Lochinvar CMP58 Kalebu Panuntun Panganggo Range CPM-SP

CMP58 Kalebu CPM-SP Range

Spesifikasi

  • Model sing dilindhungi: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 (Apa
    ora kalebu kisaran CPM-SP)
  • Disertifikasi kanggo digunakake ing kategori cerobong asap: B23, C13, C33, C43, C53,
    C63, C83

Pandhuan Panggunaan Produk

Sistem Flue Pipa Kembar Tipe C53

Kanggo sistem saluran asap kembar, tindakake ukuran lan pitungan
pedoman sing kasedhiya ing kaca 12 saka manual.

Sistem Flue Konvensional (Mung Knalpot) Tipe B23

Kanggo sistem saluran asap konvensional, deleng kaca 15 kanggo ukuran lan
instruksi pitungan.

Sistem Flue Nggunakake Flue Ora Disedhiyakake dening Lochinvar Tipe C63

Yen nggunakake flue ora diwenehake dening Lochinvar, tindakake pandhuan
mbatesi ing kaca 16 kanggo sistem flue umum.

FAQ

P: Standar apa sing kudu dipatuhi instalasi?

A: Kabeh panginstalan kudu tundhuk karo BS5440-1: 2023 kanggo
piranti nganti 70kW input net. Waca drawing 1 lan Tabel 1 kanggo
lokasi terminal.

“`

CPM Boiler range Flue Guide
Model sing dilindhungi: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 Ora kalebu kisaran CPM-SP

Isine
UMUM………………………………………………………………………………………………………………………… 2 Gambar 1 Lokasi terminal boiler……………………………………………………………………………………………….5 Tabel 1 Lokasi terminal boiler …………………………………………………………………………………………………..5 Tabel 2 Assessment risiko ………………………………………………………………………………………………………………………………….6
SISTEM FLUE KONSENTRIK ………………………………………………………………………………………………………………………7 Tipe Horizontal C13 …………………………………………………………………………………………………………………….7 Kit Plume kanggo nggunakake cerobong horisontal…………………………………………………………………………………………………….8 Tipe Vertikal C33…………………………………………………………………………………………………………………………………… 9 / Kalkulasi …………………………………………………………………………………………………………………………… 9 Konsentris………………………………………………………………………………………………………………………… 9
SISTEM SALURAN TWIN-PIPE TIPE C53 ……………………………………………………………………………………………………………11 Ukuran/perhitungan Flue-Pipa Kembar……………………………………………………………………………………..12
SISTEM SALURAN KONVENSIONAL (KUMUR) JENIS B23…………………………………………………………………….14 Ukuran/perhitungan cerobong konvensional……………………………………………………………………………………15
SISTEM FLUE MENGGUNAKAN FLUE NOT SUPPLY BY LOCHINVAR TYPE C63………………………………………………………………..16 SISTEM FLUE COMMON ………………………………………………………………………………………………………………..16 FORMULIR PESANAN DAN CATATAN …………………………………………………………………………………………………………….17
Kaca 1 saka 19

UMUM

Boiler CPM Lochinvar disertifikasi kanggo digunakake ing kategori flue ing ngisor iki:

Tipe Instalasi Kategori

Katrangan

B23

Bukak cerobong asap

Piranti sing dimaksudake kanggo disambungake menyang cerobong asap sing ngevakuasi produk pembakaran menyang njaba ruangan sing ngemot piranti kasebut. Udara pembakaran ditarik langsung saka kamar.

C13

Flue Tertutup

Piranti sing disambungake menyang sistem saluran buang konsentris utawa pipa kembar kanthi terminal saluran horisontal. Loro-lorone inlet udara lan exhaust kudu ana ing zona tekanan sing padha.

C33

Flue Tertutup

Piranti sing disambungake menyang sistem saluran asap konsentris utawa pipa kembar kanthi terminal saluran alur Vertikal. Loro-lorone inlet udara lan exhaust kudu ana ing zona tekanan sing padha.

Piranti sing disambungake menyang inlet udara umum lan sistem exhaust flue, sing dirancang kanggo luwih saka

C43

Ditutup Flue siji piranti. Sistem umum iki duwe siji inlet online lan exhaust flue lan minangka bagéan saka bangunan ora

piranti.

C53

Flue Tertutup

Piranti sing disambungake menyang sistem saluran asap kembar kanthi terminal saluran alur Horizontal utawa Vertikal. Inlet udara lan knalpot bisa uga ana ing zona tekanan sing beda.

Piranti sing dimaksudake kanggo disambungake menyang sistem sing disetujoni lan dipasarake kanthi kapisah kanggo nyedhiyakake

C63

Udhara pembakaran cerobong tertutup lan metune produk pembakaran (kayata liyane saka sing disedhiyakake dening pemanas banyu

pabrikan).

Piranti sing disambungake liwat salah sawijining saluran menyang sistem saluran siji utawa umum. Sistem saluran iki kalebu

C83

Flue Tertutup

saka saluran konsep alam tunggal (yaiku ora nggabungake penggemar) sing ngevakuasi produk pembakaran. Piranti kasebut disambungake liwat saluran liya menyang terminal, sing nyedhiyakake hawa menyang piranti kasebut

saka njaba bangunan.

Kabeh instalasi kudu tundhuk karo syarat:
1. Kanggo piranti nganti 70kW input net- BS5440-1: 2023- Flueing lan ventilasi kanggo peralatan gas saka input dirating ora ngluwihi 70 kW net (1st, 2nd lan 3 gas kulawarga). Spesifikasi kanggo instalasi peralatan gas menyang cerobong asep lan kanggo pangopènan cerobong asep. a. Deleng gambar 1 lan tabel 1 kanggo rincian lokasi terminal.
2. Kanggo Perkakas liwat 70kW input net- IGEM / UP / 10 Edition 4 + A: 2016 - Instalasi peralatan gas flued ing latar industri lan komersial, manungsa waé tartamtu kudu mbayar kanggo bagean ing ngisor iki. a. Deleng gambar 1 lan tabel 1 kanggo rincian lokasi terminal. b. Penghentian horisontal kudu ditemokake miturut jarak minimal sing diwenehake ing tabel 1, lan tundhuk karo kriteria penilaian risiko sing ditampilake ing tabel 2. c. Terminasi cerobong horisontal (saliyane kanggo sistem pengenceran kipas) ora kena dipasang kanggo piranti siji utawa klompok piranti kanthi input nett total ngluwihi input panas netto 333kW. d. Kanggo piranti siji utawa klompok piranti kanthi total input panas net ngluwihi 333 kW, syarat umum IGEM / UP / 10 Edition 4 + A: 2016 kudu ditrapake lan disetujoni saka Panguwasa Lokal sadurunge wiwitan instalasi.
3. Undhang-undhang Udara Resik kanggo instalasi sing ngluwihi input nett 333kW.

Kaca 2 saka 19

GAMBAR 1 LOKASI TERMINAL BOILER MUTU BS5440-1-2023

TABEL 1 LOKASI TERMINAL BOILER SESUAI BS5440-1-2023

Katrangan lokasi

A

Langsung ing ngisor bukaan, bata udara, jendhela mbukak lsp.

B

Ndhuwur bukaan, bata udara, jendhela mbukak lsp.

C

Horisontal menyang bukaan, bata udara, jendhela mbukak lsp.

D

Ing ngisor selokan utawa pipa sanitasi

E

Ing ngisor eaves

F

Ing ngisor atap loteng utawa port mobil

G

Saka saluran vertikal utawa pipa lemah

H

Saka sudhut internal utawa njaba

I

Ndhuwur lemah, atap utawa loteng

J

Saka permukaan sing madhep terminal

K

Saka terminal madhep terminal

L

Saka bukaan ing port mobil (contone, lawang, jendhela) menyang omah

M

Vertikal saka terminal ing tembok sing padha

N

Horisontal saka terminal ing tembok sing padha

O

Horisontal saka inlet udara mekanik ing tembok sing padha

P

Saka struktur vertikal ing atap

Q

Ndhuwur prapatan karo gendheng

R

Diagonal ngliwati bukaan menyang bangunan ing tembok sing beda

S

Terminal vertikal saka terminal vertikal liyane

T

Terminal vertikal sing cedhak karo bukaan menyang bangunan

U

Terminal vertikal saka tembok

V

Terminal bebarengan wates

W

Terminal madhep wates

X

Jejer kanggo bukaan menyang bangunan ing gendheng pitched

Y

Terminal madhep bukaan menyang bangunan

* Hubungi dhukungan teknis Lochinvar kanggo bantuan.

CPM58

mm

300

mm

300

mm

300

mm

75

mm

300

mm

200

mm

150

mm

300

mm

300

mm

600

mm

1200

mm

1200

mm

1500

mm

300

mm

1000

mm

N/A

mm

300

mm

600

mm

600

mm

1500

mm

500

mm

300

mm

600

mm

*

mm

2000

Kaca 3 saka 19

TABEL 2 PENILAIAN RISIKO MENURUT BS5440-1-2023
Luwih saka syarat ing BS5440-1: 2023 Lampiran D lan Gambar C.8, tabel C.1 pambiji resiko ing ngisor iki menehi tuntunan kanggo posisi flues horisontal. Formulir iki kudu diisi sadurunge karya diwiwiti lan ditindakake dening wong sing kompeten kanggo nindakake penilaian risiko.

Perkakas Tipe C kanthi input panas netto ora ngluwihi 70kW Assessment risiko discharge cerobong tingkat rendah (kalebu input panas netto kanggo klompok peralatan)

No Babagan posisi flue

Ora Ya

1 Apa terminal flue bakal nglanggar posisi sing ditemtokake ing tabel C.1 kanggo stopkontak cerobong asep sing disegel?

Ora Ya

2

Apa terminal kasebut bakal dilebokake ing posisi sing bakal ngidini produk pembakaran bisa dibentuk (contone, ditutupi dening struktur sing cedhak)?

Ora

ya wis

3 Apa mandap ing sumur cahya?

Ora Ya

4 Apa mandap ing carport tanpa loro sisih unobstructed?

Ora Ya

5 Apa mandhek bakal ana ing wilayah sing bisa uga ana bahan sing gampang kobong ing sacedhake?

Ora Ya

6 Apa mandhek bakal ana ing wilayah sing bisa duwe bahan mbebayani ing sacedhake (contone, petrokimia)?

Ora Ya

7 Apa mandhek bakal ana ing dalan sing ditutupi? 8 Apa ana larangan sing mandhegake pas penjaga terminal yen dibutuhake? 9 Apa penghentian bakal ngliwati wates?

Ora Ya Ora Ya Ora Ya

10 Apa kit manajemen plume dibutuhake kanggo ngubengi jarak mandap kaya sing dibutuhake ing tabel C.1?

Ora Ya

Nomer 11 12
Ora.

Pertimbangan gangguan Apa mandap dumunung ing dalan sing bisa nyebabake gangguan (contone, dhuwur sirah utawa pluming menyang pangguna)? Apa penghentian kasebut bisa nyebabake gangguan kanggo tanggane? Rute cerobong asap / cerobong asap Bakal dipasang ing kekosongan sing ora bisa nyukupi pemeriksaan visual sing lengkap?

Ora Ya
Ora Ya
Ora Ya Ora Ya Ora Ya

Apa ana watesan sing bakal nyegah flue didhukung ing kabeh dawa?

Ora Ya

Apa bahan cerobong asap nglanggar peraturan bangunan (contone, bangunan beresiko dhuwur)?

Ora Ya

Apa rute flue bakal ngliwati wilayah sing dilindhungi geni tanpa kemampuan kanggo njaga perlindungan kasebut?

Ora Ya

Apa flue bakal ngliwati omah liyane?
Apa cerobong asap bisa rusak amarga rute/lokasi (contone, bahan sing disimpen ing ruangan tanduran utawa gudang)?

Ora Ya Ora Ya

Apa flue mengaruhi integritas struktur ing (contone, lintel, nampan rongga, alangan, utawa membran)?

Ora Ya

Yen kabeh jawaban biru, mula posisi flue kudu cocog

Yen ana jawaban oranye, mula posisi cerobong asap ora cocog, coba revisi posisi utawa jinis outlet asap utawa hubungi petugas Kesehatan Lingkungan lokal kanggo pitulung lan/utawa persetujuan.

Kaca 4 saka 19

GAMBAR 2 LOKASI TERMINAL BOILER MENURUT IGEM/UP/10 EDISI 4 +A: 2016

TABEL 3 LOKASI TERMINAL BOILER MENURUT IGEM/UP/10 EDISI 4 +A: 2016

Katrangan lokasi

A

Langsung ing ngisor bukaan, bata udara, jendhela mbukak lsp.#

B

Ndhuwur bukaan, bata udara, jendhela mbukak lsp.

C

Horisontal menyang bukaan, bata udara, jendhela mbukak lsp.#

D

Ing ngisor selokan utawa pipa sanitasi

E

Ing ngisor eaves

F

Ing ngisor atap loteng utawa port mobil

G

Saka saluran vertikal utawa pipa lemah

H

Saka sudhut internal utawa njaba

I

Ndhuwur lemah, atap utawa loteng

J

Saka permukaan sing madhep terminal

K

Saka terminal madhep terminal

L

Saka bukaan ing port mobil (eg lawang, jendhela) menyang omah

M

Vertikal saka terminal ing tembok sing padha

N

Horisontal saka terminal ing tembok sing padha

N+

Vertikal saka terminal ing gendheng padha

P

Saka struktur vertikal ing atap

Q

Ndhuwur prapatan karo gendheng

CPM77 CPM96 CPM116 CPM144 CPM175

mm 2500

2500

2500

2500

2500

mm

631

760

896

1092

1294

mm

631

760

896

1092

1294

mm

200

200

200

200

200

mm

200

200

200

200

200

mm

Ora dianjurake kanggo ndeleng penilaian risiko UP10

mm

150

150

150

150

150

mm 1099

1513

1948

2573

3220

mm

300

300

300

300

300

mm 1100

1514

1948

2573

3220

mm 2083

2429

2792

3314

3855

mm

Ora dianjurake kanggo ndeleng penilaian risiko UP10

mm 2500

2500

2500

2500

2500

mm

600

600

900

900

n/a*

600

600

900

900

n/a*

mm 1500

1500

1500

1500

1500

mm

311

359

409

481

556

*Hubungi dhukungan teknis Lochinvar kanggo pandhuan babagan mandap CPM175.
Tabel ing ndhuwur kudu digunakake magepokan karo cathetan ing ngisor iki: · Jarak ditampilake njamin ketel bakal operate tanpa masalah ing paling kahanan, jarak iki bisa suda ing kahanan tartamtu · Ndhuwur kudu maca magepokan karo edition paling anyar saka BS5440-1 lan IGEM UP10 · Kanggo instalasi boiler ndhuwur 333kW kudu resik lan udhara ing ndhuwur kudu dilebokake ing instalasi, lan ing ndhuwur kudu resik. tundhuk karo syarate kanthi lengkap, hubungi tim kesehatan lingkungan lokal kanggo pandhuan luwih lanjut
Kanggo pandhuan luwih lengkap, hubungi dhukungan Teknis Lochinvar
Kaca 5 saka 19

Tabel 4 penilaian risiko Tabel ing ngisor iki minangka kutipan saka IGEMUP10 lan kudu digunakake bebarengan karo dokumen kasebut
Luwih saka syarat ing IGEM / UP / 10 Edition 4 +A: 2016 bagean 8 ing klausa 8.7.3.3 lan Figure 7 Assessment resiko ing ngisor iki menehi panuntun dhumateng kanggo posisi saka flues horisontal. Formulir iki kudu diisi sadurunge karya diwiwiti lan ditindakake dening wong sing kompeten kanggo nindakake penilaian risiko.

Perkakas Tipe C kanthi input panas netto ngluwihi 70 kW lan ora ngluwihi 333 kW evaluasi risiko discharge cerobong rendah (kalebu input panas netto kanggo klompok peralatan)

Ora.

Babagan posisi flue

Ora

ya wis

Apa penghentian cerobong sing diusulake ing jarak ing Gambar K saka dalan, dalan,

1

track, thoroughfare, walkway, wates property utawa wilayah, kang digunakake kanggo umum

Ora

ya wis

akses umum liyane saka kanggo tujuan pangopènan?

2

Apa penghentian saluran sing diusulake ing jarak ing Gambar K menyang papan dolanan,

Ora

ya wis

sekolah, pekarangan, area lenggahan, utawa area sing bisa dadi kumpul umum

3

Yen mandap flue ngajokaken terlampir ing luwih saka loro-lorone banjur nindakaken

Ora

ya wis

tundhuk karo syarat Gambar 11B?

Apa mandap flue ngajokaken ing kadohan ing Figure K saka lumahing utawa

4

unsur bangunan sing bisa kena pengaruh korosi utawa rusak saka plume

Ora

ya wis

kondensat?

5

Apa posisi flue sing diusulake ing wilayah sing bisa diparkir kendaraan

Ora

ya wis

jarak saka Figure 12 Line G kanggo flue?

6

Apa ana semak utawa wit ing jarak minimal sing dituduhake ing Gambar K

Ora

ya wis

posisi terminal sing diusulake?

7

Apa mandap flue sing diusulake ing sumur cahya?

Ora

ya wis

Apa produk pembakaran saka posisi cerobong asap sing diusulake bisa dikumpulake

8

ing kahanan atmosfer unfavorable, amarga aliran salib miskin saka online disebabake

Ora

ya wis

enclosures utawa struktur jejer lan / utawa kamungkinan kanggo nimbulaké gangguan?

9

Apa posisi terminasi flue bisa nyebabake gangguan ing properti sing ana ing jejere?

Ora

ya wis

Peraturan Bangunan Bagian J

10

Apa mandap flue sing diusulake kurang saka 300 mm saka wates properti, sing diukur saka sisih terminal menyang wates?

Ora

ya wis

Bab Undhang-undhang Udara Bersih

11

Apa output total saka individu, utawa klompok terminal flue (yen ing 5U (ndeleng A3.7)), luwih saka 333 kW input panas net?

Ora

ya wis

Umum

12

Apa ana pertimbangan liyane sing dibutuhake kanggo pambiji risiko iki, deleng sheet kapisah.

Ora

ya wis

13

Komentar:

Yen kabeh jawaban Biru banjur posisi cerobong asap kudu cocog Yen ana jawaban Oranye banjur posisi cerobong asap ora cocog, coba revisi posisi utawa jinis stopkontak cerobong utawa hubungi petugas Kesehatan Lingkungan lokal kanggo pitulungan lan/utawa persetujuan.
INFORMASI BOILER FLUE

Nomer Model FLUE DATA TIPE B23 Diameter cerobong nominal Suhu gas cerobong maksimum Suhu gas buang Persyaratan draft cerobong Tekanan kasedhiya kanggo sistem cerobong Volume gas buang maksimum TIPE DATA FLUE C13 & C33 Diameter cerobong nominal Suhu gas buang maksimum TIPE DATA FLUE C43 & C53 Suhu cerobong nominal maksimum.

mm °C °C mbar Pa g/s
mm °C
mm °C

CPM58

CPM77

80

5.59 kanggo 28.9 6.52 kanggo 38.6 80/125
80

CPM96

CPM116

CPM144

CPM175

100 95 85-95 -0.03 kanggo -0.1 200 7.69 kanggo 47.9 11.6 kanggo 57.7

130 15.2 kanggo 71.7 20.1 kanggo 86.2

100/150 95

100

130

95

Kaca 6 saka 19

SISTEM FLUE CONCENTRIC

JENIS HORIZONTAL C13

CPMH001 MODEL KOMPUTER FLUE HORIZONTAL KONSENTRIK – CPM58, CPM77

Item No

Katrangan

Klebu CPM58

LV310757 TERMINAL HORIZONTAL KONSENTRIK – Ø80/125mm PP

1

44.8

M28925B

TERMINAL DINDING PLAT

1

LV310735

KONSENTRIK BEND 90° Ø80/125mm PP

1

16.1

Resistance maksimum ing sistem flue 200pa

Total 60.9

CPM77 80.1 28.7 108.8

Nomer Item LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M84481B

Item Tambahan Flue Katrangan EMBUNG KONSENTRIK – Ø80/125mm PP EMBUNG KONSENTRIK TETAP – Ø80/125mm EKSTENSI KONSENTRASI PP – Ø80/125mm PP KONSENTRASI TETAP – Ø80/125mm – 80/125mm PP KONSENTRASI TETAP C. TELESCOPIC KONSENTRIK BEND 45° Ø80/125mm PP KONSENTRIK BEND 90° Ø80/125mm PP DINDING CLAMP Ø 125 mm

Ukuran 250mm 500mm 1000mm 2000mm
240mm-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/A

CPMH003 MODEL KOMPUTER FLUE HORIZONTAL KONSENTRIK – CPM96, CPM116

Item No

Katrangan

Klebu CPM96 CPM116

LV310758B TERMINAL HORIZONTAL KOSENTRIK Ø100/150mm PP

1

58

84

M84410B BEND KONSENTRIK 90° Ø100/150mm PP RADIUS PENDEK

1

23.6

34.2

Resistance maksimum ing sistem flue 200pa

Gunggunge 81.6 118.2

CPMH004 MODEL MAJLIS FLUE HORIZONTAL KOSENTRIK – CPM144

Item No

Katrangan

Klebu

LV310758B

TERMINAL HORIZONTAL KONSENTRIK Ø100/150mm PP

1

E61-001-172B

KIT KONVERSI KONSENTRIK

1

M84410B

BEND KONSENTRIK 90° Ø100/150mm PP RADIUS SINGKAT

1

Resistance maksimum ing sistem flue 200pa

Total

CPM144 129.9 52.9 182.8

Item No. M84405B M84402B M84412B M84413B M84421B M87196B

Katrangan Item Tambahan Flue
EKSTENSI KONSENTRIK Ø100/150mm Meja potong EKSTENSI KONSENTRIK Ø100/150mm PP TETAP
KONSENTRIK BEND 90° Ø100/150mm PP BEND KONSENTRIK 45° Ø100/150mm PP
SAMPLING POINT Ø100/150mm PP DINDING CLAMP Ø 150 mm

CPM58-77 A=45mm B=62.5mm

Ukuran 500 mm 1000 mm
Waca Drawing Ngisor Waca Drawing Ngisor
115 mm
CPM58-77 A=95mm B=110mm

CPM96-175 A=128mm B=128mm

CPM96-175 A=223mm B=208mm

Kaca 7 saka 19

PLUME KIT kanggo nggunakake karo FLUE HORIZONTAL

PLUME MANAGEMENT KIT LG800008B PLUME MANAGEMENT KIT Ø80/125mm LG800009B PLUME MANAGEMENT KIT Ø100/150mm

Ora

Katrangan

1 TENGKOK KONSENTRIK 90°-PP

2 KONSENTRIK HORIZONTAL PLUME KIT TERMINAL -PP

3 EXTENSION -PP CUTABLE (1000mm)

4 BEND 90°-PP

5 PLUME KIT MANUK GUARD

6 PLUME KIT FLUE EXIT-PP

7 TEMBUNG CLAMP

DIAMETER INTERNAL

B DIAMETER EKSTERNAL

CPM58 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm

CPM77 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm

CPM96 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm

CPM116 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm

CPM144 N/AN/AN/AN/AN/AN/AN/AN/AN/A

CPM175 N/AN/AN/AN/AN/AN/AN/AN/AN/A

Kit plume kudu ora digunakake kanggo mbenerake lokasi terminal ilegal

Kaca 8 saka 19

JENIS VERTIKAL C33

CPMV001 MODEL assembly VERTIKAL KONSENTRIK – CPM58, CPM77

No item LV310753 LV310745B

Deskripsi TERMINAL VERTIKAL KONSENTRIK – Ø80/125mm PP EKSTENSI KONSENTRIK – Ø80/125mm PP (500mm)

Kalebu 11

CPM58 61.5 5.1

LV310742B EKSTENSI KONSENTRIK – Ø80/125mm PP TETAP (1000mm)

1

10.2

Resistance maksimum ing sistem flue 200pa

Total 76.8

CPM77 109.8 9.05 18.1 136.95

Nomer item LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M87195B LV302520

Item Tambahan Flue
Deskripsi KONSENTRASI KONSENTRASI – Ø80/125mm PP KONSENTRASI KONSENTRASI TETAP – Ø80/125mm PP KONSENTRASI KONSENTRASI – Ø80/125mm PP KONSENTRASI TETAP – Ø80/125mm PP KONSENTRASI TETAP KONSENTRASI 80/1PI2 - 5mm 45° Ø80/125mm PP KONSENTRIK BEND 90° Ø80/125mm PP DINDING CLAMP Ø130mm atap datar kerlip Ø140mm ALU

Ukuran 250mm 500mm 1000mm 2000mm
240-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/AN/A

CPMV003 MODEL assembly VERTIKAL KONSENTRIK – CPM96, CPM116

Item No

Katrangan

Klebu CPM96

LV310754B

TERMINAL VERTIKAL KONSENTRIK Ø100/150mm PP

1

80

M84405B KONSENTRIK EKSTENSI Ø100/150mm (500mm) Cuttable

1

6.5

M84402B EKSTENSI KONSENTRIK Ø100/150mm (1000mm) PP TETAP

1

13

Resistance maksimum ing sistem flue 200pa

Total 99.5

CPM116 115.9 9.45 18.9 144.25

Item No. M84405B M84402B M84412B M84413B M84421B M87196B

Item Tambahan Flue
Deskripsi KONSENTRASI KONSENTRASI Ø100/150mm Meja potong KONSENTRIK KONSENTRASI Ø100/150mm PP TETAP KONSENTRIS BEND 90° Ø100/150mm PP KONSENTRIK BEND 45° Ø100/150mm PP SAMPLING POINT Ø100/150mm PP DINDING CLAMP Ø 150 mm

Ukuran 500 mm 1000 mm
Waca Drawing Ngisor Waca Drawing Ngisor
115 mm

CPM58-77 A=45mm B=62.5mm
CPM96-175 A=128mm B=128mm

CPM58-77 A=95mm B=110mm
CPM96-175 A=223mm B=208mm

Flue konsentris ora bisa digunakake karo CPM175

Kaca 9 saka 19

KONSENTRIK FLUE SIZING / Etungan

Resistance ing Pa

Item

CPM 58 80/125 CPM 77 80/125 CPM 96 100/150 CPM 116 100/150

Terminal tembok

44.8

80.1

58

84

Terminal gendheng

61.5

109.8

80

115.9

Tabung lurus (m)

10.2

18.1

13.0

18.9

45° Siku

8.6

15.4

15.5

22.4

90° Siku

16.1

28.7

23.6

34.2

Paket Plume

10

10

20

25

Kanggo digunakake kanggo Lochinvar diwenehake M & G komponen sistem flue resistance mung

CPM 144 100/150 129.9 179.2 29.2 34.7 52.9 n/a

CPM 175 100/150 188 259.3 42.2 50.2 76.5 n/a

Gunakake tabel ing ngisor iki kanggo ngetung total resistance sistem flue

Item

Jumlah Resistance Total

Terminal tembok Terminal atap Tabung lurus (m) 45° Siku 90° Siku Plume kit

Total Resistance (Pa)

Total resistensi sistem sing diwilang kudu kurang saka 200pa

Kaca 10 saka 19

SISTEM SALURAN KEMBAR JENIS C53

CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM58, CPM77

Flue Vertikal

Item No

Katrangan

Ora Dibutuhake CPM58 CPM77

LM410084006

1

TERMINAL VERTIKAL – 130 MM PP

38.8 38.8

LV305016

1

INLET UDARA HORIZONTAL Ø80mm

M28925B

1

PLAT DINDING TERMINAL (PASANGAN)

M85283 LM410084992

EXPANDER Ø80mm - Ø100mm PP
EXPANDER Ø100mm - Ø130mm PP

Resistance maksimum ing sistem flue 200pa

1 1 Total

38.8 38.8

CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM58, CPM77

Flue Horizontal

Ora

Item No

Katrangan

Dibutuhake CPM58

LV310757B

TERMINAL HORIZONTAL KONSENTRIK Ø80/125mm PP

1

29.86

LV305016

INLET UDARA HORIZONTAL Ø80mm

1

M28925B

PLAT DINDING TERMINAL (PASANGAN)

1

Resistance maksimum ing sistem flue

200pa

Total

29.86

CPM77 53.4
53.4

Item No. LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B

Katrangan Item Tambahan Flue
EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP TELESCOPIC BEND 45° 80mm PP 80mm PP BEND 90° W PP 80mmAMP Ø 80 mm

Ukuran 250mm 500mm 1000mm 2000mm
240-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/A

CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM96, CPM116

Flue Vertikal

Nomer Barang LM410084006

Katrangan
TERMINAL VERTIKAL 130 MM PP

Ora Perlu 1

CPM96 38.8

LV305039

INLET UDARA HORIZONTAL

1

Ø 100 mm

M28925B

DINDING TERMINAL

1

PLAT (PASANGAN)

LM410084992 EXPANDER Ø100mm -

1

Ø 130 mm PP

Resistance maksimum ing sistem flue 200pa

Total

38.8

CPM116 38.8

38.8

Kaca 11 saka 19

CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM96, CPM116

Flue Horizontal

Ora

Item No

Katrangan

Dibutuhake CPM96

KONSENTRIK

LV310758B

TERMINAL HORIZONTAL

1

38.66

Ø 100/150 mm PP

LV305039B

INLET UDARA HORIZONTAL Ø100mm ALU

1

Resistance maksimum ing sistem flue 200pa

Total 38.66

CPM116 56
56

Nomer Item M85176B M85177B M85181B M85182B M87193B

Item Tambahan Flue Keterangan EXTENSION Ø100mm PP CUT TO LENGTH EXTENSION Ø100mm PP CUT TO LENGTH BEND 90° 100mm PP BEND 45° 100mm PP WALL BAND (100mm)

Ukuran 500 mm 1000 mm
Waca Drawing Ngisor Waca Drawing Ngisor
n/a

CPM MODEL PERAKITAN BALUNGAN KEMBALI PIPA CPM CPM144, CPM175

Flue Vertikal

Item No

Katrangan

Ora Dibutuhake CPM144

LM410084006 TERMINAL VERTIKAL –

1

38.8

130 MM PP

LV307178

INLET UDARA HORIZONTAL

1

Ø 130 mm ALU

Resistance maksimum ing sistem flue 200pa

Total

38.8

CPM175 38.8

38.8

Item No M70242 M70251 M70252 M87195

Katrangan Item Tambahan Flue
EKSTENSI Ø130mm PP BEND 90° PP BEND 45° PP DINDING CLAMP

Ukuran 1000mm 130mm 130mm 130mm

CPM58CPM77 A=72.5mm, B=72.5mm
CPM96CPM116 A=78mm, B=65mm

CPM58CPM77 A=110mm, B=110mm
CPM96CPM116 A=78mm, B=65mm

Kaca 12 saka 19

TWIN-PIPE FLUE SIZING / Etungan

Item

Ukuran Resistance (Pa) (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Tabung lurus (saben meter)

80

4.6

8.2

X

X

Tabung lurus (saben meter) 100

1.3

2.3

3.5

5.0

Tabung lurus (saben meter) 130

0.3

0.6

0.9

1.2

45° Siku

80

4.2

7.6

X

X

45° Siku

100

2.9

5.1

7.9

11.5

45° Siku

130

0.6

1.0

1.6

2.3

90° Siku

80

10.1 18.0

X

X

90° Siku

100

4.6

8.3

12.7

18.4

90° Siku

130

1.4

2.4

3.7

5.4

Kanggo digunakake kanggo Lochinvar diwenehake M & G air inlet komponen sistem resistance mung

CPM 144 n/an/a 1.9 n/an/a 3.5 n/an/a 8.4

CPM 175 n/an/a 2.8 n/an/a 5.1 n/an/a 12.1

Item

Ukuran Resistance (Pa) (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Tabung lurus (saben meter)

80

4.0

7.1

X

X

Tabung lurus (saben meter) 100

1.1

2.0

3.0

4.4

Tabung lurus (saben meter) 130

0.3

0.5

0.7

1.1

45° Siku

80

3.7

6.5

X

X

45° Siku

100

2.5

4.4

6.8

9.9

45° Siku

130

0.5

0.9

1.4

2.0

90° Siku

80

8.7

15.6

X

X

90° Siku

100

4.0

7.1

11.0

16.0

90° Siku

130

1.2

2.1

3.2

4.7

Terminal knalpot vertikal

61.5 109.8

80

115.9

Terminal tunggal vertikal

Kanggo digunakake kanggo Lochinvar diwenehake M&G flue komponen sistem exhaust resistance mung

CPM 144 n/an/a 1.7 n/an/a 3.0 n/an/a 7.2 179.2 38.8

CPM 175 n/an/a 2.4 n/an/a 4.4 n/an/a 10.5 259.3 38.8

Gunakake tabel ing ngisor iki kanggo ngetung resistensi sistem flue.

knalpot bledug

Item tabung Lurus (m) 45° Siku 90° Siku

Jumlah Resistance Total

Air Inlet

Terminal Vertikal Konsentris

Total Resistance exhaust (Pa)

Item

Jumlah Resistance

Tabung lurus (m)

45° Siku

90° Siku

Air Inlet

Inlet udara tahan total (Pa)

Total Resistance inlet udara lan exhaust (Pa)

Total

Total resistensi sistem sing diwilang kudu kurang saka 200pa

Kaca 13 saka 19

KONVENSIONAL (Knalpot ONLY) SISTEM FLUE TIPE B23

CPM MODEL MAJLIS FLUE KONVENSIONAL CPM58, CPM77

Item No

Katrangan

Ora Dibutuhake CPM58

LV305030B

APPLIANCE AIR INTAKE GUARD Ø80/125mm

1

10.8

LM410084006

TERMINAL VERTIKAL – 130 MM PP

1

38.8

M85283

EXPANDER Ø80mm - Ø100mm PP

1

LM410084992

EXPANDER Ø100mm Ø130mm PP

1

Resistance maksimum ing sistem flue 200pa Total

51.8

CPM77 19.2 38.8 92.4

Item No. LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B

Katrangan Item Tambahan Flue
EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP TELESCOPIC BEND 45° 80mm PP 80mm PP BEND 90° W PP 80mmAMP Ø 80 mm

Ukuran 250mm 500mm 1000mm 2000mm
240-360mm Waca Drawing Ngisor Waca Drawing Ngisor
N/A

CPM MODEL MAJLIS FLUE KONVENSIONAL CPM96, CPM116

Ora

Item No

Katrangan

Dibutuhake CPM96

LV304872B

APPLIANCE AIR INTAKE GUARD Ø100/150mm

1

11.6

LM410084006

TERMINAL VERTIKAL 130 MM PP

1

38.8

Resistance maksimum ing sistem flue

200pa

Total

64.9

CPM116 16.8 38.8
94.06

CPM MODEL MAJLIS FLUE KONVENSIONAL CPM144, CPM175

Item No

Katrangan

Ora Dibutuhake CPM144 CPM175

M81660

APPLIANCE AIR INLET

1

KETEBALAN Ø 130 mm

LM410084006 TERMINAL VERTIKAL –

1

130 MM PP

8.7

12.6

38.8

38.8

Resistance maksimum ing sistem flue 200pa

Total

47.5

51.4

Item No M70242 M70251 M70252 M87195

Katrangan Item Tambahan Flue
EKSTENSI Ø130mm PP BEND 90° PP BEND 45° PP DINDING CLAMP
CPM58-CPM77 A=72.5mm, B=72.5mm CPM96-CPM116 A=78mm, B=65mm

Ukuran 1000mm 130mm 130mm 130mm
CPM58-CPM77 A=110mm, B=110mm CPM96-CPM116 A=78mm, B=65mm

Kaca 14 saka 19

KONVENSIONAL FLUE SIZING / Etungan

Item

Ukuran Resistance (Pa) (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Tabung lurus (saben meter)

80

4.0

7.1

X

X

Tabung lurus (saben meter) 100

1.1

2.0

3.0

4.4

Tabung lurus (saben meter) 130

0.3

0.5

0.7

1.1

45° Siku

80

3.7

6.5

X

X

45° Siku

100

2.5

4.4

6.8

9.9

45° Siku

130

0.5

0.9

1.4

2.0

90° Siku

80

8.7

15.6

X

X

90° Siku

100

4.0

7.1

11.0

16.0

90° Siku

130

1.2

2.1

3.2

4.7

Terminal tunggal vertikal

Kanggo digunakake kanggo Lochinvar diwenehake M & G air inlet komponen sistem resistance mung

CPM 144 n/an/a 1.7 n/an/a 3.0 n/an/a 7.2 38.8

CPM 175 n/an/a 2.4 n/an/a 4.4 n/an/a 10.5 38.8

Gunakake tabel ing ngisor iki kanggo ngetung resistensi sistem flue.

Item

Jumlah Resistance

Tabung lurus (m)

45° Siku

90° Siku

Terminal Vertikal Konsentris

Total Resistance exhaust (Pa)

Total

Total resistensi sistem sing diwilang kudu kurang saka 200pa

Kaca 15 saka 19

SISTEM FLUE MENGGUNAKAN FLUE NOT DISEDITION BY LOCHINVAR TYPE C63
Umumé, boiler disertifikasi kanthi tujuan dhewe sing disedhiyakake sistem concentric utawa Twin Pipe, peralatan sing disertifikasi C63 ngidini installer nggunakake sistem flue liyane nalika nginstal boiler, nanging kudu standar minimal sing cocog karo tabel ing ngisor iki.

CE string Bahan gas buang
Suhu standar Eropa
kelas Tekanan kelas Resistance kanggo condensate
Karat n resistance
kelas s Metal: specifications liner
Soot tahan geni
class s Jarak kanggo combustible
Bahan Plastik: Plastik: prilaku geni Plastik:

min. yaiku PP EN 14471 T120

P1

W

min. eis RVS EN 1856-1 T120

P1

W

1

n/a

O

1

L20040

O

Bahan

Boiler

dnom

Doutside

disik

Linsert

SS

CPM58-CPM77 80 80 +0,3/ -0,7 81 +0,3/ -0,3 50 +2/ -2

SS

CPM96-CPM116 100 100 +0,3/ -0,7 101 +0,3/ -0,3 50 +2/ -2

SS CPM144-CPM175 130 130 +0,3/ -0,7 131 +0,5/ -0,5 50 +2/ -2

PP

CPM58-CPM77 80 80 +0,6/ -0,6

50 +20/ -2

PP

CPM96-CPM116 100 100 +0,6/ -0,6

50 +20/ -2

PP CPM144-CPM175 130 130 +0,9/ -0,9

50 +20/ -2

30

I saka EC/E

L

40

n/an/an/a

Pipa cerobong asap aluminium ora kena digunakake ing piranti iki amarga bisa nyebabake kegagalan penukar panas sing durung wayahe lan bakal ora sah babar pisan.

SISTEM COMMON FLUE

Lochinvar bisa nyedhiyakake header flue umum PP ndeleng pandhuan kapisah sing kasedhiya ing www.lochinvar.ltd.uk
Utawa, installer bisa nggunakake spesialis instalasi flue kanggo ngrancang lan nyuplai sistem flue sing kapisah miturut sebutan flue C63 nggunakake spesifikasi sing ditampilake ing kaca 13 lan informasi ing tabel ing ngisor iki.
Sembarang panginstalan nggunakake jinis flue C63 kudu dirancang lan diinstal ing tundhuk karo sembarang Building utawa planning peraturan lokal, nanging minangka sistem iki nggunakake sistem flue ora diwenehake dening Lochinvar, Lochinvar ora bisa menehi komentar / menehi saran utawa menehi support ing desain saka jinis sistem flue. Kanggo ngrancang sistem cerobong asap kasebut, pemasang/kontraktor kudu takon karo pemasok cerobong spesialis sing bakal tanggung jawab kanggo desain lan instalasi sistem saluran pembuangan sing kapisah. Nalika ngrancang sistem flue tipe C63, instruksi ing Manual Instalasi, sing diwenehake karo boiler, kudu digatekake. Lochinvar bakal nyedhiyani tokoh mundhut meksa kanggo Unit tartamtu, nanging liyane saka iku, Lochinvar ora bisa nyedhiyani support ing panjalukan Common Flue amarga sertifikat flue diwatesi kanggo kategori certified ing tabel ing kaca 2. Lochinvar ora bisa nampa tanggung jawab kanggo desain sistem Flue.

Tekanan sing kasedhiya ing outlet gas buang Laju Massa Gas Buang (G20) 96% (g/sec) Laju Massa Gas Buang (G20) 25% (g/dtk) Laju Massa Gas Buang (G31) 96% (g/dtk) Laju Massa Gas Buang (G31) 25% (g/dtk)

CPM 58
200Pa 22.6 5.7 23.2 5.8

CPM 77
200Pa 29.8 7.5 30.6 7.7

CPM 96
200Pa 37.1 9.3 38.8 9.7

CPM 116
200Pa 45.1 11.3 46.2 11.6

CPM 144
200Pa 55.6 13.9 57 14.3

CPM 175
200Pa 67.3 16.8 69 17.3

Range boiler CPM ora duwe Non Return Valve (NRV) internal amarga cerobong kasebut kudu dirancang kanthi tekanan nol utawa negatif kajaba NRV sing cocog dipasang lan yen perlu disambungake menyang piranti. Katup Non Return kalebu karo header flue umum Lochinvar.

Kaca 16 saka 19

FORMULIR ORDER lan cathetan

Item No.

Ora dibutuhake

Cathetan-Item kanggo pesenan
Cathetan

Hubungi layanan pelanggan Lochinvar kanggo pesen item flue tambahan ing 01295 269981

Kaca 17 saka 19

Kosong Kaca 18 saka 19

Kaca 19 saka 19

Dokumen / Sumber Daya

Lochinvar CMP58 Kalebu CPM-SP Range [pdf] Pandhuan pangguna
CMP58, CPM77, CPM96, CPM116, CPM146, CPM176, CMP58 Ora Klebu CPM-SP Range, CMP58, Ora Klebu CPM-SP Range, Klebu CPM-SP Range, CPM-SP Range

Referensi

Ninggalake komentar

Alamat email sampeyan ora bakal diterbitake. Kolom sing dibutuhake ditandhani *