CMP58 Kalebu CPM-SP Range
“
Spesifikasi
- Model sing dilindhungi: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 (Apa
ora kalebu kisaran CPM-SP) - Disertifikasi kanggo digunakake ing kategori cerobong asap: B23, C13, C33, C43, C53,
C63, C83
Pandhuan Panggunaan Produk
Sistem Flue Pipa Kembar Tipe C53
Kanggo sistem saluran asap kembar, tindakake ukuran lan pitungan
pedoman sing kasedhiya ing kaca 12 saka manual.
Sistem Flue Konvensional (Mung Knalpot) Tipe B23
Kanggo sistem saluran asap konvensional, deleng kaca 15 kanggo ukuran lan
instruksi pitungan.
Sistem Flue Nggunakake Flue Ora Disedhiyakake dening Lochinvar Tipe C63
Yen nggunakake flue ora diwenehake dening Lochinvar, tindakake pandhuan
mbatesi ing kaca 16 kanggo sistem flue umum.
FAQ
P: Standar apa sing kudu dipatuhi instalasi?
A: Kabeh panginstalan kudu tundhuk karo BS5440-1: 2023 kanggo
piranti nganti 70kW input net. Waca drawing 1 lan Tabel 1 kanggo
lokasi terminal.
“`
CPM Boiler range Flue Guide
Model sing dilindhungi: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 Ora kalebu kisaran CPM-SP
Isine
UMUM………………………………………………………………………………………………………………………… 2 Gambar 1 Lokasi terminal boiler……………………………………………………………………………………………….5 Tabel 1 Lokasi terminal boiler …………………………………………………………………………………………………..5 Tabel 2 Assessment risiko ………………………………………………………………………………………………………………………………….6
SISTEM FLUE KONSENTRIK ………………………………………………………………………………………………………………………7 Tipe Horizontal C13 …………………………………………………………………………………………………………………….7 Kit Plume kanggo nggunakake cerobong horisontal…………………………………………………………………………………………………….8 Tipe Vertikal C33…………………………………………………………………………………………………………………………………… 9 / Kalkulasi …………………………………………………………………………………………………………………………… 9 Konsentris………………………………………………………………………………………………………………………… 9
SISTEM SALURAN TWIN-PIPE TIPE C53 ……………………………………………………………………………………………………………11 Ukuran/perhitungan Flue-Pipa Kembar……………………………………………………………………………………..12
SISTEM SALURAN KONVENSIONAL (KUMUR) JENIS B23…………………………………………………………………….14 Ukuran/perhitungan cerobong konvensional……………………………………………………………………………………15
SISTEM FLUE MENGGUNAKAN FLUE NOT SUPPLY BY LOCHINVAR TYPE C63………………………………………………………………..16 SISTEM FLUE COMMON ………………………………………………………………………………………………………………..16 FORMULIR PESANAN DAN CATATAN …………………………………………………………………………………………………………….17
Kaca 1 saka 19
UMUM
Boiler CPM Lochinvar disertifikasi kanggo digunakake ing kategori flue ing ngisor iki:
Tipe Instalasi Kategori
Katrangan
B23
Bukak cerobong asap
Piranti sing dimaksudake kanggo disambungake menyang cerobong asap sing ngevakuasi produk pembakaran menyang njaba ruangan sing ngemot piranti kasebut. Udara pembakaran ditarik langsung saka kamar.
C13
Flue Tertutup
Piranti sing disambungake menyang sistem saluran buang konsentris utawa pipa kembar kanthi terminal saluran horisontal. Loro-lorone inlet udara lan exhaust kudu ana ing zona tekanan sing padha.
C33
Flue Tertutup
Piranti sing disambungake menyang sistem saluran asap konsentris utawa pipa kembar kanthi terminal saluran alur Vertikal. Loro-lorone inlet udara lan exhaust kudu ana ing zona tekanan sing padha.
Piranti sing disambungake menyang inlet udara umum lan sistem exhaust flue, sing dirancang kanggo luwih saka
C43
Ditutup Flue siji piranti. Sistem umum iki duwe siji inlet online lan exhaust flue lan minangka bagéan saka bangunan ora
piranti.
C53
Flue Tertutup
Piranti sing disambungake menyang sistem saluran asap kembar kanthi terminal saluran alur Horizontal utawa Vertikal. Inlet udara lan knalpot bisa uga ana ing zona tekanan sing beda.
Piranti sing dimaksudake kanggo disambungake menyang sistem sing disetujoni lan dipasarake kanthi kapisah kanggo nyedhiyakake
C63
Udhara pembakaran cerobong tertutup lan metune produk pembakaran (kayata liyane saka sing disedhiyakake dening pemanas banyu
pabrikan).
Piranti sing disambungake liwat salah sawijining saluran menyang sistem saluran siji utawa umum. Sistem saluran iki kalebu
C83
Flue Tertutup
saka saluran konsep alam tunggal (yaiku ora nggabungake penggemar) sing ngevakuasi produk pembakaran. Piranti kasebut disambungake liwat saluran liya menyang terminal, sing nyedhiyakake hawa menyang piranti kasebut
saka njaba bangunan.
Kabeh instalasi kudu tundhuk karo syarat:
1. Kanggo piranti nganti 70kW input net- BS5440-1: 2023- Flueing lan ventilasi kanggo peralatan gas saka input dirating ora ngluwihi 70 kW net (1st, 2nd lan 3 gas kulawarga). Spesifikasi kanggo instalasi peralatan gas menyang cerobong asep lan kanggo pangopènan cerobong asep. a. Deleng gambar 1 lan tabel 1 kanggo rincian lokasi terminal.
2. Kanggo Perkakas liwat 70kW input net- IGEM / UP / 10 Edition 4 + A: 2016 - Instalasi peralatan gas flued ing latar industri lan komersial, manungsa waé tartamtu kudu mbayar kanggo bagean ing ngisor iki. a. Deleng gambar 1 lan tabel 1 kanggo rincian lokasi terminal. b. Penghentian horisontal kudu ditemokake miturut jarak minimal sing diwenehake ing tabel 1, lan tundhuk karo kriteria penilaian risiko sing ditampilake ing tabel 2. c. Terminasi cerobong horisontal (saliyane kanggo sistem pengenceran kipas) ora kena dipasang kanggo piranti siji utawa klompok piranti kanthi input nett total ngluwihi input panas netto 333kW. d. Kanggo piranti siji utawa klompok piranti kanthi total input panas net ngluwihi 333 kW, syarat umum IGEM / UP / 10 Edition 4 + A: 2016 kudu ditrapake lan disetujoni saka Panguwasa Lokal sadurunge wiwitan instalasi.
3. Undhang-undhang Udara Resik kanggo instalasi sing ngluwihi input nett 333kW.
Kaca 2 saka 19
GAMBAR 1 LOKASI TERMINAL BOILER MUTU BS5440-1-2023
TABEL 1 LOKASI TERMINAL BOILER SESUAI BS5440-1-2023
Katrangan lokasi
A
Langsung ing ngisor bukaan, bata udara, jendhela mbukak lsp.
B
Ndhuwur bukaan, bata udara, jendhela mbukak lsp.
C
Horisontal menyang bukaan, bata udara, jendhela mbukak lsp.
D
Ing ngisor selokan utawa pipa sanitasi
E
Ing ngisor eaves
F
Ing ngisor atap loteng utawa port mobil
G
Saka saluran vertikal utawa pipa lemah
H
Saka sudhut internal utawa njaba
I
Ndhuwur lemah, atap utawa loteng
J
Saka permukaan sing madhep terminal
K
Saka terminal madhep terminal
L
Saka bukaan ing port mobil (contone, lawang, jendhela) menyang omah
M
Vertikal saka terminal ing tembok sing padha
N
Horisontal saka terminal ing tembok sing padha
O
Horisontal saka inlet udara mekanik ing tembok sing padha
P
Saka struktur vertikal ing atap
Q
Ndhuwur prapatan karo gendheng
R
Diagonal ngliwati bukaan menyang bangunan ing tembok sing beda
S
Terminal vertikal saka terminal vertikal liyane
T
Terminal vertikal sing cedhak karo bukaan menyang bangunan
U
Terminal vertikal saka tembok
V
Terminal bebarengan wates
W
Terminal madhep wates
X
Jejer kanggo bukaan menyang bangunan ing gendheng pitched
Y
Terminal madhep bukaan menyang bangunan
* Hubungi dhukungan teknis Lochinvar kanggo bantuan.
CPM58
mm
300
mm
300
mm
300
mm
75
mm
300
mm
200
mm
150
mm
300
mm
300
mm
600
mm
1200
mm
1200
mm
1500
mm
300
mm
1000
mm
N/A
mm
300
mm
600
mm
600
mm
1500
mm
500
mm
300
mm
600
mm
*
mm
2000
Kaca 3 saka 19
TABEL 2 PENILAIAN RISIKO MENURUT BS5440-1-2023
Luwih saka syarat ing BS5440-1: 2023 Lampiran D lan Gambar C.8, tabel C.1 pambiji resiko ing ngisor iki menehi tuntunan kanggo posisi flues horisontal. Formulir iki kudu diisi sadurunge karya diwiwiti lan ditindakake dening wong sing kompeten kanggo nindakake penilaian risiko.
Perkakas Tipe C kanthi input panas netto ora ngluwihi 70kW Assessment risiko discharge cerobong tingkat rendah (kalebu input panas netto kanggo klompok peralatan)
No Babagan posisi flue
Ora Ya
1 Apa terminal flue bakal nglanggar posisi sing ditemtokake ing tabel C.1 kanggo stopkontak cerobong asep sing disegel?
Ora Ya
2
Apa terminal kasebut bakal dilebokake ing posisi sing bakal ngidini produk pembakaran bisa dibentuk (contone, ditutupi dening struktur sing cedhak)?
Ora
ya wis
3 Apa mandap ing sumur cahya?
Ora Ya
4 Apa mandap ing carport tanpa loro sisih unobstructed?
Ora Ya
5 Apa mandhek bakal ana ing wilayah sing bisa uga ana bahan sing gampang kobong ing sacedhake?
Ora Ya
6 Apa mandhek bakal ana ing wilayah sing bisa duwe bahan mbebayani ing sacedhake (contone, petrokimia)?
Ora Ya
7 Apa mandhek bakal ana ing dalan sing ditutupi? 8 Apa ana larangan sing mandhegake pas penjaga terminal yen dibutuhake? 9 Apa penghentian bakal ngliwati wates?
Ora Ya Ora Ya Ora Ya
10 Apa kit manajemen plume dibutuhake kanggo ngubengi jarak mandap kaya sing dibutuhake ing tabel C.1?
Ora Ya
Nomer 11 12
Ora.
Pertimbangan gangguan Apa mandap dumunung ing dalan sing bisa nyebabake gangguan (contone, dhuwur sirah utawa pluming menyang pangguna)? Apa penghentian kasebut bisa nyebabake gangguan kanggo tanggane? Rute cerobong asap / cerobong asap Bakal dipasang ing kekosongan sing ora bisa nyukupi pemeriksaan visual sing lengkap?
Ora Ya
Ora Ya
Ora Ya Ora Ya Ora Ya
Apa ana watesan sing bakal nyegah flue didhukung ing kabeh dawa?
Ora Ya
Apa bahan cerobong asap nglanggar peraturan bangunan (contone, bangunan beresiko dhuwur)?
Ora Ya
Apa rute flue bakal ngliwati wilayah sing dilindhungi geni tanpa kemampuan kanggo njaga perlindungan kasebut?
Ora Ya
Apa flue bakal ngliwati omah liyane?
Apa cerobong asap bisa rusak amarga rute/lokasi (contone, bahan sing disimpen ing ruangan tanduran utawa gudang)?
Ora Ya Ora Ya
Apa flue mengaruhi integritas struktur ing (contone, lintel, nampan rongga, alangan, utawa membran)?
Ora Ya
Yen kabeh jawaban biru, mula posisi flue kudu cocog
Yen ana jawaban oranye, mula posisi cerobong asap ora cocog, coba revisi posisi utawa jinis outlet asap utawa hubungi petugas Kesehatan Lingkungan lokal kanggo pitulung lan/utawa persetujuan.
Kaca 4 saka 19
GAMBAR 2 LOKASI TERMINAL BOILER MENURUT IGEM/UP/10 EDISI 4 +A: 2016
TABEL 3 LOKASI TERMINAL BOILER MENURUT IGEM/UP/10 EDISI 4 +A: 2016
Katrangan lokasi
A
Langsung ing ngisor bukaan, bata udara, jendhela mbukak lsp.#
B
Ndhuwur bukaan, bata udara, jendhela mbukak lsp.
C
Horisontal menyang bukaan, bata udara, jendhela mbukak lsp.#
D
Ing ngisor selokan utawa pipa sanitasi
E
Ing ngisor eaves
F
Ing ngisor atap loteng utawa port mobil
G
Saka saluran vertikal utawa pipa lemah
H
Saka sudhut internal utawa njaba
I
Ndhuwur lemah, atap utawa loteng
J
Saka permukaan sing madhep terminal
K
Saka terminal madhep terminal
L
Saka bukaan ing port mobil (eg lawang, jendhela) menyang omah
M
Vertikal saka terminal ing tembok sing padha
N
Horisontal saka terminal ing tembok sing padha
N+
Vertikal saka terminal ing gendheng padha
P
Saka struktur vertikal ing atap
Q
Ndhuwur prapatan karo gendheng
CPM77 CPM96 CPM116 CPM144 CPM175
mm 2500
2500
2500
2500
2500
mm
631
760
896
1092
1294
mm
631
760
896
1092
1294
mm
200
200
200
200
200
mm
200
200
200
200
200
mm
Ora dianjurake kanggo ndeleng penilaian risiko UP10
mm
150
150
150
150
150
mm 1099
1513
1948
2573
3220
mm
300
300
300
300
300
mm 1100
1514
1948
2573
3220
mm 2083
2429
2792
3314
3855
mm
Ora dianjurake kanggo ndeleng penilaian risiko UP10
mm 2500
2500
2500
2500
2500
mm
600
600
900
900
n/a*
600
600
900
900
n/a*
mm 1500
1500
1500
1500
1500
mm
311
359
409
481
556
*Hubungi dhukungan teknis Lochinvar kanggo pandhuan babagan mandap CPM175.
Tabel ing ndhuwur kudu digunakake magepokan karo cathetan ing ngisor iki: · Jarak ditampilake njamin ketel bakal operate tanpa masalah ing paling kahanan, jarak iki bisa suda ing kahanan tartamtu · Ndhuwur kudu maca magepokan karo edition paling anyar saka BS5440-1 lan IGEM UP10 · Kanggo instalasi boiler ndhuwur 333kW kudu resik lan udhara ing ndhuwur kudu dilebokake ing instalasi, lan ing ndhuwur kudu resik. tundhuk karo syarate kanthi lengkap, hubungi tim kesehatan lingkungan lokal kanggo pandhuan luwih lanjut
Kanggo pandhuan luwih lengkap, hubungi dhukungan Teknis Lochinvar
Kaca 5 saka 19
Tabel 4 penilaian risiko Tabel ing ngisor iki minangka kutipan saka IGEMUP10 lan kudu digunakake bebarengan karo dokumen kasebut
Luwih saka syarat ing IGEM / UP / 10 Edition 4 +A: 2016 bagean 8 ing klausa 8.7.3.3 lan Figure 7 Assessment resiko ing ngisor iki menehi panuntun dhumateng kanggo posisi saka flues horisontal. Formulir iki kudu diisi sadurunge karya diwiwiti lan ditindakake dening wong sing kompeten kanggo nindakake penilaian risiko.
Perkakas Tipe C kanthi input panas netto ngluwihi 70 kW lan ora ngluwihi 333 kW evaluasi risiko discharge cerobong rendah (kalebu input panas netto kanggo klompok peralatan)
Ora.
Babagan posisi flue
Ora
ya wis
Apa penghentian cerobong sing diusulake ing jarak ing Gambar K saka dalan, dalan,
1
track, thoroughfare, walkway, wates property utawa wilayah, kang digunakake kanggo umum
Ora
ya wis
akses umum liyane saka kanggo tujuan pangopènan?
2
Apa penghentian saluran sing diusulake ing jarak ing Gambar K menyang papan dolanan,
Ora
ya wis
sekolah, pekarangan, area lenggahan, utawa area sing bisa dadi kumpul umum
3
Yen mandap flue ngajokaken terlampir ing luwih saka loro-lorone banjur nindakaken
Ora
ya wis
tundhuk karo syarat Gambar 11B?
Apa mandap flue ngajokaken ing kadohan ing Figure K saka lumahing utawa
4
unsur bangunan sing bisa kena pengaruh korosi utawa rusak saka plume
Ora
ya wis
kondensat?
5
Apa posisi flue sing diusulake ing wilayah sing bisa diparkir kendaraan
Ora
ya wis
jarak saka Figure 12 Line G kanggo flue?
6
Apa ana semak utawa wit ing jarak minimal sing dituduhake ing Gambar K
Ora
ya wis
posisi terminal sing diusulake?
7
Apa mandap flue sing diusulake ing sumur cahya?
Ora
ya wis
Apa produk pembakaran saka posisi cerobong asap sing diusulake bisa dikumpulake
8
ing kahanan atmosfer unfavorable, amarga aliran salib miskin saka online disebabake
Ora
ya wis
enclosures utawa struktur jejer lan / utawa kamungkinan kanggo nimbulaké gangguan?
9
Apa posisi terminasi flue bisa nyebabake gangguan ing properti sing ana ing jejere?
Ora
ya wis
Peraturan Bangunan Bagian J
10
Apa mandap flue sing diusulake kurang saka 300 mm saka wates properti, sing diukur saka sisih terminal menyang wates?
Ora
ya wis
Bab Undhang-undhang Udara Bersih
11
Apa output total saka individu, utawa klompok terminal flue (yen ing 5U (ndeleng A3.7)), luwih saka 333 kW input panas net?
Ora
ya wis
Umum
12
Apa ana pertimbangan liyane sing dibutuhake kanggo pambiji risiko iki, deleng sheet kapisah.
Ora
ya wis
13
Komentar:
Yen kabeh jawaban Biru banjur posisi cerobong asap kudu cocog Yen ana jawaban Oranye banjur posisi cerobong asap ora cocog, coba revisi posisi utawa jinis stopkontak cerobong utawa hubungi petugas Kesehatan Lingkungan lokal kanggo pitulungan lan/utawa persetujuan.
INFORMASI BOILER FLUE
Nomer Model FLUE DATA TIPE B23 Diameter cerobong nominal Suhu gas cerobong maksimum Suhu gas buang Persyaratan draft cerobong Tekanan kasedhiya kanggo sistem cerobong Volume gas buang maksimum TIPE DATA FLUE C13 & C33 Diameter cerobong nominal Suhu gas buang maksimum TIPE DATA FLUE C43 & C53 Suhu cerobong nominal maksimum.
mm °C °C mbar Pa g/s
mm °C
mm °C
CPM58
CPM77
80
5.59 kanggo 28.9 6.52 kanggo 38.6 80/125
80
CPM96
CPM116
CPM144
CPM175
100 95 85-95 -0.03 kanggo -0.1 200 7.69 kanggo 47.9 11.6 kanggo 57.7
130 15.2 kanggo 71.7 20.1 kanggo 86.2
100/150 95
100
130
95
Kaca 6 saka 19
SISTEM FLUE CONCENTRIC
JENIS HORIZONTAL C13
CPMH001 MODEL KOMPUTER FLUE HORIZONTAL KONSENTRIK – CPM58, CPM77
Item No
Katrangan
Klebu CPM58
LV310757 TERMINAL HORIZONTAL KONSENTRIK – Ø80/125mm PP
1
44.8
M28925B
TERMINAL DINDING PLAT
1
–
LV310735
KONSENTRIK BEND 90° Ø80/125mm PP
1
16.1
Resistance maksimum ing sistem flue 200pa
Total 60.9
CPM77 80.1 28.7 108.8
Nomer Item LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M84481B
Item Tambahan Flue Katrangan EMBUNG KONSENTRIK – Ø80/125mm PP EMBUNG KONSENTRIK TETAP – Ø80/125mm EKSTENSI KONSENTRASI PP – Ø80/125mm PP KONSENTRASI TETAP – Ø80/125mm – 80/125mm PP KONSENTRASI TETAP C. TELESCOPIC KONSENTRIK BEND 45° Ø80/125mm PP KONSENTRIK BEND 90° Ø80/125mm PP DINDING CLAMP Ø 125 mm
Ukuran 250mm 500mm 1000mm 2000mm
240mm-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/A
CPMH003 MODEL KOMPUTER FLUE HORIZONTAL KONSENTRIK – CPM96, CPM116
Item No
Katrangan
Klebu CPM96 CPM116
LV310758B TERMINAL HORIZONTAL KOSENTRIK Ø100/150mm PP
1
58
84
M84410B BEND KONSENTRIK 90° Ø100/150mm PP RADIUS PENDEK
1
23.6
34.2
Resistance maksimum ing sistem flue 200pa
Gunggunge 81.6 118.2
CPMH004 MODEL MAJLIS FLUE HORIZONTAL KOSENTRIK – CPM144
Item No
Katrangan
Klebu
LV310758B
TERMINAL HORIZONTAL KONSENTRIK Ø100/150mm PP
1
E61-001-172B
KIT KONVERSI KONSENTRIK
1
M84410B
BEND KONSENTRIK 90° Ø100/150mm PP RADIUS SINGKAT
1
Resistance maksimum ing sistem flue 200pa
Total
CPM144 129.9 52.9 182.8
Item No. M84405B M84402B M84412B M84413B M84421B M87196B
Katrangan Item Tambahan Flue
EKSTENSI KONSENTRIK Ø100/150mm Meja potong EKSTENSI KONSENTRIK Ø100/150mm PP TETAP
KONSENTRIK BEND 90° Ø100/150mm PP BEND KONSENTRIK 45° Ø100/150mm PP
SAMPLING POINT Ø100/150mm PP DINDING CLAMP Ø 150 mm
CPM58-77 A=45mm B=62.5mm
Ukuran 500 mm 1000 mm
Waca Drawing Ngisor Waca Drawing Ngisor
115 mm
CPM58-77 A=95mm B=110mm
CPM96-175 A=128mm B=128mm
CPM96-175 A=223mm B=208mm
Kaca 7 saka 19
PLUME KIT kanggo nggunakake karo FLUE HORIZONTAL
PLUME MANAGEMENT KIT LG800008B PLUME MANAGEMENT KIT Ø80/125mm LG800009B PLUME MANAGEMENT KIT Ø100/150mm
Ora
Katrangan
1 TENGKOK KONSENTRIK 90°-PP
2 KONSENTRIK HORIZONTAL PLUME KIT TERMINAL -PP
3 EXTENSION -PP CUTABLE (1000mm)
4 BEND 90°-PP
5 PLUME KIT MANUK GUARD
6 PLUME KIT FLUE EXIT-PP
7 TEMBUNG CLAMP
DIAMETER INTERNAL
B DIAMETER EKSTERNAL
CPM58 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm
CPM77 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm
CPM96 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm
CPM116 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm
CPM144 N/AN/AN/AN/AN/AN/AN/AN/AN/A
CPM175 N/AN/AN/AN/AN/AN/AN/AN/AN/A
Kit plume kudu ora digunakake kanggo mbenerake lokasi terminal ilegal
Kaca 8 saka 19
JENIS VERTIKAL C33
CPMV001 MODEL assembly VERTIKAL KONSENTRIK – CPM58, CPM77
No item LV310753 LV310745B
Deskripsi TERMINAL VERTIKAL KONSENTRIK – Ø80/125mm PP EKSTENSI KONSENTRIK – Ø80/125mm PP (500mm)
Kalebu 11
CPM58 61.5 5.1
LV310742B EKSTENSI KONSENTRIK – Ø80/125mm PP TETAP (1000mm)
1
10.2
Resistance maksimum ing sistem flue 200pa
Total 76.8
CPM77 109.8 9.05 18.1 136.95
Nomer item LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M87195B LV302520
Item Tambahan Flue
Deskripsi KONSENTRASI KONSENTRASI – Ø80/125mm PP KONSENTRASI KONSENTRASI TETAP – Ø80/125mm PP KONSENTRASI KONSENTRASI – Ø80/125mm PP KONSENTRASI TETAP – Ø80/125mm PP KONSENTRASI TETAP KONSENTRASI 80/1PI2 - 5mm 45° Ø80/125mm PP KONSENTRIK BEND 90° Ø80/125mm PP DINDING CLAMP Ø130mm atap datar kerlip Ø140mm ALU
Ukuran 250mm 500mm 1000mm 2000mm
240-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/AN/A
CPMV003 MODEL assembly VERTIKAL KONSENTRIK – CPM96, CPM116
Item No
Katrangan
Klebu CPM96
LV310754B
TERMINAL VERTIKAL KONSENTRIK Ø100/150mm PP
1
80
M84405B KONSENTRIK EKSTENSI Ø100/150mm (500mm) Cuttable
1
6.5
M84402B EKSTENSI KONSENTRIK Ø100/150mm (1000mm) PP TETAP
1
13
Resistance maksimum ing sistem flue 200pa
Total 99.5
CPM116 115.9 9.45 18.9 144.25
Item No. M84405B M84402B M84412B M84413B M84421B M87196B
Item Tambahan Flue
Deskripsi KONSENTRASI KONSENTRASI Ø100/150mm Meja potong KONSENTRIK KONSENTRASI Ø100/150mm PP TETAP KONSENTRIS BEND 90° Ø100/150mm PP KONSENTRIK BEND 45° Ø100/150mm PP SAMPLING POINT Ø100/150mm PP DINDING CLAMP Ø 150 mm
Ukuran 500 mm 1000 mm
Waca Drawing Ngisor Waca Drawing Ngisor
115 mm
CPM58-77 A=45mm B=62.5mm
CPM96-175 A=128mm B=128mm
CPM58-77 A=95mm B=110mm
CPM96-175 A=223mm B=208mm
Flue konsentris ora bisa digunakake karo CPM175
Kaca 9 saka 19
KONSENTRIK FLUE SIZING / Etungan
Resistance ing Pa
Item
CPM 58 80/125 CPM 77 80/125 CPM 96 100/150 CPM 116 100/150
Terminal tembok
44.8
80.1
58
84
Terminal gendheng
61.5
109.8
80
115.9
Tabung lurus (m)
10.2
18.1
13.0
18.9
45° Siku
8.6
15.4
15.5
22.4
90° Siku
16.1
28.7
23.6
34.2
Paket Plume
10
10
20
25
Kanggo digunakake kanggo Lochinvar diwenehake M & G komponen sistem flue resistance mung
CPM 144 100/150 129.9 179.2 29.2 34.7 52.9 n/a
CPM 175 100/150 188 259.3 42.2 50.2 76.5 n/a
Gunakake tabel ing ngisor iki kanggo ngetung total resistance sistem flue
Item
Jumlah Resistance Total
Terminal tembok Terminal atap Tabung lurus (m) 45° Siku 90° Siku Plume kit
Total Resistance (Pa)
Total resistensi sistem sing diwilang kudu kurang saka 200pa
Kaca 10 saka 19
SISTEM SALURAN KEMBAR JENIS C53
CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM58, CPM77
Flue Vertikal
Item No
Katrangan
Ora Dibutuhake CPM58 CPM77
LM410084006
1
TERMINAL VERTIKAL – 130 MM PP
38.8 38.8
LV305016
1
INLET UDARA HORIZONTAL Ø80mm
–
–
M28925B
1
PLAT DINDING TERMINAL (PASANGAN)
–
–
M85283 LM410084992
EXPANDER Ø80mm - Ø100mm PP
EXPANDER Ø100mm - Ø130mm PP
Resistance maksimum ing sistem flue 200pa
1 1 Total
–
–
–
–
38.8 38.8
CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM58, CPM77
Flue Horizontal
Ora
Item No
Katrangan
Dibutuhake CPM58
LV310757B
TERMINAL HORIZONTAL KONSENTRIK Ø80/125mm PP
1
29.86
LV305016
INLET UDARA HORIZONTAL Ø80mm
1
–
M28925B
PLAT DINDING TERMINAL (PASANGAN)
1
–
Resistance maksimum ing sistem flue
200pa
Total
29.86
CPM77 53.4
53.4
Item No. LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B
Katrangan Item Tambahan Flue
EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP TELESCOPIC BEND 45° 80mm PP 80mm PP BEND 90° W PP 80mmAMP Ø 80 mm
Ukuran 250mm 500mm 1000mm 2000mm
240-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/A
CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM96, CPM116
Flue Vertikal
Nomer Barang LM410084006
Katrangan
TERMINAL VERTIKAL 130 MM PP
Ora Perlu 1
CPM96 38.8
LV305039
INLET UDARA HORIZONTAL
1
–
Ø 100 mm
M28925B
DINDING TERMINAL
1
–
PLAT (PASANGAN)
LM410084992 EXPANDER Ø100mm -
1
–
Ø 130 mm PP
Resistance maksimum ing sistem flue 200pa
Total
38.8
CPM116 38.8
–
38.8
Kaca 11 saka 19
CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM96, CPM116
Flue Horizontal
Ora
Item No
Katrangan
Dibutuhake CPM96
KONSENTRIK
LV310758B
TERMINAL HORIZONTAL
1
38.66
Ø 100/150 mm PP
LV305039B
INLET UDARA HORIZONTAL Ø100mm ALU
1
–
Resistance maksimum ing sistem flue 200pa
Total 38.66
CPM116 56
56
Nomer Item M85176B M85177B M85181B M85182B M87193B
Item Tambahan Flue Keterangan EXTENSION Ø100mm PP CUT TO LENGTH EXTENSION Ø100mm PP CUT TO LENGTH BEND 90° 100mm PP BEND 45° 100mm PP WALL BAND (100mm)
Ukuran 500 mm 1000 mm
Waca Drawing Ngisor Waca Drawing Ngisor
n/a
CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM144, CPM175
Flue Vertikal
Item No
Katrangan
Ora Dibutuhake CPM144
LM410084006 TERMINAL VERTIKAL –
1
38.8
130 MM PP
LV307178
INLET UDARA HORIZONTAL
1
–
Ø 130 mm ALU
Resistance maksimum ing sistem flue 200pa
Total
38.8
CPM175 38.8
–
38.8
Item No M70242 M70251 M70252 M87195
Katrangan Item Tambahan Flue
EKSTENSI Ø130mm PP BEND 90° PP BEND 45° PP DINDING CLAMP
Ukuran 1000mm 130mm 130mm 130mm
CPM58CPM77 A=72.5mm, B=72.5mm
CPM96CPM116 A=78mm, B=65mm
CPM58CPM77 A=110mm, B=110mm
CPM96CPM116 A=78mm, B=65mm
Kaca 12 saka 19
TWIN-PIPE FLUE SIZING / Etungan
Item
Ukuran Resistance (Pa) (mm)
CPM 58 CPM 77 CPM 96 CPM 116
Tabung lurus (saben meter)
80
4.6
8.2
X
X
Tabung lurus (saben meter) 100
1.3
2.3
3.5
5.0
Tabung lurus (saben meter) 130
0.3
0.6
0.9
1.2
45° Siku
80
4.2
7.6
X
X
45° Siku
100
2.9
5.1
7.9
11.5
45° Siku
130
0.6
1.0
1.6
2.3
90° Siku
80
10.1 18.0
X
X
90° Siku
100
4.6
8.3
12.7
18.4
90° Siku
130
1.4
2.4
3.7
5.4
Kanggo digunakake kanggo Lochinvar diwenehake M & G air inlet komponen sistem resistance mung
CPM 144 n/an/a 1.9 n/an/a 3.5 n/an/a 8.4
CPM 175 n/an/a 2.8 n/an/a 5.1 n/an/a 12.1
Item
Ukuran Resistance (Pa) (mm)
CPM 58 CPM 77 CPM 96 CPM 116
Tabung lurus (saben meter)
80
4.0
7.1
X
X
Tabung lurus (saben meter) 100
1.1
2.0
3.0
4.4
Tabung lurus (saben meter) 130
0.3
0.5
0.7
1.1
45° Siku
80
3.7
6.5
X
X
45° Siku
100
2.5
4.4
6.8
9.9
45° Siku
130
0.5
0.9
1.4
2.0
90° Siku
80
8.7
15.6
X
X
90° Siku
100
4.0
7.1
11.0
16.0
90° Siku
130
1.2
2.1
3.2
4.7
Terminal knalpot vertikal
61.5 109.8
80
115.9
Terminal tunggal vertikal
–
–
–
–
Kanggo digunakake kanggo Lochinvar diwenehake M&G flue komponen sistem exhaust resistance mung
CPM 144 n/an/a 1.7 n/an/a 3.0 n/an/a 7.2 179.2 38.8
CPM 175 n/an/a 2.4 n/an/a 4.4 n/an/a 10.5 259.3 38.8
Gunakake tabel ing ngisor iki kanggo ngetung resistensi sistem flue.
knalpot bledug
Item tabung Lurus (m) 45° Siku 90° Siku
Jumlah Resistance Total
Air Inlet
Terminal Vertikal Konsentris
Total Resistance exhaust (Pa)
Item
Jumlah Resistance
Tabung lurus (m)
45° Siku
90° Siku
Air Inlet
Inlet udara tahan total (Pa)
Total Resistance inlet udara lan exhaust (Pa)
Total
Total resistensi sistem sing diwilang kudu kurang saka 200pa
Kaca 13 saka 19
KONVENSIONAL (Knalpot ONLY) SISTEM FLUE TIPE B23
CPM MODEL MAJLIS FLUE KONVENSIONAL CPM58, CPM77
Item No
Katrangan
Ora Dibutuhake CPM58
LV305030B
APPLIANCE AIR INTAKE GUARD Ø80/125mm
1
10.8
LM410084006
TERMINAL VERTIKAL – 130 MM PP
1
38.8
M85283
EXPANDER Ø80mm - Ø100mm PP
1
–
LM410084992
EXPANDER Ø100mm Ø130mm PP
1
–
Resistance maksimum ing sistem flue 200pa Total
51.8
CPM77 19.2 38.8 92.4
Item No. LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B
Katrangan Item Tambahan Flue
EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP TELESCOPIC BEND 45° 80mm PP 80mm PP BEND 90° W PP 80mmAMP Ø 80 mm
Ukuran 250mm 500mm 1000mm 2000mm
240-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/A
CPM MODEL MAJLIS FLUE KONVENSIONAL CPM96, CPM116
Ora
Item No
Katrangan
Dibutuhake CPM96
LV304872B
APPLIANCE AIR INTAKE GUARD Ø100/150mm
1
11.6
LM410084006
TERMINAL VERTIKAL 130 MM PP
1
38.8
Resistance maksimum ing sistem flue
200pa
Total
64.9
CPM116 16.8 38.8
94.06
CPM MODEL MAJLIS FLUE KONVENSIONAL CPM144, CPM175
Item No
Katrangan
Ora Dibutuhake CPM144 CPM175
M81660
APPLIANCE AIR INLET
1
KETEBALAN Ø 130 mm
LM410084006 TERMINAL VERTIKAL –
1
130 MM PP
8.7
12.6
38.8
38.8
Resistance maksimum ing sistem flue 200pa
Total
47.5
51.4
Item No M70242 M70251 M70252 M87195
Katrangan Item Tambahan Flue
EKSTENSI Ø130mm PP BEND 90° PP BEND 45° PP DINDING CLAMP
CPM58-CPM77 A=72.5mm, B=72.5mm CPM96-CPM116 A=78mm, B=65mm
Ukuran 1000mm 130mm 130mm 130mm
CPM58-CPM77 A=110mm, B=110mm CPM96-CPM116 A=78mm, B=65mm
Kaca 14 saka 19
KONVENSIONAL FLUE SIZING / Etungan
Item
Ukuran Resistance (Pa) (mm)
CPM 58 CPM 77 CPM 96 CPM 116
Tabung lurus (saben meter)
80
4.0
7.1
X
X
Tabung lurus (saben meter) 100
1.1
2.0
3.0
4.4
Tabung lurus (saben meter) 130
0.3
0.5
0.7
1.1
45° Siku
80
3.7
6.5
X
X
45° Siku
100
2.5
4.4
6.8
9.9
45° Siku
130
0.5
0.9
1.4
2.0
90° Siku
80
8.7
15.6
X
X
90° Siku
100
4.0
7.1
11.0
16.0
90° Siku
130
1.2
2.1
3.2
4.7
Terminal tunggal vertikal
–
–
–
–
Kanggo digunakake kanggo Lochinvar diwenehake M & G air inlet komponen sistem resistance mung
CPM 144 n/an/a 1.7 n/an/a 3.0 n/an/a 7.2 38.8
CPM 175 n/an/a 2.4 n/an/a 4.4 n/an/a 10.5 38.8
Gunakake tabel ing ngisor iki kanggo ngetung resistensi sistem flue.
Item
Jumlah Resistance
Tabung lurus (m)
45° Siku
90° Siku
Terminal Vertikal Konsentris
Total Resistance exhaust (Pa)
Total
Total resistensi sistem sing diwilang kudu kurang saka 200pa
Kaca 15 saka 19
SISTEM FLUE MENGGUNAKAN FLUE NOT DISEDITION BY LOCHINVAR TYPE C63
Umumé, boiler disertifikasi kanthi tujuan dhewe sing disedhiyakake sistem concentric utawa Twin Pipe, peralatan sing disertifikasi C63 ngidini installer nggunakake sistem flue liyane nalika nginstal boiler, nanging kudu standar minimal sing cocog karo tabel ing ngisor iki.
CE string Bahan gas buang
Suhu standar Eropa
kelas Tekanan kelas Resistance kanggo condensate
Karat n resistance
kelas s Metal: specifications liner
Soot tahan geni
class s Jarak kanggo combustible
Bahan Plastik: Plastik: prilaku geni Plastik:
min. yaiku PP EN 14471 T120
P1
W
min. eis RVS EN 1856-1 T120
P1
W
1
n/a
O
1
L20040
O
Bahan
Boiler
dnom
Doutside
disik
Linsert
SS
CPM58-CPM77 80 80 +0,3/ -0,7 81 +0,3/ -0,3 50 +2/ -2
SS
CPM96-CPM116 100 100 +0,3/ -0,7 101 +0,3/ -0,3 50 +2/ -2
SS CPM144-CPM175 130 130 +0,3/ -0,7 131 +0,5/ -0,5 50 +2/ -2
PP
CPM58-CPM77 80 80 +0,6/ -0,6
50 +20/ -2
PP
CPM96-CPM116 100 100 +0,6/ -0,6
50 +20/ -2
PP CPM144-CPM175 130 130 +0,9/ -0,9
50 +20/ -2
30
I saka EC/E
L
40
n/an/an/a
Pipa cerobong asap aluminium ora kena digunakake ing piranti iki amarga bisa nyebabake kegagalan penukar panas sing durung wayahe lan bakal ora sah babar pisan.
SISTEM COMMON FLUE
Lochinvar bisa nyedhiyakake header flue umum PP ndeleng pandhuan kapisah sing kasedhiya ing www.lochinvar.ltd.uk
Utawa, installer bisa nggunakake spesialis instalasi flue kanggo ngrancang lan nyuplai sistem flue sing kapisah miturut sebutan flue C63 nggunakake spesifikasi sing ditampilake ing kaca 13 lan informasi ing tabel ing ngisor iki.
Sembarang panginstalan nggunakake jinis flue C63 kudu dirancang lan diinstal ing tundhuk karo sembarang Building utawa planning peraturan lokal, nanging minangka sistem iki nggunakake sistem flue ora diwenehake dening Lochinvar, Lochinvar ora bisa menehi komentar / menehi saran utawa menehi support ing desain saka jinis sistem flue. Kanggo ngrancang sistem cerobong asap kasebut, pemasang/kontraktor kudu takon karo pemasok cerobong spesialis sing bakal tanggung jawab kanggo desain lan instalasi sistem saluran pembuangan sing kapisah. Nalika ngrancang sistem flue tipe C63, instruksi ing Manual Instalasi, sing diwenehake karo boiler, kudu digatekake. Lochinvar bakal nyedhiyani tokoh mundhut meksa kanggo Unit tartamtu, nanging liyane saka iku, Lochinvar ora bisa nyedhiyani support ing panjalukan Common Flue amarga sertifikat flue diwatesi kanggo kategori certified ing tabel ing kaca 2. Lochinvar ora bisa nampa tanggung jawab kanggo desain sistem Flue.
Tekanan sing kasedhiya ing outlet gas buang Laju Massa Gas Buang (G20) 96% (g/sec) Laju Massa Gas Buang (G20) 25% (g/dtk) Laju Massa Gas Buang (G31) 96% (g/dtk) Laju Massa Gas Buang (G31) 25% (g/dtk)
CPM 58
200Pa 22.6 5.7 23.2 5.8
CPM 77
200Pa 29.8 7.5 30.6 7.7
CPM 96
200Pa 37.1 9.3 38.8 9.7
CPM 116
200Pa 45.1 11.3 46.2 11.6
CPM 144
200Pa 55.6 13.9 57 14.3
CPM 175
200Pa 67.3 16.8 69 17.3
Range boiler CPM ora duwe Non Return Valve (NRV) internal amarga cerobong kasebut kudu dirancang kanthi tekanan nol utawa negatif kajaba NRV sing cocog dipasang lan yen perlu disambungake menyang piranti. Katup Non Return kalebu karo header flue umum Lochinvar.
Kaca 16 saka 19
FORMULIR ORDER lan cathetan
Item No.
Ora dibutuhake
Cathetan-Item kanggo pesenan
Cathetan
Hubungi layanan pelanggan Lochinvar kanggo pesen item flue tambahan ing 01295 269981
Kaca 17 saka 19
Kosong Kaca 18 saka 19
Kaca 19 saka 19
Dokumen / Sumber Daya
![]() |
Lochinvar CMP58 Kalebu CPM-SP Range [pdf] Pandhuan pangguna CMP58, CPM77, CPM96, CPM116, CPM146, CPM176, CMP58 Ora Klebu CPM-SP Range, CMP58, Ora Klebu CPM-SP Range, Klebu CPM-SP Range, CPM-SP Range |