Guide Instalasi
Pengontrol kasus
Tipe EKC 223Danfoss EKC 223 Case Controller - barcode 2

Identifikasi

Danfoss EKC 224 Case Controller - Identifikasi

Aplikasi

Danfoss EKC 224 Case Controller - Aplikasi

ukuran

Danfoss EKC 224 Case Controller - Dimensi

Pemasangan

Danfoss EKC 224 Case Controller - Mounting

Wiring diagram

Aplikasi  Wiring diagram
1 Danfoss EKC 224 Case Controller - Wiring diagram 1
2 Danfoss EKC 224 Case Controller - Wiring diagram 2
3 Danfoss EKC 224 Case Controller - Wiring diagram 3
4 Danfoss EKC 224 Case Controller - Wiring diagram 4

Cathetan: Konektor daya: ukuran kawat = 0.5 – 1.5 mm 2, maks. torsi tightening = 0.4 Nm Low voltagkonektor sinyal e: ukuran kabel = 0.15 – 1.5 mm 2, max. torsi tightening = 0.2 Nm 2L lan 3L kudu disambungake menyang phase padha.

Komunikasi data

Instalasi Wiring
Danfoss EKC 224 Case Controller - Komunikasi data 1

Kontroler EKC 22x bisa digabungake menyang jaringan Modbus liwat adaptor RS-485 (EKA 206) nggunakake kabel antarmuka (080N0327). Kanggo rincian instalasi, waca pandhuan instalasi kanggo adaptor EKA 206 – RS485.

Danfoss EKC 224 Case Controller - Komunikasi data 2

data teknis

Fitur Katrangan
Tujuan kontrol Kontrol sensing suhu operasi sing cocog kanggo digabungake menyang aplikasi AC lan kulkas komersial
Konstruksi kontrol Kontrol tergabung
sumber daya 084B4055 – 115 V AC / 084B4056 – 230 V AC 50/60 Hz, galvanik isolasi low voltage sumber daya diatur
daya dirating Kurang saka 0.7 W
Input Input sensor, Input digital, Tombol Pemrograman Disambungake menyang energi winates SELV <15 W
Jinis sensor sing diidini NTC 5000 Ohm ing 25 °C, (Nilai Beta=3980 ing 25/100 °C - EKS 211)
NTC 10000 Ohm ing 25 °C, (Nilai Beta=3435 ing 25/85 °C - EKS 221)
PTC 990 Ohm ing 25 °C, (EKS 111)
Pt1000, (AKS 11, AKS 12, AKS 21)
Akurasi Rentang pangukuran: -40 – 105 °C (-40 – 221 °F)
Akurasi Controller:
± 1 K ing ngisor -35 °C, ± 0.5 K antarane -35 – 25 °C,
± 1 K ing ndhuwur 25 °C
Jinis tumindak 1B (relay)
Output DO1 - Relay 1:
16 A, 16 (16) A, EN 60730-1
10 FLA / 60 LRA ing 230 V, UL60730-1
16 FLA / 72 LRA ing 115 V, UL60730-1
DO2 - Relay 2:
8 A, 2 FLA / 12 LRA, UL60730-1
8 A, 2 (2 A), EN60730-1
DO3 - Relay 3:
3 A, 2 FLA / 12 LRA, UL60730-1
3 A, 2 (2 A), EN60730-1
DO4 – Relay 4: 2 A
Tampilan Tampilan LED, 3 digit, titik desimal lan lambang multi-fungsi, skala °C + °F
kahanan operasi -10 – 55 °C (14 – 131 °F), 90% Rh
Kondisi panyimpenan -40 – 70 °C (-40 – +158 °F), 90% Rh
pangayoman Ngarep: IP65 (gasket terpadu)
Mburi: IP00
lingkungan Tingkat polusi II, non-kondensasi
Overvoltage kategori II – 230 V versi sumber – (ENEC, UL dikenali)
III – 115 V versi sumber – (UL diakoni)
Resistance kanggo panas lan geni Kategori D (UL94-V0)
Suhu kanggo statement tes tekanan bola Miturut Annex G (EN 60730-1)
Kategori EMC Kategori I
Persetujuan Pangenalan UL (AS & Kanada) (UL 60730-1)
CE (LVD & EMC Directive)
EAC (HANTU)
UKCA
UA
CMIM
ROHS 2.0
Persetujuan Hazloc kanggo refrigeran sing gampang kobong (R290/R600a).
R290/R600a aplikasi pungkasan nggunakake makaryakke sesuai karo syarat IEC60079-15.

Operasi tampilan

Tombol ing ngarep tampilan bisa dioperasikake kanthi mencet cendhak lan dawa (3s).

Danfoss EKC 224 Case Controller - Operasi tampilan

A Indikasi status: Lampu LED ing mode ECO/Night, pendinginan, defrost lan kipas mlaku.
B Indikasi weker: Lambang weker kelip-kelip yen ana weker.
C Pencet cendhak = Navigasi bali
Pencet dawa = Miwiti siklus pulldown. Tampilan bakal nuduhake
"Pod" kanggo konfirmasi wiwitan.
D Pencet cendhak = Navigasi munggah
Tekan dawa = Ngalih pengontrol ON/OFF (nyetel r12 Saklar utama ing posisi ON/OFF)
E Pencet cendhak = Navigasi mudhun
Pencet dawa = Mulai siklus defrosting. Tampilan bakal nuduhake kode "-d-" kanggo konfirmasi wiwitan.
F Pencet cendhak = Ganti set point
Pencet dawa = Pindhah menyang menu parameter

Pengontrol Case Danfoss EKC 224 - Operasi tampilan 2

Reset pabrik

Kontroler bisa diset bali menyang setelan pabrik kanthi nggunakake prosedur ing ngisor iki:

  1. Kontrol daya OFF
  2. Terus tombol panah "∧" lan mudhun "∨" ditekan nalika nyambungake maneh sumber voltage
  3. Nalika kode "Pasuryan" ditampilake ing tampilan, pilih "ya"

Cathetan: Setelan pabrik OEM bakal dadi setelan pabrik Danfoss utawa setelan pabrik sing ditetepake pangguna yen wis digawe. Pangguna bisa nyimpen setelan kasebut minangka setelan pabrik OEM liwat parameter o67.

Kode tampilan

Kode tampilan  Katrangan
-d- Siklus defrost lagi ditindakake
Pod Siklus pulldown suhu wis diwiwiti
Kesalahan Suhu ora bisa ditampilake amarga kesalahan sensor
Dituduhake ing ndhuwur tampilan: Nilai parameter wis tekan maksimal. watesan
Dituduhake ing ngisor tampilan: Nilai parameter wis tekan min. watesan
Kunci Papan tombol tampilan dikunci
Null Papan tombol tampilan wis ora dikunci
PS Kode akses dibutuhake kanggo ngetik menu parameter
Ax / Ext Weker utawa kode kesalahan sumunar kanthi suhu normal. wacan
OFF Kontrol mandheg nalika r12 ngalih utama disetel OFF
On Kontrol diwiwiti nalika switch utama r12 disetel ON (kode ditampilake ing 3 detik)
Pasuryan Kontroler direset menyang setelan pabrik

Pandhu arah

Menu parameter diakses kanthi mencet tombol "SET" kanggo 3 detik. Yen kode proteksi akses "o05" wis ditetepake tampilan bakal njaluk kode akses kanthi nuduhake kode "PS". Sawise kode akses wis diwenehake dening pangguna, dhaptar parameter bakal diakses.

Danfoss EKC 224 Case Controller - Navigasi

Entuk wiwitan sing apik

Kanthi prosedur ing ngisor iki, sampeyan bisa miwiti regulasi kanthi cepet:

  1. Pencet tombol "SET" kanggo 3 detik lan ngakses menu parameter (tampilan bakal nuduhake "ing")
  2. Pencet tombol mudhun "∨" kanggo pindhah menyang menu "tcfg" (tampilan bakal nuduhake "tcfg")
  3. Pencet tombol tengen / ">" kanggo mbukak menu konfigurasi (tampilan bakal nuduhake r12)
  4. Bukak parameter "r12 Main switch" lan mungkasi kontrol kanthi nyetel OFF (Pencet SET)
  5. Bukak "mode aplikasi o61" lan pilih mode aplikasi sing dibutuhake (Pencet SET)
  6. Bukak "o06 Sensor type" lan pilih jinis sensor suhu sing digunakake (n5 = NTC 5 K, n10 = NTC 10 K, Pct. = PTC, Pt1 = Pt1000) - (Pencet "SET").
  7. Bukak "O02 DI1 Konfigurasi" lan pilih fungsi sing ana gandhengane karo input digital 1 (Mangga deleng dhaptar parameter) - (Pencet "SET").
  8. Bukak "O37 DI2 Konfigurasi" lan pilih fungsi sing ana gandhengane karo input digital 2 (Mangga deleng dhaptar parameter) - (Pencet "SET").
  9. Bukak parameter "o62 Quick setting" lan pilih prasetel sing cocog karo aplikasi sing digunakake (waca tabel prasetel ing ngisor iki) - (Pencet "SET").
  10. Bukak "alamat Jaringan o03" lan setel alamat Modbus yen dibutuhake.
  11. Navigasi bali menyang parameter "r12 Main switch" lan nyetel ing posisi "ON" kanggo miwiti kontrol.
  12. Bukak kabeh dhaptar parameter lan ganti setelan pabrik yen perlu.

Pamilihan setelan cepet

Setelan cepet 1 2 3 4 5 6 7
Kabinet MT
Natural def.
Mungkasi ing wektu
Kabinet MT
El. def.
Mungkasi ing wektu
Kabinet MT
El. def.
Mungkasi ing suhu
Kabinet LT
El. def.
Mungkasi ing suhu
Ruang MT
El. def.
Mungkasi ing wektu
Ruang MT
El. def.
Mungkasi ing suhu
Kamar LT
El. def.
Mungkasi ing suhu
r00 Cut-out 4 °C 2 °C 2 °C -24 °C 6 °C 3 °C -22 °C
r02 Max Cut-out 6 °C 4 °C 4 °C -22 °C 8 °C 5 °C -20 °C
r03 Min Cut-out 2 °C 0 °C 0 °C -26 °C 4 °C 1 °C -24 °C
A13 Highly Air 10 °C 8 °C 8 °C -15 °C 10 °C 8 °C -15 °C
Al 4 Lowly Air -5 °C -5 °C -5 °C -30 °C 0 °C 0 °C -30 °C
d01 Def. Metode Alamiah listrik listrik listrik listrik listrik listrik
d03 Def.lnterval 6 jam 6 jam 6 jam 12 jam 8 jam 8 jam 12 jam
d10 DefStopSens. Wektu Wektu S5 Sensor Kab 55 Sensor Wektu S5 Sensor Kab S5 Sensor Kab
o02 DI1 Konfigurasi. Lawang fct. Lawang fct. Lawang fct.

Tombol pemrograman

Pengontrol pemrograman dengan Mass Programming Key (EKA 201)

  1. Power munggah controller. Priksa manawa pengontrol disambungake menyang listrik.
  2. Sambungake EKA 201 menyang controller nggunakake kabel antarmuka controller pamilike.
  3. EKA 201 bakal miwiti proses pemrograman kanthi otomatis.

Danfoss EKC 224 Case Controller - tombol Programming

Daftar parameter

Kode Manual teks singkat Min. Maks. 2 Unit R/W EKC 224 Appl.
1 2 3 4
CFg Konfigurasi
r12 Saklar utama (-1 = layanan / 0 = OFF / 1 = 0N) -1 1 0 R/W * * * *
o61¹) Pilihan saka mode aplikasi
(1) API: Cmp/Def/Fan/Light
(2) AP2: Cmp/Def/Fan/Weker
(3)AP3: Cmp/ Al/F an/Light
(4) AP4: Panas/Weker/Lampu
1 4 R/W * * * *
o06¹) Pilihan jinis sensor
(0) n5= NTC 5k, (1) n10 = NTC 10k, (2)Pt = Pt1003, (3) Pt. = PTC 1000
0 3 2 R/W * * * *
o02¹) Konfigurasi Dell
(0) saka = ora digunakake (1) SD = status, (2) fungsi doo-lawang, (3) do = weker lawang, (4) SCH = switch utama,
(5) wengi = mode awan / wengi, (6) rd = pamindahan referensi (7) EAL = weker eksternal, (8) def. = defrost,
(9) Pod = narik I mudhun, (10) Sc = sensor kondensor
0 10 0 R/W * * * *
037¹) konfigurasi DI2
(0) saka = ora digunakake (1) SD = status, (2) fungsi doo-lawang, (3) do = weker lawang, (4) SCH = switch utama,
(5) bengi=mode awan/wengi, (6) sled=pamindahan refrefence (7) EAL=weker eksternal, (8) def.=defrost,
(9) Pod = narik mudhun
0 9 0 R/W * * * *
o62¹) Prasetel cepet paramèter utama
0 = Ora digunakake
1 = MT, Defrost alami, mandheg ing wektu
2 = MT, El defrost, mandheg ing wektu 3= MT, El defrost, mandheg ing suhu.
4 = LT, El defrost mandeg ing suhu.
5 = Kamar, MT, El defrost, mandheg ing wektu 6 = Kamar, MT, El defrost, mandheg ing suhu.
7 = Kamar, LT, El defrost, mandheg ing suhu.
0 7 0 RIW * * *
o03¹) Alamat jaringan 0 247 0 R/W * * * *
r– Thermostat
r00 Setpoint suhu r03 r02 2.0 °C R/W * * * *
r01 Diferensial 0.1 20.0 2.0 K R/W * * * *
r02 Maks. watesan setelan setpoint r03 105.0 50.0 °C R/W * * * *
r03 Min. watesan setelan setpoint –40.0 r02 –35.0 °C R/W * * * *
r04 Pangaturan maca suhu tampilan –10.0 10.0 0.0 K R/W * * * *
r05 Unit suhu rC / °F) 0/C 1/F 0/C R/W * * * *
r09 Koreksi sinyal saka sensor Sair –20.0 20.0 0.0 °C R/W * * * *
r12 Saklar utama (-1 = layanan / 0 = OFF / 1 = 0N) -1 1 0 R/W * * * *
r13 Pamindahan referensi sajrone operasi wengi –50.0 50.0 0.0 K R/W * * *
r40 Pamindahan referensi termostat –50.0 20.0 0.0 K R/W * * * *
r96 Pull-mudhun durasi 0 960 0 min R/W * * *
r97 Pull-mudhun suhu watesan –40.0 105.0 0.0 °C R/W * * *
A- Setelan weker
A03 Tundha kanggo weker suhu (singkat) 0 240 30 min R/W * * * *
Al2 Tundha kanggo weker suhu nalika mundur (dawa) 0 240 60 min R/W * * * *
A13 watesan weker dhuwur –40.0 105.0 8.0 °C R/W * * * *
A14 watesan weker kurang –40.0 105.0 –30.0 °C R/W * * * *
A27 Weker tundha Dll 0 240 30 min R/W * * * *
A28 Tundha weker DI2 0 240 30 min R/W * * * *
A37 Watesan weker kanggo weker suhu kondensor 0.0 200.0 80.0 °C R/W * * *
A54 Watesan kanggo weker blok kondensor lan komp. mandeg 0.0 200.0 85.0 °C R/W * * *
A72 Voltage pangayoman ngaktifake 0/Ora 1/Ya 0/Ora R/W * * *
A73 Minimal cut-in voltage 0 270 0 Volt R/W * * *
A74 Minimal cut-out voltage 0 270 0 Volt R/W * * *
A75 Maksimum cut-in voltage 0 270 270 Volt R/W * * *
d— defrost
d01 Metode defrost
(0) non = Ora ana, (1) ora = Alam, (2) E1 = Listrik, (3) gas = Gas panas
0 3 2 R/W * * *
d02 Suhu mandeg defrost 0.0 50.0 6.0 °C R/W * * *
d03 Interval antarane defrost diwiwiti 0 240 8 jam R/W * * *
d04 Maks. durasi defrost 0 480 30 min R/W * * *
d05 offset jeruk kanggo wiwitan defrost pisanan ing wiwitan 0 240 0 min R/W * * *
d06 Tetes wektu 0 60 0 min R/W * * *
d07 Tundha kanggo wiwitan penggemar sawise defrost 0 60 0 min R/W * * *
d08 Suhu wiwitan kipas -40.0 50.0 -5.0 °C R/W * * *
d09 Operasi kipas nalika defrost 0/Pateni 1 / Ing 1 / Ing R/W * * *
d10" Sensor defrost (0=waktu, 1=Sair, 2=55) 0 2 0 R/W * * *
d18 Maks. komp. runtime antarane rong defrosts 0 96 0 jam R/W * * *
d19 Defrost on demand - 55 suhu ngidini variasi sajrone frost build-up.
Ing pabrik tengah pilih 20 K (=mati)
0.0 20.0 20.0 K R/W * * *
d30 Tundha defrost sawise ditarik mudhun (0 = OFF) 0 960 0 min R/W * * *
F— Penggemar
F1 Fan ing mandeg kompresor
(0) FFC = Follow comp., (1) Foo = ON, (2) FPL = Fan pulsing
0 2 1 R/W * * *
F4 Suhu mandeg kipas (55) -40.0 50.0 50.0 °C R/W * * *
F7 Fan pulsing ON siklus 0 180 2 min R/W * *
F8 Siklus OFF pulsing kipas 0 180 2 min R/W * * *
c— Kompresor
c01 Min. ON-wektu 0 30 1 min R/W * * *
c02 Min. OFF-wektu 0 30 2 min R/W * * *
c04 Kompresor OFF tundha nalika lawang mbukak 0 900 0 sek R/W * * *
c70 Zero crossing pilihan 0/Ora 1/Ya 1/Ya R/W * * *
o— macem-macem
o01 Tundha output nalika wiwitan 0 600 10 sek R/W * * * *
o2" konfigurasi DI1
(0) OFF = ora digunakake (1) Sdc = status, (2) doo = fungsi lawang, (3) doA = weker lawang, (4) SCH = switch utama
(5) nig=mode awan/wengi, (6) rFd=pamindahan referensi, (7) EAL=weker eksternal, (8) dEF=clefrost,
(9) Pud = narik mudhun, (10) Sc = sensor kondensor
0 10 0 R/W * * * *
o3" Alamat jaringan 0 247 0 R/W * * * *
5 Kode akses 0 999 0 R/W * * * *
006″ Pilihan jinis sensor
(0) n5 = NTC 5k, (1) n10 = NTC 10k, (2)Pt = Pt1000, (3) Ptc = PTC 1000
0 3 2 R/W * * * *
o15 Résolusi tampilan
(0) 0.1, (1)0.5, (2)1.0
0 2 0 R/W * * * *
o16 Maks. jeruk siaga sawise defrost terkoordinasi 0 360 20 min R/W * * *
o37. Dl? konfigurasi
(0) saka = ora digunakake (1) Karung = status, (2) doo = fungsi lawang, (3) do = weker lawang, (4) SCH = switch utama,
(5) cedhak=mode awan/wengi, (6) rd=ref Terence pamindahan, (7) EAL=weker eksternal, (8) def.=def ran,
(9) Pod = narik aku mudhun
0 9 0 R/W * * * *
o38 Konfigurasi fungsi cahya
(0) on=tansah on, (1) Dan=dina/wengi
(2) doo = adhedhasar tumindak lawang, (3) jaring = Jaringan
0 3 1 R/W * * *
o39 Kontrol cahya liwat jaringan (mung yen o38=3(.NET)) 0/Pateni 1 / Ing 1 / Ing R/W * * *
061″ Pilihan saka mode aplikasi
(1) API: Cmp/Def/Fan/Light
(2) AP2: Cmp/Def/Fan/A 6 rim
(3) AP3: Cmp/Al/Fan/Lampu
(4) AP4: Panas / Weker / Cahya
1 4 1 R/W * * * *
o62 ing Prasetel cepet paramèter utama 0= Ora digunakake
1= MT, Defrost alami, mandheg ing wektu 2 = MT, El defrost, mandheg ing wektu 3= MT, El defrost, mandheg ing suhu. 4 = LT, El defrost mandeg ing suhu
5 = Kamar, MT, El defrost, mandheg ing wektu 6 = Kamar, MT, El defrost, mandheg ing suhu. 7 = Kamar, LT, El defrost, mandheg ing suhu.
0 7 0 R/W * * *
67 Ganti setelan pabrik pengontrol karo setelan saiki 0/Ora 1/Ya 0/Ora R/W * * * *
91 Tampilan ing defrost
(0) Udara=Suhu Sari / (1) Fret=suhu beku/ (2) -drvd ditampilake
0 2 2 R/W * * *
P— Polaritas
P75 Relay weker kuwalik (1) = Tindakan relay kuwalik 0 1 0 R/W * * *
P76 Kunci keyboard ngaktifake 0/Ora 1/Ya 0/Ora R/W * * * *
u— Layanan
u00 Negara kontrol 50: Normal, 51: Wart sawise defrosting. 52: Timer Min ON, 53: Timer Min. OFF, 54: Sering netes 510: r12 Saklar utama disetel OFF, 511: Cut-out termostat 514: Defrosting, $15: Tundha kipas, 517: Lawang mbukak, 520: Pendinginan darurat, 525 : Kontrol manual, 530: Siklus Pulldown, 532: Tundha daya, S33: Pemanasan 0 33 0 R * * * *
u01 Suhu Udara Sari -100.0 200.0 0.0 °C R  * * * *
u09 S5 suhu Evaporator -100.0 200.0 0.0 °C R * * * *
u10 Status input DI1 0/Pateni 1 / Ing 0/Pateni R * * * *
u13 Kondisi wengi 0/Pateni 1 / Ing 0/Pateni R * * * *
u37 Status input DI2 0/Pateni 1 / Ing 0/Pateni R * * * *
u28 Referensi termostat nyata -100.0 200.0 0.0 R * * * *
u58 Kompresor / Katup solenoid garis Cairan 0/Pateni 1 / Ing 0/Pateni R * * *
u59 Relay kipas 0/Pateni 1 / Ing 0/Pateni R * * *
u60 Relay defrost 0/Pateni 1 / Ing 0/Pateni R * *
u62 Relay weker 0/Pateni 1 / Ing 0/Pateni R * * *
u63 Relay cahya 0/Pateni 1 / Ing 0/Pateni R * * *
LSO Pembacaan versi firmware R * * * *
u82 Kode pengontrol no. R * * * *
u84 relay panas 0/Pateni 1 / Ing 0/Pateni R *
U09 Suhu Kondensor Sc -100.0 200.0 0.0 R * * *

1) Parameter mung bisa diganti nalika parameter r12 Ngalih utama ing posisi OFF.

Kode weker

Ing kahanan weker tampilan bakal sulih antarane maca suhu udhara nyata lan maca kode weker weker aktif.

Kode Weker Katrangan Weker jaringan
E29 Salah sensor sari Sensor suhu udara cacat utawa sambungan listrik ilang - Salah Sari
E27 Def sensor kesalahan Sensor Evaporator S5 cacat utawa sambungan listrik ilang - Kesalahan S5
E30 kesalahan sensor SC Sensor Sac Condenser cacat utawa sambungan listrik ilang - Kesalahan Sac
A01 Alarm suhu dhuwur Suhu udara ing lemari dhuwur banget - Weker dhuwur
A02 Weker suhu rendah Suhu udhara ing lemari sithik banget - Kurang t. Weker
A99 Alarm High Volt Pasokan voltage dhuwur banget (proteksi kompresor) - Dhuwur Voltage
AA1 Weker Low Volt Pasokan voltage kurang banget (proteksi kompresor) - Low Voltage
A61 Alarm kondensor Suhu kondensor dhuwur banget - mriksa aliran udara - Weker Cond
A80 Cond. weker pamblokiran Suhu kondensor dhuwur banget - Reset manual weker dibutuhake - Cond Diblokir
A04 Weker lawang Lawang wis dibukak suwe banget - Weker lawang
A15 Weker DI Weker eksternal saka input DI - Weker DI
A45 Weker siyaga Kontrol wis mandheg dening "r12 Main switch" - Mode siyaga

1) Weker pemblokiran kondensor bisa direset kanthi nyetel r12 Main switch OFF lan ON maneh utawa kanthi mateni controller.

Danfoss A / S
Solusi Iklim « danfoss.com « +45 7488 2222

Informasi apa wae, kalebu, nanging ora winates ing informasi babagan pilihan produk, aplikasi utawa panggunaan, desain produk, bobot, dimensi, kapasitas utawa data teknis liyane ing manual produk, katrangan katalog, pariwara, lsp. , lisan, elektronik, online utawa liwat download, bakal dianggep informatif, lan mung naleni yen lan kanggo ombone, referensi eksplisit digawe ing kutipan utawa konfirmasi pesenan. Danfoss ora bisa nampa tanggung jawab kanggo kesalahan ing katalog, brosur, video lan materi liyane.
Danfoss duwe hak kanggo ngganti produke tanpa kabar. Iki uga ditrapake kanggo produk sing dipesen nanging ora dikirim yen owah-owahan kasebut bisa ditindakake tanpa owah-owahan wujud, pas utawa fungsi produk kasebut.
Kabeh merek dagang ing materi iki minangka properti saka Danfoss A/S utawa perusahaan grup Danfoss. Danfoss lan logo Danfoss minangka merek dagang Danfoss A/S. Kabeh hak dilindhungi undhang-undhang.

AN432635050585en-000201
© Danfoss | Solusi Iklim | 2023.05

Dokumen / Sumber Daya

Danfoss EKC 223 Case Controller [pdf] Pandhuan Instalasi