ENGINEERING
ESOK
Guide Instalasi
Pengontrol kasus
Tipe EKC 223
Identifikasi
Aplikasi
ukuran
Pemasangan
Wiring diagram
Aplikasi | Wiring diagram |
1 | ![]() |
2 | ![]() |
3 | ![]() |
4 | ![]() |
Cathetan: Konektor daya: ukuran kawat = 0.5 – 1.5 mm 2, maks. torsi tightening = 0.4 Nm Low voltagkonektor sinyal e: ukuran kabel = 0.15 – 1.5 mm 2, max. torsi tightening = 0.2 Nm 2L lan 3L kudu disambungake menyang phase padha.
Komunikasi data
Instalasi | Wiring |
![]() Kontroler EKC 22x bisa digabungake menyang jaringan Modbus liwat adaptor RS-485 (EKA 206) nggunakake kabel antarmuka (080N0327). Kanggo rincian instalasi, waca pandhuan instalasi kanggo adaptor EKA 206 – RS485. |
![]() |
data teknis
Fitur | Katrangan |
Tujuan kontrol | Kontrol sensing suhu operasi sing cocog kanggo digabungake menyang aplikasi AC lan kulkas komersial |
Konstruksi kontrol | Kontrol tergabung |
sumber daya | 084B4055 – 115 V AC / 084B4056 – 230 V AC 50/60 Hz, galvanik isolasi low voltage sumber daya diatur |
daya dirating | Kurang saka 0.7 W |
Input | Input sensor, Input digital, Tombol Pemrograman Disambungake menyang energi winates SELV <15 W |
Jinis sensor sing diidini | NTC 5000 Ohm ing 25 °C, (Nilai Beta=3980 ing 25/100 °C - EKS 211) NTC 10000 Ohm ing 25 °C, (Nilai Beta=3435 ing 25/85 °C - EKS 221) PTC 990 Ohm ing 25 °C, (EKS 111) Pt1000, (AKS 11, AKS 12, AKS 21) |
Akurasi | Rentang pangukuran: -40 – 105 °C (-40 – 221 °F) |
Akurasi Controller: ± 1 K ing ngisor -35 °C, ± 0.5 K antarane -35 – 25 °C, ± 1 K ing ndhuwur 25 °C |
|
Jinis tumindak | 1B (relay) |
Output | DO1 - Relay 1: 16 A, 16 (16) A, EN 60730-1 10 FLA / 60 LRA ing 230 V, UL60730-1 16 FLA / 72 LRA ing 115 V, UL60730-1 |
DO2 - Relay 2: 8 A, 2 FLA / 12 LRA, UL60730-1 8 A, 2 (2 A), EN60730-1 |
|
DO3 - Relay 3: 3 A, 2 FLA / 12 LRA, UL60730-1 3 A, 2 (2 A), EN60730-1 |
|
DO4 – Relay 4: 2 A | |
Tampilan | Tampilan LED, 3 digit, titik desimal lan lambang multi-fungsi, skala °C + °F |
kahanan operasi | -10 – 55 °C (14 – 131 °F), 90% Rh |
Kondisi panyimpenan | -40 – 70 °C (-40 – +158 °F), 90% Rh |
pangayoman | Ngarep: IP65 (gasket terpadu) Mburi: IP00 |
lingkungan | Tingkat polusi II, non-kondensasi |
Overvoltage kategori | II – 230 V versi sumber – (ENEC, UL dikenali) III – 115 V versi sumber – (UL diakoni) |
Resistance kanggo panas lan geni | Kategori D (UL94-V0) Suhu kanggo statement tes tekanan bola Miturut Annex G (EN 60730-1) |
Kategori EMC | Kategori I |
Persetujuan | Pangenalan UL (AS & Kanada) (UL 60730-1) CE (LVD & EMC Directive) EAC (HANTU) UKCA UA CMIM ROHS 2.0 Persetujuan Hazloc kanggo refrigeran sing gampang kobong (R290/R600a). R290/R600a aplikasi pungkasan nggunakake makaryakke sesuai karo syarat IEC60079-15. |
Operasi tampilan
Tombol ing ngarep tampilan bisa dioperasikake kanthi mencet cendhak lan dawa (3s).
A | Indikasi status: Lampu LED ing mode ECO/Night, pendinginan, defrost lan kipas mlaku. |
B | Indikasi weker: Lambang weker kelip-kelip yen ana weker. |
C | Pencet cendhak = Navigasi bali Pencet dawa = Miwiti siklus pulldown. Tampilan bakal nuduhake "Pod" kanggo konfirmasi wiwitan. |
D | Pencet cendhak = Navigasi munggah Tekan dawa = Ngalih pengontrol ON/OFF (nyetel r12 Saklar utama ing posisi ON/OFF) |
E | Pencet cendhak = Navigasi mudhun Pencet dawa = Mulai siklus defrosting. Tampilan bakal nuduhake kode "-d-" kanggo konfirmasi wiwitan. |
F | Pencet cendhak = Ganti set point Pencet dawa = Pindhah menyang menu parameter |
Reset pabrik
Kontroler bisa diset bali menyang setelan pabrik kanthi nggunakake prosedur ing ngisor iki:
- Kontrol daya OFF
- Terus tombol panah "∧" lan mudhun "∨" ditekan nalika nyambungake maneh sumber voltage
- Nalika kode "Pasuryan" ditampilake ing tampilan, pilih "ya"
Cathetan: Setelan pabrik OEM bakal dadi setelan pabrik Danfoss utawa setelan pabrik sing ditetepake pangguna yen wis digawe. Pangguna bisa nyimpen setelan kasebut minangka setelan pabrik OEM liwat parameter o67.
Kode tampilan
Kode tampilan | Katrangan |
-d- | Siklus defrost lagi ditindakake |
Pod | Siklus pulldown suhu wis diwiwiti |
Kesalahan | Suhu ora bisa ditampilake amarga kesalahan sensor |
— | Dituduhake ing ndhuwur tampilan: Nilai parameter wis tekan maksimal. watesan |
— | Dituduhake ing ngisor tampilan: Nilai parameter wis tekan min. watesan |
Kunci | Papan tombol tampilan dikunci |
Null | Papan tombol tampilan wis ora dikunci |
PS | Kode akses dibutuhake kanggo ngetik menu parameter |
Ax / Ext | Weker utawa kode kesalahan sumunar kanthi suhu normal. wacan |
OFF | Kontrol mandheg nalika r12 ngalih utama disetel OFF |
On | Kontrol diwiwiti nalika switch utama r12 disetel ON (kode ditampilake ing 3 detik) |
Pasuryan | Kontroler direset menyang setelan pabrik |
Menu parameter diakses kanthi mencet tombol "SET" kanggo 3 detik. Yen kode proteksi akses "o05" wis ditetepake tampilan bakal njaluk kode akses kanthi nuduhake kode "PS". Sawise kode akses wis diwenehake dening pangguna, dhaptar parameter bakal diakses.
Entuk wiwitan sing apik
Kanthi prosedur ing ngisor iki, sampeyan bisa miwiti regulasi kanthi cepet:
- Pencet tombol "SET" kanggo 3 detik lan ngakses menu parameter (tampilan bakal nuduhake "ing")
- Pencet tombol mudhun "∨" kanggo pindhah menyang menu "tcfg" (tampilan bakal nuduhake "tcfg")
- Pencet tombol tengen / ">" kanggo mbukak menu konfigurasi (tampilan bakal nuduhake r12)
- Bukak parameter "r12 Main switch" lan mungkasi kontrol kanthi nyetel OFF (Pencet SET)
- Bukak "mode aplikasi o61" lan pilih mode aplikasi sing dibutuhake (Pencet SET)
- Bukak "o06 Sensor type" lan pilih jinis sensor suhu sing digunakake (n5 = NTC 5 K, n10 = NTC 10 K, Pct. = PTC, Pt1 = Pt1000) - (Pencet "SET").
- Bukak "O02 DI1 Konfigurasi" lan pilih fungsi sing ana gandhengane karo input digital 1 (Mangga deleng dhaptar parameter) - (Pencet "SET").
- Bukak "O37 DI2 Konfigurasi" lan pilih fungsi sing ana gandhengane karo input digital 2 (Mangga deleng dhaptar parameter) - (Pencet "SET").
- Bukak parameter "o62 Quick setting" lan pilih prasetel sing cocog karo aplikasi sing digunakake (waca tabel prasetel ing ngisor iki) - (Pencet "SET").
- Bukak "alamat Jaringan o03" lan setel alamat Modbus yen dibutuhake.
- Navigasi bali menyang parameter "r12 Main switch" lan nyetel ing posisi "ON" kanggo miwiti kontrol.
- Bukak kabeh dhaptar parameter lan ganti setelan pabrik yen perlu.
Pamilihan setelan cepet
Setelan cepet | 1 | 2 | 3 | 4 | 5 | 6 | 7 |
Kabinet MT Natural def. Mungkasi ing wektu |
Kabinet MT El. def. Mungkasi ing wektu |
Kabinet MT El. def. Mungkasi ing suhu |
Kabinet LT El. def. Mungkasi ing suhu |
Ruang MT El. def. Mungkasi ing wektu |
Ruang MT El. def. Mungkasi ing suhu |
Kamar LT El. def. Mungkasi ing suhu |
|
r00 Cut-out | 4 °C | 2 °C | 2 °C | -24 °C | 6 °C | 3 °C | -22 °C |
r02 Max Cut-out | 6 °C | 4 °C | 4 °C | -22 °C | 8 °C | 5 °C | -20 °C |
r03 Min Cut-out | 2 °C | 0 °C | 0 °C | -26 °C | 4 °C | 1 °C | -24 °C |
A13 Highly Air | 10 °C | 8 °C | 8 °C | -15 °C | 10 °C | 8 °C | -15 °C |
Al 4 Lowly Air | -5 °C | -5 °C | -5 °C | -30 °C | 0 °C | 0 °C | -30 °C |
d01 Def. Metode | Alamiah | listrik | listrik | listrik | listrik | listrik | listrik |
d03 Def.lnterval | 6 jam | 6 jam | 6 jam | 12 jam | 8 jam | 8 jam | 12 jam |
d10 DefStopSens. | Wektu | Wektu | S5 Sensor Kab | 55 Sensor | Wektu | S5 Sensor Kab | S5 Sensor Kab |
o02 DI1 Konfigurasi. | Lawang fct. | Lawang fct. | Lawang fct. |
Tombol pemrograman
Pengontrol pemrograman dengan Mass Programming Key (EKA 201)
- Power munggah controller. Priksa manawa pengontrol disambungake menyang listrik.
- Sambungake EKA 201 menyang controller nggunakake kabel antarmuka controller pamilike.
- EKA 201 bakal miwiti proses pemrograman kanthi otomatis.
Daftar parameter
Kode | Manual teks singkat | Min. | Maks. | 2 | Unit | R/W | EKC 224 Appl. | |||
1 | 2 | 3 | 4 | |||||||
CFg | Konfigurasi | |||||||||
r12 | Saklar utama (-1 = layanan / 0 = OFF / 1 = 0N) | -1 | 1 | 0 | R/W | * | * | * | * | |
o61¹) | Pilihan saka mode aplikasi (1) API: Cmp/Def/Fan/Light (2) AP2: Cmp/Def/Fan/Weker (3)AP3: Cmp/ Al/F an/Light (4) AP4: Panas/Weker/Lampu |
1 | 4 | R/W | * | * | * | * | ||
o06¹) | Pilihan jinis sensor (0) n5= NTC 5k, (1) n10 = NTC 10k, (2)Pt = Pt1003, (3) Pt. = PTC 1000 |
0 | 3 | 2 | R/W | * | * | * | * | |
o02¹) | Konfigurasi Dell (0) saka = ora digunakake (1) SD = status, (2) fungsi doo-lawang, (3) do = weker lawang, (4) SCH = switch utama, (5) wengi = mode awan / wengi, (6) rd = pamindahan referensi (7) EAL = weker eksternal, (8) def. = defrost, (9) Pod = narik I mudhun, (10) Sc = sensor kondensor |
0 | 10 | 0 | R/W | * | * | * | * | |
037¹) | konfigurasi DI2 (0) saka = ora digunakake (1) SD = status, (2) fungsi doo-lawang, (3) do = weker lawang, (4) SCH = switch utama, (5) bengi=mode awan/wengi, (6) sled=pamindahan refrefence (7) EAL=weker eksternal, (8) def.=defrost, (9) Pod = narik mudhun |
0 | 9 | 0 | R/W | * | * | * | * | |
o62¹) | Prasetel cepet paramèter utama 0 = Ora digunakake 1 = MT, Defrost alami, mandheg ing wektu 2 = MT, El defrost, mandheg ing wektu 3= MT, El defrost, mandheg ing suhu. 4 = LT, El defrost mandeg ing suhu. 5 = Kamar, MT, El defrost, mandheg ing wektu 6 = Kamar, MT, El defrost, mandheg ing suhu. 7 = Kamar, LT, El defrost, mandheg ing suhu. |
0 | 7 | 0 | RIW | * | * | * | ||
o03¹) | Alamat jaringan | 0 | 247 | 0 | R/W | * | * | * | * | |
r– | Thermostat | |||||||||
r00 | Setpoint suhu | r03 | r02 | 2.0 | °C | R/W | * | * | * | * |
r01 | Diferensial | 0.1 | 20.0 | 2.0 | K | R/W | * | * | * | * |
r02 | Maks. watesan setelan setpoint | r03 | 105.0 | 50.0 | °C | R/W | * | * | * | * |
r03 | Min. watesan setelan setpoint | –40.0 | r02 | –35.0 | °C | R/W | * | * | * | * |
r04 | Pangaturan maca suhu tampilan | –10.0 | 10.0 | 0.0 | K | R/W | * | * | * | * |
r05 | Unit suhu rC / °F) | 0/C | 1/F | 0/C | R/W | * | * | * | * | |
r09 | Koreksi sinyal saka sensor Sair | –20.0 | 20.0 | 0.0 | °C | R/W | * | * | * | * |
r12 | Saklar utama (-1 = layanan / 0 = OFF / 1 = 0N) | -1 | 1 | 0 | R/W | * | * | * | * | |
r13 | Pamindahan referensi sajrone operasi wengi | –50.0 | 50.0 | 0.0 | K | R/W | * | * | * | |
r40 | Pamindahan referensi termostat | –50.0 | 20.0 | 0.0 | K | R/W | * | * | * | * |
r96 | Pull-mudhun durasi | 0 | 960 | 0 | min | R/W | * | * | * | |
r97 | Pull-mudhun suhu watesan | –40.0 | 105.0 | 0.0 | °C | R/W | * | * | * | |
A- | Setelan weker | |||||||||
A03 | Tundha kanggo weker suhu (singkat) | 0 | 240 | 30 | min | R/W | * | * | * | * |
Al2 | Tundha kanggo weker suhu nalika mundur (dawa) | 0 | 240 | 60 | min | R/W | * | * | * | * |
A13 | watesan weker dhuwur | –40.0 | 105.0 | 8.0 | °C | R/W | * | * | * | * |
A14 | watesan weker kurang | –40.0 | 105.0 | –30.0 | °C | R/W | * | * | * | * |
A27 | Weker tundha Dll | 0 | 240 | 30 | min | R/W | * | * | * | * |
A28 | Tundha weker DI2 | 0 | 240 | 30 | min | R/W | * | * | * | * |
A37 | Watesan weker kanggo weker suhu kondensor | 0.0 | 200.0 | 80.0 | °C | R/W | * | * | * | |
A54 | Watesan kanggo weker blok kondensor lan komp. mandeg | 0.0 | 200.0 | 85.0 | °C | R/W | * | * | * | |
A72 | Voltage pangayoman ngaktifake | 0/Ora | 1/Ya | 0/Ora | R/W | * | * | * | ||
A73 | Minimal cut-in voltage | 0 | 270 | 0 | Volt | R/W | * | * | * | |
A74 | Minimal cut-out voltage | 0 | 270 | 0 | Volt | R/W | * | * | * | |
A75 | Maksimum cut-in voltage | 0 | 270 | 270 | Volt | R/W | * | * | * | |
d— | defrost | |||||||||
d01 | Metode defrost (0) non = Ora ana, (1) ora = Alam, (2) E1 = Listrik, (3) gas = Gas panas |
0 | 3 | 2 | R/W | * | * | * | ||
d02 | Suhu mandeg defrost | 0.0 | 50.0 | 6.0 | °C | R/W | * | * | * | |
d03 | Interval antarane defrost diwiwiti | 0 | 240 | 8 | jam | R/W | * | * | * | |
d04 | Maks. durasi defrost | 0 | 480 | 30 | min | R/W | * | * | * | |
d05 | offset jeruk kanggo wiwitan defrost pisanan ing wiwitan | 0 | 240 | 0 | min | R/W | * | * | * | |
d06 | Tetes wektu | 0 | 60 | 0 | min | R/W | * | * | * | |
d07 | Tundha kanggo wiwitan penggemar sawise defrost | 0 | 60 | 0 | min | R/W | * | * | * | |
d08 | Suhu wiwitan kipas | -40.0 | 50.0 | -5.0 | °C | R/W | * | * | * | |
d09 | Operasi kipas nalika defrost | 0/Pateni | 1 / Ing | 1 / Ing | R/W | * | * | * | ||
d10" | Sensor defrost (0=waktu, 1=Sair, 2=55) | 0 | 2 | 0 | R/W | * | * | * | ||
d18 | Maks. komp. runtime antarane rong defrosts | 0 | 96 | 0 | jam | R/W | * | * | * | |
d19 | Defrost on demand - 55 suhu ngidini variasi sajrone frost build-up. Ing pabrik tengah pilih 20 K (=mati) |
0.0 | 20.0 | 20.0 | K | R/W | * | * | * | |
d30 | Tundha defrost sawise ditarik mudhun (0 = OFF) | 0 | 960 | 0 | min | R/W | * | * | * | |
F— | Penggemar | |||||||||
F1 | Fan ing mandeg kompresor (0) FFC = Follow comp., (1) Foo = ON, (2) FPL = Fan pulsing |
0 | 2 | 1 | R/W | * | * | * | ||
F4 | Suhu mandeg kipas (55) | -40.0 | 50.0 | 50.0 | °C | R/W | * | * | * | |
F7 | Fan pulsing ON siklus | 0 | 180 | 2 | min | R/W | * | * | ||
F8 | Siklus OFF pulsing kipas | 0 | 180 | 2 | min | R/W | * | * | * | |
c— | Kompresor | |||||||||
c01 | Min. ON-wektu | 0 | 30 | 1 | min | R/W | * | * | * | |
c02 | Min. OFF-wektu | 0 | 30 | 2 | min | R/W | * | * | * | |
c04 | Kompresor OFF tundha nalika lawang mbukak | 0 | 900 | 0 | sek | R/W | * | * | * | |
c70 | Zero crossing pilihan | 0/Ora | 1/Ya | 1/Ya | R/W | * | * | * | ||
o— | macem-macem | |||||||||
o01 | Tundha output nalika wiwitan | 0 | 600 | 10 | sek | R/W | * | * | * | * |
o2" | konfigurasi DI1 (0) OFF = ora digunakake (1) Sdc = status, (2) doo = fungsi lawang, (3) doA = weker lawang, (4) SCH = switch utama (5) nig=mode awan/wengi, (6) rFd=pamindahan referensi, (7) EAL=weker eksternal, (8) dEF=clefrost, (9) Pud = narik mudhun, (10) Sc = sensor kondensor |
0 | 10 | 0 | R/W | * | * | * | * | |
o3" | Alamat jaringan | 0 | 247 | 0 | R/W | * | * | * | * | |
5 | Kode akses | 0 | 999 | 0 | R/W | * | * | * | * | |
006″ | Pilihan jinis sensor (0) n5 = NTC 5k, (1) n10 = NTC 10k, (2)Pt = Pt1000, (3) Ptc = PTC 1000 |
0 | 3 | 2 | R/W | * | * | * | * | |
o15 | Résolusi tampilan (0) 0.1, (1)0.5, (2)1.0 |
0 | 2 | 0 | R/W | * | * | * | * | |
o16 | Maks. jeruk siaga sawise defrost terkoordinasi | 0 | 360 | 20 | min | R/W | * | * | * | |
o37. | Dl? konfigurasi (0) saka = ora digunakake (1) Karung = status, (2) doo = fungsi lawang, (3) do = weker lawang, (4) SCH = switch utama, (5) cedhak=mode awan/wengi, (6) rd=ref Terence pamindahan, (7) EAL=weker eksternal, (8) def.=def ran, (9) Pod = narik aku mudhun |
0 | 9 | 0 | R/W | * | * | * | * | |
o38 | Konfigurasi fungsi cahya (0) on=tansah on, (1) Dan=dina/wengi (2) doo = adhedhasar tumindak lawang, (3) jaring = Jaringan |
0 | 3 | 1 | R/W | * | * | * | ||
o39 | Kontrol cahya liwat jaringan (mung yen o38=3(.NET)) | 0/Pateni | 1 / Ing | 1 / Ing | R/W | * | * | * | ||
061″ | Pilihan saka mode aplikasi (1) API: Cmp/Def/Fan/Light (2) AP2: Cmp/Def/Fan/A 6 rim (3) AP3: Cmp/Al/Fan/Lampu (4) AP4: Panas / Weker / Cahya |
1 | 4 | 1 | R/W | * | * | * | * | |
o62 ing | Prasetel cepet paramèter utama 0= Ora digunakake 1= MT, Defrost alami, mandheg ing wektu 2 = MT, El defrost, mandheg ing wektu 3= MT, El defrost, mandheg ing suhu. 4 = LT, El defrost mandeg ing suhu 5 = Kamar, MT, El defrost, mandheg ing wektu 6 = Kamar, MT, El defrost, mandheg ing suhu. 7 = Kamar, LT, El defrost, mandheg ing suhu. |
0 | 7 | 0 | R/W | * | * | * | ||
67 | Ganti setelan pabrik pengontrol karo setelan saiki | 0/Ora | 1/Ya | 0/Ora | R/W | * | * | * | * | |
91 | Tampilan ing defrost (0) Udara=Suhu Sari / (1) Fret=suhu beku/ (2) -drvd ditampilake |
0 | 2 | 2 | R/W | * | * | * | ||
P— | Polaritas | |||||||||
P75 | Relay weker kuwalik (1) = Tindakan relay kuwalik | 0 | 1 | 0 | R/W | * | * | * | ||
P76 | Kunci keyboard ngaktifake | 0/Ora | 1/Ya | 0/Ora | R/W | * | * | * | * | |
u— | Layanan | |||||||||
u00 | Negara kontrol 50: Normal, 51: Wart sawise defrosting. 52: Timer Min ON, 53: Timer Min. OFF, 54: Sering netes 510: r12 Saklar utama disetel OFF, 511: Cut-out termostat 514: Defrosting, $15: Tundha kipas, 517: Lawang mbukak, 520: Pendinginan darurat, 525 : Kontrol manual, 530: Siklus Pulldown, 532: Tundha daya, S33: Pemanasan | 0 | 33 | 0 | R | * | * | * | * | |
u01 | Suhu Udara Sari | -100.0 | 200.0 | 0.0 | °C | R | * | * | * | * |
u09 | S5 suhu Evaporator | -100.0 | 200.0 | 0.0 | °C | R | * | * | * | * |
u10 | Status input DI1 | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | * | |
u13 | Kondisi wengi | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | * | |
u37 | Status input DI2 | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | * | |
u28 | Referensi termostat nyata | -100.0 | 200.0 | 0.0 | R | * | * | * | * | |
u58 | Kompresor / Katup solenoid garis Cairan | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | ||
u59 | Relay kipas | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | ||
u60 | Relay defrost | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | |||
u62 | Relay weker | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | ||
u63 | Relay cahya | 0/Pateni | 1 / Ing | 0/Pateni | R | * | * | * | ||
LSO | Pembacaan versi firmware | R | * | * | * | * | ||||
u82 | Kode pengontrol no. | R | * | * | * | * | ||||
u84 | relay panas | 0/Pateni | 1 / Ing | 0/Pateni | R | * | ||||
U09 | Suhu Kondensor Sc | -100.0 | 200.0 | 0.0 | R | * | * | * |
1) Parameter mung bisa diganti nalika parameter r12 Ngalih utama ing posisi OFF.
Kode weker
Ing kahanan weker tampilan bakal sulih antarane maca suhu udhara nyata lan maca kode weker weker aktif.
Kode | Weker | Katrangan | Weker jaringan |
E29 | Salah sensor sari | Sensor suhu udara cacat utawa sambungan listrik ilang | - Salah Sari |
E27 | Def sensor kesalahan | Sensor Evaporator S5 cacat utawa sambungan listrik ilang | - Kesalahan S5 |
E30 | kesalahan sensor SC | Sensor Sac Condenser cacat utawa sambungan listrik ilang | - Kesalahan Sac |
A01 | Alarm suhu dhuwur | Suhu udara ing lemari dhuwur banget | - Weker dhuwur |
A02 | Weker suhu rendah | Suhu udhara ing lemari sithik banget | - Kurang t. Weker |
A99 | Alarm High Volt | Pasokan voltage dhuwur banget (proteksi kompresor) | - Dhuwur Voltage |
AA1 | Weker Low Volt | Pasokan voltage kurang banget (proteksi kompresor) | - Low Voltage |
A61 | Alarm kondensor | Suhu kondensor dhuwur banget - mriksa aliran udara | - Weker Cond |
A80 | Cond. weker pamblokiran | Suhu kondensor dhuwur banget - Reset manual weker dibutuhake | - Cond Diblokir |
A04 | Weker lawang | Lawang wis dibukak suwe banget | - Weker lawang |
A15 | Weker DI | Weker eksternal saka input DI | - Weker DI |
A45 | Weker siyaga | Kontrol wis mandheg dening "r12 Main switch" | - Mode siyaga |
1) Weker pemblokiran kondensor bisa direset kanthi nyetel r12 Main switch OFF lan ON maneh utawa kanthi mateni controller.
Danfoss A / S
Solusi Iklim « danfoss.com « +45 7488 2222
Informasi apa wae, kalebu, nanging ora winates ing informasi babagan pilihan produk, aplikasi utawa panggunaan, desain produk, bobot, dimensi, kapasitas utawa data teknis liyane ing manual produk, katrangan katalog, pariwara, lsp. , lisan, elektronik, online utawa liwat download, bakal dianggep informatif, lan mung naleni yen lan kanggo ombone, referensi eksplisit digawe ing kutipan utawa konfirmasi pesenan. Danfoss ora bisa nampa tanggung jawab kanggo kesalahan ing katalog, brosur, video lan materi liyane.
Danfoss duwe hak kanggo ngganti produke tanpa kabar. Iki uga ditrapake kanggo produk sing dipesen nanging ora dikirim yen owah-owahan kasebut bisa ditindakake tanpa owah-owahan wujud, pas utawa fungsi produk kasebut.
Kabeh merek dagang ing materi iki minangka properti saka Danfoss A/S utawa perusahaan grup Danfoss. Danfoss lan logo Danfoss minangka merek dagang Danfoss A/S. Kabeh hak dilindhungi undhang-undhang.
AN432635050585en-000201
© Danfoss | Solusi Iklim | 2023.05
Dokumen / Sumber Daya
![]() |
Danfoss EKC 223 Case Controller [pdf] Pandhuan Instalasi EKC 223, 084B4053, 084B4054, Pengontrol Kasus, Pengontrol Kasus EKC 223 |
![]() |
Danfoss EKC 223 Case Controller [pdf] Pandhuan Instalasi EKC 223 Case Controller, EKC 223, Case Controller, Controller |