EMKO-PROOP-Input-or-Output--Modul-LOGO

EMKO PROOP Input or Output Module

EMKO-PROOP-Input-or-Output--Modul-PRODUCT

Preface

Proop-I/O Module is used with the Prop device. It can also be used as a data path for any brand. This document will be helpful the user to install and connect Proop-I/O Module.

  • Before beginning the installation of this product, please read the instruction manual.
  • The contents of the document may have been updated. You can access the most updated version at www.emkoelektronik.com.tr
  • This symbol is used for safety warnings. User must pay attention to these warnings.

Environmental Conditions

Operating Temperature    : 0-50C
Maximum Humidity           : 0-90 %RH (None Condensing)
Weight                                    : 238gr
Dimension                              : 160 x 90 x 35 mm

Features

Proop-I/O modules are divided into several types according to inputs-outputs. The types are as follows.

Product Type

Proop-I/O.P.

A  

 

.

B  

 

.

C  

 

.

D  

 

.

E  

 

.

F
2 2 1 3    
Module Supply
24 Vdc/Vac (Isolation) 2  
Communication
RS-485 (Isolation) 2  
Digital Inputs
8x Digital 1  
Digital Outputs
8x 1A Transistor (+V) 3  
Analog Inputs
5x Pt-100 (-200…650°C)

5x 0/4..20mAdc 5x 0…10Vdc

5x 0…50mV

1  
2
3
4
Analog Outputs
2x 0/4…20mAdc

2x 0…10Vdc

1
2

Dimensions

 

Mounting of Module on Proop Device

1-  Insert the Prop I/O Module into the holes of the Prop device as in the picture.

2-  Check the locking parts are plugged into the Proop-I/ O Module device and pulled out.

3-  Press the Proop-I / O Module device firmly in the specified direction.

 

4-  Insert the locking parts by pushing them in.

5- The inserted image of module device should look like the one on the left.

Mounting of Module on DIN-Ray

EMKO-PROOP-Input-or-Output--Modul-FIG-5 1- Drag the Proop-I/O Module device onto the DIN-ray as shown.

2-  Check the locking parts are plugged into the Prop- I/O Module device and pulled out.

EMKO-PROOP-Input-or-Output--Modul-FIG-6 3- Insert the locking parts by pushing them in.
EMKO-PROOP-Input-or-Output--Modul-FIG-7 4- The inserted image of the module device should look like the one on the left.

Installation

  • Before beginning installation of this product, please read the instruction manual and warnings below carefully.
  • A visual inspection of this product for possible damage occured during shipment is recommended before installation. It is your responsibility to ensure that qualified mechanical and electrical technicians install this product.
  • Do not use the unit in combustible or explosive gaseous atmospheres.
  • Do not expose the unit to direct sun rays or any other heat source.
  • Do not place the unit in the neighbourhood of magnetic equipment such as transformers, motors or devices which generate interference (welding machines, etc.)
  • To reduce the effect of electrical noise on device, Low voltage line (especially sensor input cable) wiring must be separated from high current and voltage line.
  • During installation of the equipment in the panel, sharp edges on metal parts can cause cuts on the hands, please use caution.
  • Mounting of the product must be done with its own mounting clamps.
  • Do not mount the device with inappropriate clamps. Do not drop the device during installation.
  • If possible, use shielded cable. To prevent ground loops the shield should be grounded on one end only.
  • To prevent electric shock or damage to the device, do not apply power to the device until all of the wiring is completed.
  • The digital outputs and supply connections are designed to be isolated from each other.
  • Before commissioning the device, parameters must be set in accordance with desired use.
  • Incomplete or incorrect configuration can be dangerous.
  • The unit is normally supplied without a power switch, fuse, or circuit breaker. Use a power switch, fuse, and circuit breaker as required by local regulations.
  • Apply only the rated power supply voltage to the unit, to prevent equipment damage.
  • If there is danger of serious accident resulting from a failure or defect in this unit, power off the system and disconnect the device from the system.
  • Never attempt to disassemble, modify or repair this unit. Tampering with the unit may result in malfunction, electric shock, or fire.
  • Please contact us with any questions related to the safe operation of this unit.
  • This equipment must be used in the manner specified in this instruction manual.

Connections

Power Supply

EMKO-PROOP-Input-or-Output--Modul-FIG-8 Terminal
+
 

Communication Link with HMI Device

EMKO-PROOP-Input-or-Output--Modul-FIG-9 Terminal
A
B
GND

Digital Inputs

  

EMKO-PROOP-Input-or-Output--Modul-FIG-10

Terminal Comment Connection Sheme
DI8  

 

 

 

 

 

Digital Inputs

EMKO-PROOP-Input-or-Output--Modul-FIG-11
DI7
DI6
DI5
DI4
DI3
DI2
DI1
 

+/-

NPN / PNP

Selection of Digital Inputs

Digital Outputs

 

EMKO-PROOP-Input-or-Output--Modul-FIG-12

 

 

 

 

 

Terminal Comment Connection Scheme
DO1  

 

 

 

 

 

 

 

 

Digital Outputs

EMKO-PROOP-Input-or-Output--Modul-FIG-13
DO2
DO3
DO4
DO5
DO6
DO7
DO8

Analog Inputs

EMKO-PROOP-Input-or-Output--Modul-FIG-14

 

 

 

 

 

 

 

Terminal Comment Connection Scheme
AI5-  

 

Analog Input5

EMKO-PROOP-Input-or-Output--Modul-FIG-15
AI5+
AI4-  

 

Analog Input4

AI4+
AI3-  

Analog Input3

AI3+
AI2-  

 

Analog Input2

AI2+
AI1-  

 

Analog Input1

AI1+

Analog Outputs

 

EMKO-PROOP-Input-or-Output--Modul-FIG-16

 

 

Terminal Comment Connection Scheme
 

AO+

 

 

Analog Output Supply

EMKO-PROOP-Input-or-Output--Modul-FIG-17
 

AO-

 

AO1

 

 

Analog Outputs

 

AO2

Technical Features

Power Supply

Power Supply : 24VDC
Permissible Range : 20.4 – 27.6 VDC
Power Consumption : 3W

Digital Inputs

Digital Inputs : 8 Input
Nominal Input Voltage : 24 VDC
 

Input Voltage

 

:

For Logic 0 For Logic 1
< 5 VDC >10 VDC
Input Current : 6mA max.
Input Impedance : 5.9 kΩ
Response Time : ‘0’ to ‘1’ 50ms
Galvanic Isolation : 500 VAC for 1 minute

High Speed Counter Inputs

HSC Inputs : 2 Input(HSC1: DI1 and DI2, HSC2: DI3 and DI4)
Nominal Input Voltage : 24 VDC
 

Input Voltage

 

:

For Logic 0 For Logic 1
< 10 VDC >20 VDC
Input Current : 6mA max.
Input Impedance : 5.6 kΩ
Frequency range : 15KHz max. for single phase 10KHz max. for double phase
Galvanic Isolation : 500 VAC for 1 minute

Digital Outputs

Digital Outputs   8 Output
Outputs Current : 1 A max. (Total current 8 A max.)
Galvanic Isolation : 500 VAC for 1 minute
Short Circuit Protection : Yes

Analog Inputs

Analog Inputs :   5 Input
 

Input Impedance

 

:

PT-100 0/4-20mA 0-10V 0-50mV
-200oC-650oC 100Ω >6.6kΩ >10MΩ
Galvanic Isolation :   No  
Resolution :   14 Bits  
Accuracy :   ±0,25%  
Sampling Time :   250 ms  
Status Indication :   Yes  

Analog Outputs

 

Analog Output

 

:

2 Output
0/4-20mA 0-10V
Galvanic Isolation : No
Resolution : 12 Bits
Accuracy : 1% of full scale

Internal Address Definitions

Communication Settings:

Parameters Address Options Default
ID 40001 1–255 1
BAUDRATE 40002 0- 1200 / 1- 2400 / 2- 4000 / 3- 9600 / 4- 19200 / 5- 38400 /

6- 57600 /7- 115200

6
STOP BIT 40003 0- 1Bit / 1- 2Bit 0
PARITY 40004 0- None / 1- Even / 2- Odd 0

Device addresses:

Memory Format Arange Address Type
Digital Input DIn n: 0 – 7 10001 – 10008 Read
Digital Output DOn n: 0 – 7 1 – 8 Read-Write
Analog Input AIn n: 0 – 7 30004 – 30008 Read
Analog Output AOn n: 0 – 1 40010 – 40011 Read-Write
Version* (aaabbbbbcccccccc)bit n: 0 30001 Read
  • Note:The a bits in this address are major, b bits are minor version number, c bits indicate device type.
  • Example: Value read from 30001 (0x2121)hex = (0010000100100001)bit ,
  • a bits (001)bit = 1 (Major version number)
  • b bits (00001)bit = 1 (Minor version number)
  • c bits (00100001)bit = 33 (The device types are indicated in the table.) Device version = V1.1
  • Device type = 0-10V Analog Input 0-10V Analog Output

Device Types:

Device Type Value
PT100 Analog Input 4-20mA Analog Output 0
PT100 Analog Input 0-10V Analog Output 1
4-20mA Analog Input 4-20mA Analog Output 16
4-20mA Analog Input 0-10V Analog Output 17
0-10V Analog Input 4-20mA Analog Output 32
0-10V Analog Input 0-10V Analog Output 33
0-50mV Analog Input 4-20mA Analog Output 48
0-50mV Analog Input 0-10V Analog Output 49

The conversion of the values read from the module according to the analog input type is described in the following table:

Analog Input The Value Range Conversion Factor Example of value shown in PROOP
 

PT-100

-200° 650°

 

 

-2000 – 6500

 

 

x101

Example-1: The read value as 100 is converted to 10oC.
Example-2: The read value as 203 is converted to 20.3oC.
0 10V 0 – 20000 0.5×103 Example-1: The read value as 2500 is converted to 1.25V.
0 50mV 0 – 20000 2.5×103 Example-1: The read value as 3000 is converted to 7.25mV.
 

0/4 20mA

 

 

0 – 20000

 

 

0.1×103

Example-1: The read value as 3500 is converted to 7mA.
Example-2: The read value as 1000 is converted to 1mA.

The conversion of the values write at the module according to the analog output type is described in the following table:

Analog Output The Value Range Conversion Rate Example of Value Written in Modules
0 10V 0 – 10000 x103 Example-1: The value to be written as 1.25V is converted to 1250.
0/4 20mA 0 – 20000 x103 Example-1: The value to be written as 1.25mA is converted to 1250.

Analog Input-Specific Addresses:

Parameter AI1 AI2 AI3 AI4 AI5 Default
Configuration Bits 40123 40133 40143 40153 40163 0
Minimum Scale Value 40124 40134 40144 40154 40164 0
Maximum Scale Value 40125 40135 40145 40155 40165 0
Scaled Value 30064 30070 30076 30082 30088

Analog Input Configuration Bits:

AI1 AI2 AI3 AI4 AI5 Description
40123.0bit 40133.0bit 40143.0bit 40153.0bit 40163.0bit 4-20mA/2-10V Select:

0 = 0-20 mA/0-10 V

1 = 4-20 mA/2-10 V

The Scaled Value for analog inputs is calculated according to the state of the 4-20mA / 2-10V Selection configuration bit.
Analog Output Specific Addresses:

Parameter AO1 AO2 Default
Minimum Scale Value for Input 40173 40183 0
Maximum Scale Value for Input 40174 40184 20000
Minimum Scale Value for Output 40175 40185 0
Maximum Scale Value for Output 40176 40186 10000/20000
Analog Output Function

0: Manual use

1: Using the scale values above, it reflects the input to the output. 2: It drives the analog output as PID output, using the minimum and maximum scale parameters for the output.

40177 40187 0
  • In case the analog output function parameter is set to 1 or 2;
  • AI1 is used as input for A01 output.
  • AI2 is used as input for A02 output.
  • Not: Mirroring the input to output feature (Analoque Output Function = 1) cannot be used in modules with PT100 inputs.

HSC(High-Speed Counter) SettingsEMKO-PROOP-Input-or-Output--Modul-FIG-21

Single Phase Counter Connection

  • High-speed counters count high-speed events that cannot be controlled at PROOP-IO scan rates. The maximum counting frequency of a high-speed counter is 10kHz for Encoder inputs and 15kHz for counter inputs.
  • There are five basic types of counters: single-phase counter with internal direction control, single-phase counter with external direction control, two-phase counter with 2 clock inputs, A/B phase quadrature counter, and frequency measurement type.
  • Note that every mode is not supported by every counter. You can use each type except the frequency measurement type: without reset or start inputs, with reset and without start, or with both start and reset inputs.
  • When you activate the reset input, it clears the current value and holds it clear until you deactivate reset.
  • When you activate the start input, it allows the counter to count. While start is deactivated, the current value of the counter is held constant and clocking events are ignored.
  • If reset is activated while start is inactive, the reset is ignored and the current value is not changed. If the start input becomes active while the reset input is active, the current value is cleared.
Parameters Address Default
HSC1 Configuration ve Mode Select* 40012 0
HSC2 Configuration ve Mode Select* 40013 0
HSC1 New Current Value (Least Significant 16 byte) 40014 0
HSC1 New Current Value (Most Significant 16 byte) 40015 0
HSC2 New Current Value (Least Significant 16 byte) 40016 0
HSC2 New Current Value (Most Significant 16 byte) 40017 0
HSC1 Current Value (Least Significant 16 byte) 30010 0
HSC1 Current Value (Most Significant 16 byte) 30011 0
HSC2 Current Value (Least Significant 16 byte) 30012 0
HSC2 Current Value (Most Significant 16 byte) 30013 0

Note: This parameter;

  • The least significant byte is the Mode parameter.
  • The most significant byte is the Configuration parameter.

HSC Configuration Description:

HSC1 HSC2 Description
40012.8bit 40013.8bit Active level control bit for Reset:

0 = Reset is active low           1 = Reset is active high

40012.9bit 40013.9bit Active level control bit for Start:

0 = Start is active low             1 = Start is active high

40012.10bit 40013.10bit Counting direction control bit:

0 = Count down                      1 = Count up

40012.11bit 40013.11bit Write the new current value to the HSC:

0 = No update                          1 = Update current value

40012.12bit 40013.12bit Enable the HSC:

0 = Disable the HSC               1 = Enable the HSC

40012.13bit 40013.13bit Reserve
40012.14bit 40013.14bit Reserve
40012.15bit 40013.15bit Reserve

HSC Modes:

Mode Description Inputs
  HSC1 DI1 DI2 DI5 DI6
HSC2 DI3 DI4 DI7 DI8
0 Single Phase Counter with Internal Direction Clock      
1 Clock   Reset  
2 Clock   Reset Start
3 Single Phase Counter with External Direction Clock Direction    
4 Clock Direction Reset  
5 Clock Direction Reset Start
6 Two Phase Counter with 2 Clock Input Clock Up Clock Down    
7 Clock Up Clock Down Reset  
8 Clock Up Clock Down Reset Start
9 A/B Phase Encoder Counter Clock A Clock B    
10 Clock A Clock B Reset  
11 Clock A Clock B Reset Start
12 Reserve        
13 Reserve        
14 Period Measurement (with 10 μs sampling time) Period Input      
15 Counter /

Period Ölçümü (1ms sampling time)

Max. 15 kHz Max. 15 kHz Max. 1 kHz Max. 1 kHz

Specific Addresses for Mode 15:

Parameter DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 Default
Configuration Bits 40193 40201 40209 40217 40225 40233 40241 40249 2
Period Reset Time (1-1000 sn)  

40196

 

40204

 

40212

 

40220

 

40228

 

40236

 

40244

 

40252

 

60

Counter low-order 16-bit value 30094 30102 30110 30118 30126 30134 30142 30150
Counter high-order 16-bit value 30095 30103 30111 30119 30127 30135 30143 30151
Period low-order 16-bit value(ms) 30096 30104 30112 30120 30128 30136 30144 30152
Period high-order 16-bit value(ms) 30097 30105 30113 30121 30129 30137 30145 30153

Configuration Bits:

DI1 DI2 DI3 DI4 DI5 DI6 DI7 DI8 Description
40193.0bit 40201.0bit 40209.0bit 40217.0bit 40225.0bit 40233.0bit 40241.0bit 40249.0bit DIx enable bit: 0 = DIx enable 1 = DIx disable
 

40193.1bit

 

40201.1bit

 

40209.1bit

 

40217.1bit

 

40225.1bit

 

40233.1bit

 

40241.1bit

 

40249.1bit

Count direction bit:

0 = Count down 1 = Count up

40193.2bit 40201.2bit 40209.2bit 40217.2bit 40225.2bit 40233.2bit 40241.2bit 40249.2bit Reserve
40193.3bit 40201.3bit 40209.3bit 40217.3bit 40225.3bit 40233.3bit 40241.3bit 40249.3bit DIx count reset bit:

1 = Reset the DIx counter

PID Settings

The PID or On/Off control feature can be used by setting the parameters determined for each analog input in the module. The analog input with PID or ON/OFF function activated controls the corresponding digital output. The digital output associated with the channel whose PID or ON/OFF function is activated cannot be driven manually.

  • Analog input AI1 controls digital output DO1.
  • Analog input AI2 controls digital output DO2.
  • Analog input AI3 controls digital output DO3.
  • Analog input AI4 controls digital output DO4.
  • Analog input AI5 controls digital output DO5.

PID Parameters:

Parameter Description
PID Active Enables PID or ON/OFF operation.

0 = Manual use          1 = PID active         2 = ON/OFF active

Set Value It is the set value for PID or ON/OFF operation. PT100 values can be between -200.0 and 650.0 for input, 0 and 20000 for other types.
Set Offset It is used as Set Offset value in PID operation. It can take values between -325.0 and

325.0 for PT100 input, -10000 to 10000 for other types.

Set Hysteresis It is used as Set Hysteresis value in ON/OFF operation. It can take values between

-325.0 and 325.0 for PT100 input, -10000 to 10000 for other types.

Minimum Scale Value Working scale is the lower limit value. PT100 values can be between -200.0 and

650.0 for input, 0 and 20000 for other types.

Maximum Scale Value Working scale is the upper limit value. PT100 values can be between -200.0 and

650.0 for input, 0 and 20000 for other types.

Heating Proportional Value Proportional value for heating. It can take values between 0.0 and 100.0.
Heating Integral Value Integral value for heating. It can take values between 0 and 3600 seconds.
Heating Derivative Value Derivative value for heating. It can take values between 0.0 and 999.9.
Cooling Proportional Value Proportional value for cooling. It can take values between 0.0 and 100.0.
Cooling Integral Value Integral value for cooling. It can take values between 0 and 3600 seconds.
Cooling Derivative Value Derivative value for cooling. It can take values between 0.0 and 999.9.
Output Period Output is the control period. It can take values between 1 and 150 seconds.
Heating/Cooling Select Specifies the channel operation for PID or ON/OFF. 0 = Heating          1 = Cooling
Auto Tune Starts Auto Tune operation for PID.

0 = Auto Tune passive         1 = Auto Tune active

  • Note: For the values in dotted notation, 10 times the real value of these parameters are used in Modbus communication.

PID Modbus Addresses:

Parameter AI1

Address

AI2

Address

AI3

Address

AI4

Address

AI5

Address

Default
PID Active 40023 40043 40063 40083 40103 0
Set Value 40024 40044 40064 40084 40104 0
Set Offset 40025 40045 40065 40085 40105 0
Sensor Offset 40038 40058 40078 40098 40118 0
Set Hysteresis 40026 40046 40066 40086 40106 0
Minimum Scale Value 40027 40047 40067 40087 40107 0/-200.0
Maximum Scale Value 40028 40048 40068 40088 40108 20000/650.0
Heating Proportional Value 40029 40049 40069 40089 40109 10.0
Heating Integral Value 40030 40050 40070 40090 40110 100
Heating Derivative Value 40031 40051 40071 40091 40111 25.0
Cooling Proportional Value 40032 40052 40072 40092 40112 10.0
Cooling Integral Value 40033 40053 40073 40093 40113 100
Cooling Derivative Value 40034 40054 40074 40094 40114 25.0
Output Period 40035 40055 40075 40095 40115 1
Heating/Cooling Select 40036 40056 40076 40096 40116 0
Auto Tune 40037 40057 40077 40097 40117 0
PID Instant Output Value (%) 30024 30032 30040 30048 30056
PID Status Bits 30025 30033 30041 30049 30057
PID Configuration Bits 40039 40059 40079 40099 40119 0
Auto Tune Status Bits 30026 30034 30042 30050 30058

PID Configuration Bits :

AI1 Address AI2 Address AI3 Address AI4 Address AI5 Address Description
40039.0bit 40059.0bit 40079.0bit 40099.0bit 40119.0bit PID pause:

0 = PID operation continues.

1 = PID is stopped and the output is turned off.

PID Status Bits :

AI1 Address AI2 Address AI3 Address AI4 Address AI5 Address Description
30025.0bit 30033.0bit 30041.0bit 30049.0bit 30057.0bit PID calculation status:

0 = Calculating PID               1 = PID is not calculated.

 

30025.1bit

 

30033.1bit

 

30041.1bit

 

30049.1bit

 

30057.1bit

Integral calculation status:

0 = Calculating integral      1 = Integral is not calculated

Auto-Tune Status Bits :

AI1 Address AI2 Address AI3 Address AI4 Address AI5 Address Description
30026.0bit 30034.0bit 30042.0bit 30050.0bit 30058.0bit Auto Tune first step status:

1 = The first step is active.

30026.1bit 30034.1bit 30042.1bit 30050.1bit 30058.1bit Auto Tune second step status:

1 = The second step is active.

30026.2bit 30034.2bit 30042.2bit 30050.2bit 30058.2bit Auto Tune third step status:

1 = The third step is active.

30026.3bit 30034.3bit 30042.3bit 30050.3bit 30058.3bit Auto Tune final step status:

1 = Auto Tune complete.

30026.4bit 30034.4bit 30042.4bit 30050.4bit 30058.4bit Auto Tune Timeout error:

1 = There is a timeout.

Installing Communication Settings by Default

For cards with version V01;EMKO-PROOP-Input-or-Output--Modul-FIG-18

  1. Power off the I/O Module device.
  2. Lift the cover of the device.
  3. Short circuit pins 2 and 4 on the socket shown in the picture.
  4. Wait for at least 2 seconds by energizing. After 2 seconds, the communication settings will return to default.
  5. Remove the short circuit.
  6. Close the device cover.

For cards with version V02;EMKO-PROOP-Input-or-Output--Modul-FIG-19

  1. Power off the I/O Module device.
  2. Lift the cover of the device.
  3. Put a jumper on the socket shown in the picture.
  4. Wait for at least 2 seconds by energizing. After 2 seconds, the communication settings will return to default.
  5. Remove the jumper.
  6. Close the device cover.

Modbus Slave Address Selection

The slave address can be set from 1 to 255 at address 40001 of the modbus. In addition, the Dip Switch on the card can be used to set the slave address on V02 cards.EMKO-PROOP-Input-or-Output--Modul-FIG-20

  DIP SWITCH
SLAVE ID 1 2 3 4
Not1 ON ON ON ON
1 OFF ON ON ON
2 ON OFF ON ON
3 OFF OFF ON ON
4 ON ON OFF ON
5 OFF ON OFF ON
6 ON OFF OFF ON
7 OFF OFF OFF ON
8 ON ON ON OFF
9 OFF ON ON OFF
10 ON OFF ON OFF
11 OFF OFF ON OFF
12 ON ON OFF OFF
13 OFF ON OFF OFF
14 ON OFF OFF OFF
15 OFF OFF OFF OFF
  • Note 1: When all of the Dip Switches are ON, the value in Modbus register 40001 is used as the slave address.

Warranty

This product is warranted against defects in materials and workmanship for a period of two years from the date of shipment to Buyer. The Warranty is limited to repair or replacement of the defective unit at theoption of the manufacturer. This warranty is void if the product has been altered, misused, dismantled, or otherwise abused.

Maintenance

Repairs should only be performed by trained and specialized personnel. Cut power to the device before accessing internal parts. Do not clean the case with hydrocarbon-based solvents (Petrol, Trichlorethylene, etc.). Use of these solvents can reduce the mechanical reliability of the device.

Other Information

  • Manufacturer Information:
  • Emko Elektronik Sanayi ve Ticaret A.Ş.
  • Bursa Organize Sanayi Bölgesi, (Fethiye OSB Mah.)
  • Ali Osman Sönmez Bulvarı, 2. Sokak, No:3 16215
  • BURSA/TURKEY
  • Phone : (224) 261 1900
  • Fax : (224) 261 1912
  • Repair and maintenance service information:
  • Emko Elektronik Sanayi ve Ticaret A.Ş.
  • Bursa Organize Sanayi Bölgesi, (Fethiye OSB Mah.)
  • Ali Osman Sönmez Bulvarı, 2. Sokak, No:3 16215
  • BURSA/TURKEY
  • Phone : (224) 261 1900
  • Fax : (224) 261 1912

Documents / Resources

EMKO PROOP Input or Output Module [pdf] User Manual
PROOP, Input or Output Module, PROOP Input or Output Module, Input Module, Output Module, Module

References

Leave a comment

Your email address will not be published. Required fields are marked *