10" | Sénsor defrost (0=waktu, 1=Sair, 2=55) | 0 | 2 | 0 | Urang Sunda/W | * | * | * | ||
d18 | Max. komp. runtime antara dua defrosts | 0 | 96 | 0 | jam | Urang Sunda/W | * | * | * | |
d19 | Defrost on paménta - 55 hawa diwenangkeun variasi salila ibun ngawangun-up. Dina tutuwuhan sentral pilih 20 K (=pareum) |
0.0 | 20.0 | 20.0 | K | Urang Sunda/W | * | * | * | |
d30 | Defrost reureuh sanggeus pull-down (0 = OFF) | 0 | 960 | 0 | min | Urang Sunda/W | * | * | * | |
F— | Kipas angin | |||||||||
F1 | Kipas di eureun tina compressor (0) FFC = Follow comp., (1) Foo = ON, (2) FPL = Kipas pulsing |
0 | 2 | 1 | Urang Sunda/W | * | * | * | ||
F4 | Suhu eureun kipas (55) | -40.0 | 50.0 | 50.0 | °C | Urang Sunda/W | * | * | * | |
F7 | Kipas pulsing ON siklus | 0 | 180 | 2 | min | Urang Sunda/W | * | * | ||
F8 | Kipas pulsing siklus OFF | 0 | 180 | 2 | min | Urang Sunda/W | * | * | * | |
c— | Kompresor | |||||||||
c01 | Min. Dina waktosna | 0 | 30 | 1 | min | Urang Sunda/W | * | * | * | |
c02 | Min. Pareum-waktos | 0 | 30 | 2 | min | Urang Sunda/W | * | * | * | |
c04 | Kompresor OFF reureuh di panto muka | 0 | 900 | 0 | sek | Urang Sunda/W | * | * | * | |
c70 | Pilihan pameuntasan nol | 0/No | 1/Leres | 1/Leres | Urang Sunda/W | * | * | * | ||
o— | Rupa-rupa | |||||||||
o01 | Tunda kaluaran nalika ngamimitian | 0 | 600 | 10 | sek | Urang Sunda/W | * | * | * | * |
o2" | Konfigurasi DI1 (0) OFF = henteu dianggo (1) Sdc = status, (2) doo = fungsi panto, (3) doA = alarm panto, (4) SCH = switch utama (5) nig = mode beurang / wengi, (6) rFd = kapindahan rujukan, (7) EAL = alarm éksternal, (8) dEF = clefrost, (9) Pud = narik ka handap, (10) Sc = sensor condenser |
0 | 10 | 0 | Urang Sunda/W | * | * | * | * | |
o3" | Alamat jaringan | 0 | 247 | 0 | Urang Sunda/W | * | * | * | * | |
5 | Kodeu aksés | 0 | 999 | 0 | Urang Sunda/W | * | * | * | * | |
006″ | Pilihan tipe sénsor (0) n5 = NTC 5k, (1) n10 = NTC 10k, (2)Pt = Pt1000, (3) Ptc = PTC 1000 |
0 | 3 | 2 | Urang Sunda/W | * | * | * | * | |
o15 | Resolusi tampilan (0) 0.1, (1)0.5, (2)1.0 |
0 | 2 | 0 | Urang Sunda/W | * | * | * | * | |
o16 | Max. kapur sayaga sanggeus koordinasi defrost | 0 | 360 | 20 | min | Urang Sunda/W | * | * | * | |
o37'. | Dl? konfigurasi (0) tina = henteu dianggo (1) Karung = status, (2) doo = fungsi panto, (3) ngalakukeun = alarm panto, (4) SCH = switch utama, (5) wengi = mode beurang / wengi, (6) rd = ref Terence kapindahan, (7) EAL = alarm éksternal, (8) def. = def lumpat, (9) Pod = narik kuring ka handap |
0 | 9 | 0 | Urang Sunda/W | * | * | * | * | |
o38 | Konfigurasi fungsi lampu (0) on = salawasna on, (1) Dan = beurang / peuting (2) doo = dumasar kana aksi panto, (3) jaring = Jaringan |
0 | 3 | 1 | Urang Sunda/W | * | * | * | ||
o39 | Kontrol cahaya via jaringan (ngan upami o38=3(.NET)) | 0/Pareuman | 1/ Dina | 1/Dina | Urang Sunda/W | * | * | * | ||
061″ | Pamilihan mode aplikasi (1) API: Cmp/Def/Fan/Lampu (2) AP2: Cmp / Def / kipas / A 6 pasisian (3) AP3: Cmp/Al/Kipas/Lampu (4) AP4: Panas / Alarm / Lampu |
1 | 4 | 1 | Urang Sunda/W | * | * | * | * | |
o62 urang | Preset gancang parameter primér 0= Teu dipaké 1= MT, defrost alam, eureun dina waktu 2 = MT, El defrost, eureun dina waktu 3= MT, El defrost, eureun dina temp. 4 = LT, El defrost eureun dina temp 5 = Kamar, MT, El defrost, eureun dina waktu 6 = Kamar, MT, El defrost, eureun dina temp. 7 = Kamar, LT, El defrost, eureun dina temp. |
0 | 7 | 0 | Urang Sunda/W | * | * | * | ||
67 | Ganti setélan pabrik Controllers sareng setélan ayeuna | 0/No | 1/Leres | 0/No | Urang Sunda/W | * | * | * | * | |
91 | Témbongkeun dina defrost (0) Hawa = Suhu Sari / (1) Fret = suhu beku / (2) -drvds ditampilkeun |
0 | 2 | 2 | Urang Sunda/W | * | * | * | ||
P— | Polaritasna | |||||||||
P75 | Balikkeun relay alarem (1) = Balikkeun aksi relay | 0 | 1 | 0 | Urang Sunda/W | * | * | * | ||
P76 | Aktipkeun konci keyboard | 0/No | 1/Leres | 0/No | Urang Sunda/W | * | * | * | * | |
anjeun— | Palayanan | |||||||||
u00 | kaayaan kontrol 50: Normal, 51: Kutil sanggeus defrosting. 52: Min ON timer, 53: Min OFF timer, 54: Netes sering 510: r12 Main switch disetel OFF, 511: Thermostat cut-out 514: Defrosting, $15: Fan reureuh, 517: Panto muka, 520: cooling darurat, 525 : Kontrol manual, 530: Pulldown cycle, 532: Power up reureuh, S33: Pemanasan | 0 | 33 | 0 | R | * | * | * | * | |
u01 | Suhu hawa Sari | -100.0 | 200.0 | 0.0 | °C | R | * | * | * | * |
u09 | S5 suhu évaporator | -100.0 | 200.0 | 0.0 | °C | R | * | * | * | * |
u10 | Status input DI1 | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | * | |
u13 | Kaayaan peuting | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | * | |
u37 | Status input DI2 | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | * | |
u28 | Rujukan thermostat sabenerna | -100.0 | 200.0 | 0.0 | R | * | * | * | * | |
u58 | Compressor / garis Cairan klep solenoid | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | ||
u59 | Relay kipas | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | ||
u60 | Relay defrost | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | |||
u62 | Relay alarem | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | ||
u63 | Relay cahaya | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | * | * | ||
LSO | Pembacaan versi firmware | R | * | * | * | * | ||||
u82 | Kodeu Controller No. | R | * | * | * | * | ||||
u84 | Relay panas | 0/Pareuman | 1/ Dina | 0/Pareuman | R | * | ||||
U09 | Suhu Kondensor Sc | -100.0 | 200.0 | 0.0 | R | * | * | * |
1) Parameter ngan bisa dirobah lamun parameter r12 Main switch dina posisi OFF.
Kodeu alarem
Dina kaayaan alarem, tampilan bakal silih ganti antara pamacaan suhu hawa saleresna sareng pamacaan kodeu alarem alarm aktip.
Kodeu | Alarem | Katerangan | Alarm jaringan |
E29 | Kasalahan sensor sari | Sensor suhu hawa cacad atanapi sambungan listrik leungit | - Kasalahan Sari |
E27 | Kasalahan sensor def | S5 Evaporator sensor cacad atawa sambungan listrik leungit | - Kasalahan S5 |
E30 | kasalahan sensor SC | Sensor Sac Condenser cacad atanapi sambungan listrik leungit | - Kasalahan Sac |
A01 | Alarm suhu luhur | Suhu hawa dina kabinét teuing tinggi | - Alarm tinggi |
A02 | Alarm suhu rendah | Suhu hawa dina kabinét rendah teuing | - Low t. Alarem |
A99 | Alarm High Volt | Pasokan voltage luhur teuing (perlindungan kompresor) | - High Voltage |
AA1 | Alarm Low Volt | Pasokan voltage rendah teuing (perlindungan kompresor) | - Low Voltage |
A61 | Alarm kondensor | Suhu kondensor luhur teuing - pariksa aliran hawa | - Alarm Cond |
A80 | Cond. blok alarem | Suhu kondensor luhur teuing - Reset manual alarm diperlukeun | - Cond Diblokir |
A04 | Alarem panto | Panto geus muka lila teuing | - Alarem panto |
A15 | DI Alarm | Alarm éksternal ti input DI | - Alarm DI |
A45 | Alarm sayaga | Kontrol geus dieureunkeun ku "r12 Main switch" | - Modeu sayaga |
1) The condenser block alarem bisa ngareset ku netepkeun r12 Main switch OFF na ON deui atawa ku powering handap controller.
Danfoss A / S
Solusi Iklim « danfoss.com « +45 7488 2222
Inpormasi naon waé, kalebet, tapi henteu dugi ka inpormasi ngeunaan pilihan produk, aplikasi atanapi panggunaanana, desain produk, beurat, dimensi, kapasitas atanapi data téknis anu sanés dina manual produk, déskripsi katalog, pariwara, jsb. , sacara lisan, éléktronik, online atanapi via download, bakal dianggap informatif, sarta ngan mengikat lamun jeung extent, rujukan eksplisit dijieun dina cutatan atawa konfirmasi urutan. Danfoss teu tiasa nampi tanggung jawab naon waé pikeun kamungkinan kasalahan dina katalog, brosur, pidéo sareng bahan sanés.
Danfoss ngagaduhan hak pikeun ngarobih produkna tanpa aya bewara. Ieu ogé lumaku pikeun produk anu dipesen tapi henteu dikirimkeun upami parobihan sapertos kitu tiasa dilakukeun tanpa parobihan bentuk, pas atanapi fungsi produk.
Sadaya merek dagang dina bahan ieu milik Danfoss A/S atawa pausahaan grup Danfoss. Danfoss sareng logo Danfoss mangrupikeun mérek dagang Danfoss A/S. Sadaya hak disimpen.
AN432635050585en-000201
© Danfoss | Solusi Iklim | 2023.05