Specifikimet

  • Models covered: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 (Does
    not include CPM-SP range)
  • Certified for use on flue categories: B23, C13, C33, C43, C53,
    C63, C83

Udhëzimet e përdorimit të produktit

Sistemet e tymit me dy tuba Lloji C53

For twin-pipe flue systems, follow the sizing and calculation
guidelines provided on page 12 of the manual.

Sisteme konvencionale (vetëm shkarkime) të tymit të tipit B23

For conventional flue systems, refer to page 15 for sizing and
calculation instructions.

Flue Systems Using Flue Not Supplied by Lochinvar Type C63

If using a flue not supplied by Lochinvar, follow the guidelines
outlined on page 16 for common flue systems.

FAQ

P: Cilat standarde duhet të përmbushin instalimet?

A: All installations should comply with BS5440-1:2023 for
appliances up to 70kW net input. Refer to drawing 1 and table 1 for
terminal locations.

“`

CPM Boiler range Flue Guide
Models covered: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 Does not include CPM-SP range

Përmbajtja
GENERAL………………………………………………………………………………………………………………………………………………… 2 Drawing 1 Boiler terminal locations………………………………………………………………………………………………………….5 Table 1 Boiler terminal locations ……………………………………………………………………………………………………………..5 Table 2 risk assesment …………………………………………………………………………………………………………………………..6 Boiler flue information…………………………………………………………………………………………………………………………..6
CONCENTRIC FLUE SYSTEMS ………………………………………………………………………………………………………………………7 Horizontal Type C13 ……………………………………………………………………………………………………………………………….7 Plume kit for use with horizontal flue……………………………………………………………………………………………………….8 Vertical Type C33……………………………………………………………………………………………………………………………………9 Concentric flue sizing/calculations …………………………………………………………………………………………………………10
TWIN-PIPE FLUE SYSTEMS TYPE C53 ……………………………………………………………………………………………………………11 Twin-Pipe flue sizing/calculations…………………………………………………………………………………………………………..12
CONVENTIONAL (EXHAUST ONLY) FLUE SYSTEMS TYPE B23…………………………………………………………………………….14 Conventional flue sizing/calculations………………………………………………………………………………………………………15
FLUE SYSTEMS USING FLUE NOT SUPPLIED BY LOCHINVAR TYPE C63………………………………………………………………..16 COMMON FLUE SYSTEMS ………………………………………………………………………………………………………………………..16 ORDER FORM AND NOTES ……………………………………………………………………………………………………………………….17
Faqja 1 nga 19

E PËRGJITHSHME

Kaldaja Lochinvar CPM janë të certifikuara për përdorim në kategoritë e mëposhtme të tymit:

Lloji i instalimit Kategoria

Përshkrimi

B23

Typ i hapur

Një pajisje që synohet të lidhet me një kanal tymi që evakuon produktet e djegies në pjesën e jashtme të dhomës që përmban pajisjen. Ajri i djegies nxirret direkt nga dhoma.

C13

Typ i mbyllur

Një pajisje e lidhur me një sistem kanalesh tymi koncentrike ose me dy tuba me një terminal kanalesh tymi horizontale. Hyrja e ajrit dhe shkarkimi i tymit duhet të jenë në të njëjtën zonë presioni.

C33

Typ i mbyllur

Një pajisje e lidhur me një sistem tymi koncentrik ose me dy tuba me një terminal vertikal të tymit. Hyrja e ajrit dhe shkarkimi i tymit duhet të jenë në të njëjtën zonë presioni.

Një pajisje e lidhur me një sistem të përbashkët hyrjeje ajri dhe shkarkimi të oxhakut, e cila është projektuar për më shumë se

C43

Oxhak i Mbyllur me një pajisje. Ky sistem i përbashkët ka një hyrje të vetme ajri dhe një dalje oxhaku dhe është pjesë e ndërtesës jo

pajisjen.

C53

Typ i mbyllur

Një pajisje e lidhur me një sistem kanalesh tymi me dy tuba me një terminal tymi horizontal ose vertikal. Si hyrja e ajrit ashtu edhe shkarkimi i tymit mund të jenë në zona të ndryshme presioni.

Një pajisje e destinuar për t'u lidhur me një sistem të miratuar dhe të tregtuar veçmas për furnizimin e

C63

Ajri i djegies së oxhakut të mbyllur dhe shkarkimi i produkteve të djegies (domethënë, përveç atyre të furnizuara nga ngrohësi i ujit)

prodhuesi).

Një pajisje e lidhur nëpërmjet njërit prej kanaleve të saj në një sistem kanalesh të vetëm ose të përbashkët. Ky sistem kanalesh përbëhet

C83

Typ i mbyllur

të një kanali të vetëm natyror të tërheqjes (domethënë pa përfshirë një ventilator) që nxjerr produktet e djegies. Pajisja është e lidhur nëpërmjet një kanali të dytë me një terminal, i cili furnizon pajisjen me ajër.

nga jashtë ndërtesës.

Të gjitha instalimet duhet të jenë në përputhje me kërkesat e:
1. Për pajisje deri në 70kW hyrje neto - BS5440-1:2023 - Kanalet e tymit dhe ventilimi për pajisjet me gaz me hyrje të vlerësuar që nuk tejkalon 70 kW neto (gazrat e familjes së 1-rë, të 2-të dhe të 3-të). Specifikime për instalimin e pajisjeve me gaz në oxhaqe dhe për mirëmbajtjen e oxhaqeve. a. Referojuni vizatimit 1 dhe tabelës 1 për detaje mbi vendndodhjet e terminaleve.
2. Për pajisjet me hyrje neto mbi 70kW - IGEM/UP/10 Edicioni 4 +A: 2016 – Instalimi i pajisjeve me gaz të oxhakut në ambiente industriale dhe tregtare, vëmendje e veçantë duhet t'i kushtohet seksioneve të mëposhtme. a. Referojuni vizatimit 1 dhe tabelës 1 për detaje mbi vendndodhjet e terminaleve. b. Fundet horizontale duhet të vendosen sipas distancave minimale të dhëna në tabelën 1, dhe në varësi të kritereve të vlerësimit të rrezikut të treguara në tabelën 2. c. Fundet horizontale të oxhakut (përveç sistemeve të hollimit me ventilator) nuk duhet të instalohen për asnjë pajisje të vetme ose grup pajisjesh me një hyrje neto totale që tejkalon 333kW hyrje neto të nxehtësisë. d. Për çdo pajisje të vetme ose grup pajisjesh me një hyrje neto totale të nxehtësisë që tejkalon 333 kW, do të zbatohen kërkesat e përgjithshme të IGEM/UP/10 Edicioni 4 +A: 2016 dhe duhet të kërkohet miratimi nga Autoriteti Lokal para fillimit të instalimit.
3. Akti i Ajrit të Pastër për instalimet që tejkalojnë hyrjen neto prej 333 kW.

Faqja 2 nga 19

DRAWING 1 BOILER TERMINAL LOCATIONS ACCORDING TO BS5440-1-2023

TABLE 1 BOILER TERMINAL LOCATIONS ACOORDING TO BS5440-1-2023

Përshkrimi i vendndodhjes

A

Direkt poshtë një hapjeje, tulla ajri, dritare hapëse etj.

B

Mbi një hapje, tulla ajri, dritare hapëse etj.

C

Horizontalisht në një hapje, tulla ajri, dritare hapëse etj.

D

Nën një kanal ose tubacione sanitare

E

Poshtë strehës

F

Poshtë një ballkoni ose çati porti makine

G

Nga një tub vertikal kullimi ose dheu

H

Nga një kënd i brendshëm ose i jashtëm

I

Mbi tokë, çati ose nivel ballkoni

J

Nga një sipërfaqe përballë terminalit

K

Nga një terminal përballë terminalit

L

Nga një hapje në portin e makinës (p.sh. derë, dritare) në banesë

M

Vertikalisht nga një terminal në të njëjtin mur

N

Horizontalisht nga një terminal në të njëjtin mur

O

Horizontally from a mechanical air inlet on the same wall

P

Nga një strukturë vertikale në çati

Q

Mbi kryqëzimin me çatinë

R

Diagonally across from an opening into a building on a different wall

S

Vertical terminal from another vertical terminal

T

Vertical terminal adjacent to an opening into a building

U

Vertical terminal from a wall

V

Terminal alongside a boundary

W

Terminal facing a boundary

X

Adjacent to an opening into a building on a pitched roof

Y

Terminal facing an opening into a building

* Contact Lochinvar technical support for help.

CPM58

mm

300

mm

300

mm

300

mm

75

mm

300

mm

200

mm

150

mm

300

mm

300

mm

600

mm

1200

mm

1200

mm

1500

mm

300

mm

1000

mm

N/A

mm

300

mm

600

mm

600

mm

1500

mm

500

mm

300

mm

600

mm

*

mm

2000

Faqja 3 nga 19

TABLE 2 RISK ASSESSMENT ACCORDING TO BS5440-1-2023
Further to the requirements in BS5440-1:2023 Annex D and Figure C.8, table C.1 the following risk assessment gives guidance for the positioning of horizontal flues. This form should be completed before work commences and undertaken by a person who is competent to undertake the risk assessment.

Type C appliances with net heat input not exceeding 70kW Low level flue discharge risk assessment (including net heat input for groups of appliances)

No. Regarding the flue position

Jo Po

1 Will the flue terminal contravene the positions set out in table C.1 for room sealed chimney outlets?

Jo Po

2

Will the terminal be sited in a position that will likely allow products of combustion to build up (e.g., enclosed by adjacent structures)?

Nr

po

3 Is the termination in a light well?

Jo Po

4 Is the termination within a carport without two unobstructed sides?

Jo Po

5 Will the termination be in an area that might have combustible material in the vicinity?

Jo Po

6 Will the termination be in an area that might have hazardous material in the vicinity (e.g., petrochemicals)?

Jo Po

7 Will the termination be sited within a covered walkway? 8 Are there any restrictions stopping the fitting of a terminal guard if required? 9 Will the termination discharge over a boundary?

Jo Po Jo Po Jo Po

10 Is a plume management kit required to circumvent the termination distances as required in table C.1?

Jo Po

Nr. 11 12
Nr.

Nuisance considerations Is the termination sited over a pathway that is likely to cause nuisance (e.g., head height or pluming towards users)? Is the termination likely to cause a nuisance to neighbours? Chimney/flue routes Will the flue be installed in a void that will not be able to satisfy a full visual inspection?

Jo Po
Jo Po
Jo Po Jo Po Jo Po

Are there any restrictions that will prevent the flue from being supported throughout its entire length?

Jo Po

Do the flue materials contravene building regulations (e.g., high risk buildings)?

Jo Po

Will the flue route pass through any fire protected areas without the ability to maintain its protection?

Jo Po

Will the flue pass through another dwelling?
Is the flue likely to be damaged due to its route/location (e.g., materials stored on it in a plantroom or storeroom)?

Jo Po Jo Po

Does the flue affect the integrity of the structure it is in (e.g., lintels, cavity trays, barriers, or membranes)?

Jo Po

Nëse të gjitha përgjigjet janë blu, atëherë pozicioni i tymit duhet të jetë i përshtatshëm

Nëse ndonjë përgjigje është Portokalli, atëherë pozicioni i tymit është i papërshtatshëm, merrni parasysh të rishikoni pozicionin ose llojin e daljes së tymit ose kontaktoni oficerin lokal të Shëndetit Mjedisor për ndihmë dhe/ose miratim

Faqja 4 nga 19

DRAWING 2 BOILER TERMINAL LOCATIONS ACCORDING TO IGEM/UP/10 EDITION 4 +A: 2016

TABLE 3 BOILER TERMINAL LOCATIONS ACORDING TO IGEM/UP/10 EDITION 4 +A: 2016

Përshkrimi i vendndodhjes

A

Direkt poshtë një hapjeje, tulla ajri, dritare hapëse etj.#

B

Mbi një hapje, tulla ajri, dritare hapëse etj.

C

Horizontalisht në një hapje, tullë ajri, dritare hapëse etj.#

D

Nën një kanal ose tubacione sanitare

E

Poshtë strehës

F

Poshtë një ballkoni ose çati porti makine

G

Nga një tub vertikal kullimi ose dheu

H

Nga një kënd i brendshëm ose i jashtëm

I

Mbi tokë, çati ose nivel ballkoni

J

Nga një sipërfaqe përballë terminalit

K

Nga një terminal përballë terminalit

L

Nga një hapje në portin e makinës (p.sh. derë, dritare) në banesë

M

Vertikalisht nga një terminal në të njëjtin mur

N

Horizontalisht nga një terminal në të njëjtin mur

N+

Vertikalisht nga një terminal në të njëjtën çati

P

Nga një strukturë vertikale në çati

Q

Mbi kryqëzimin me çatinë

CPM77 CPM96 CPM116 CPM144 CPM175

mm 2500

2500

2500

2500

2500

mm

631

760

896

1092

1294

mm

631

760

896

1092

1294

mm

200

200

200

200

200

mm

200

200

200

200

200

mm

Nuk rekomandohet shih vlerësimin e rrezikut UP10

mm

150

150

150

150

150

mm 1099

1513

1948

2573

3220

mm

300

300

300

300

300

mm 1100

1514

1948

2573

3220

mm 2083

2429

2792

3314

3855

mm

Nuk rekomandohet shih vlerësimin e rrezikut UP10

mm 2500

2500

2500

2500

2500

mm

600

600

900

900

n/a*

600

600

900

900

n/a*

mm 1500

1500

1500

1500

1500

mm

311

359

409

481

556

*Please contact Lochinvar technical support for guidance on CPM175 termination.
The table above should be used in conjunction with the following notes: · Distances shown ensure the boiler will operate without problems under most conditions, these distances can be reduced in certain circumstances · The above should be read in conjunction with the latest edition of BS5440-1 and IGEM UP10 · For boiler installation above 333kW nett input the table above should not be used, these installations are covered by the clean air act and must comply with its requirements in full, contact your local environmental health team for further guidance
Për udhëzime të mëtejshme, ju lutemi kontaktoni mbështetjen teknike të Lochinvar.
Faqja 5 nga 19

Table 4 risk assesment The table below is an excerpt from IGEMUP10 and should be used in conjunction with that document
Në vijim të kërkesave në IGEM/UP/10 Edition 4 +A: 2016 Seksioni 8 nën pikën 8.7.3.3 dhe Figurën 7, vlerësimi i rrezikut në vijim jep udhëzime për pozicionimin e kanaleve të tymit horizontal. Ky formular duhet të plotësohet përpara se të fillojë puna dhe të ndërmerret nga një person i cili është kompetent për të ndërmarrë vlerësimin e rrezikut.

Pajisjet e tipit C me hyrje të nxehtësisë neto që tejkalon 70 kW dhe jo më shumë se 333 kW, vlerësimi i rrezikut të shkarkimit të tymit të nivelit të ulët (përfshirë hyrjen e nxehtësisë neto për grupet e pajisjeve)

Nr.

Në lidhje me pozicionin e tymit

Nr

po

A është përfundimi i propozuar i oxhakut brenda distancës në Figurën K të një rruge, shtegu,

1

pistë, rrugë kryesore, shteg për këmbësorë, kufi ose zonë prone, e cila përdoret për përdorim të përgjithshëm

Nr

po

akses publik përveçse për qëllime mirëmbajtjeje?

2

A është përfundimi i propozuar i oxhakut brenda distancës në Figurën K nga një shesh lojërash,

Nr

po

shkollë, oborr, zonë ulëseje ose zonë ku mund të ketë një tubim publik

3

If the proposed flue termination enclosed on more than two sides then does it

Nr

po

comply with the requirements of Figure 11B?

A është përfundimi i propozuar i oxhakut brenda distancës në Figurën K të një sipërfaqeje apo

4

element ndërtimi që mund të preket nga korrozioni ose përkeqësimi nga tymi

Nr

po

kondensat?

5

A është pozicioni i propozuar i oxhakut në një zonë ku mund të parkohen automjete brenda?

Nr

po

distancat nga Figura 12 Linja G deri te oxhaku?

6

A ka shkurre ose pemë brenda distancave minimale të treguara në Figurën K të

Nr

po

pozicioni i propozuar i terminalit?

7

A është përfundimi i propozuar i tymit brenda një pusi me dritë?

Nr

po

A ka gjasa që produktet e djegies nga pozicioni i propozuar i oxhakut të grumbullohen?

8

në kushte të pafavorshme atmosferike, për shkak të rrjedhës së dobët të ajrit të shkaktuar nga

Nr

po

rrethime ose struktura ngjitur dhe/ose që ka të ngjarë të shkaktojë shqetësim?

9

A ka gjasa që pozicioni i mbylljes së kanalit të tymit të shkaktojë shqetësim në pronat fqinje?

Nr

po

Rregullat e ndërtimit pjesa J

10

A është përfundimi i propozuar i tymit më pak se 300 mm nga kufiri i pronës, i matur nga ana e terminalit në kufi?

Nr

po

Lidhur me ligjin për ajër të pastër

11

A është prodhimi total i terminaleve individuale ose grupit të tymit (nëse është brenda 5U (shih A3.7)), më i madh se 333 kW input neto i nxehtësisë?

Nr

po

Gjeneral

12

A ka ndonjë konsideratë tjetër që kërkohet për këtë vlerësim të rrezikut, shih fletën e veçantë.

Nr

po

13

Komentet:

If all answers are Blue then the flue position should be suitable If any answer is Orange then the flue position is unsuitable, consider revising the position or type of flue outlet or contac t the local Environmental Health officer for assistance and/or approval
INFORMACION PËR QYRIN E KALDAJES

Model Number FLUE DATA TYPE B23 Nominal flue diameter Maximum flue gas temp Flue gas temperature Flue draught requirements Available pressure for the flue system Maximum flue gas volume FLUE DATA TYPE C13 & C33 Nominal flue diameter Maximum flue gas temp FLUE DATA TYPE C43 & C53 Nominal flue diameter Maximum flue gas temp

mm °C °C mbar Pa g/s
mm °C
mm °C

CPM58

CPM77

80

5.59 to 28.9 6.52 to 38.6 80/125
80

CPM96

CPM116

CPM144

CPM175

100 95 85-95 -0.03 to -0.1 200 7.69 to 47.9 11.6 to 57.7

130 15.2 deri në 71.7 20.1 deri në 86.2

100/150 95

100

130

95

Faqja 6 nga 19

SISTEMET KONCENTRIKE TË GRIPIT

TIPI HORIZONTAL C13

CPMH001 CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS – CPM58, CPM77

Artikulli Nr

Përshkrimi

Included CPM58

LV310757 CONCENTRIC HORIZONTAL TERMINAL – Ø80/125mm PP

1

44.8

M28925B

PLAKA MURI TERMINAL

1

LV310735

KËRKIM KONQENTRIK 90° Ø80/125mm PP

1

16.1

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej 60.9

CPM77 80.1 28.7 108.8

Item No. LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M84481B

Additional Flue Ancillary Items Description CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP TELESCOPIC CONCENTRIC BEND 45° Ø80/125mm PP CONCENTRIC BEND 90° Ø80/125mm PP WALL CLAMP Ø125 mm

Përmasat 250mm 500mm 1000mm 2000mm
240mm-360mm See Drawing Below See Drawing Below
N/A

CPMH003 CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS – CPM96, CPM116

Artikulli Nr

Përshkrimi

Included CPM96 CPM116

LV310758B CONCENTRIC HORIZONTAL TERMINAL Ø100/150mm PP

1

58

84

M84410B CONCENTRIC BEND 90° Ø100/150mm PP SHORT RADIUS

1

23.6

34.2

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej 81.6 118.2

CPMH004 CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS – CPM144

Artikulli Nr

Përshkrimi

Të përfshira

LV310758B

TERMINAL HORIZONTAL KONQENTRIK Ø100/150mm PP

1

E61-001-172B

KIT KONCENTRIK KONVERTIMI

1

M84410B

KËRKIM KONQENTRIK 90° Ø100/150mm PP RREZE E SHKURTËR

1

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej

CPM144 129.9 52.9 182.8

Item No. M84405B M84402B M84412B M84413B M84421B M87196B

Përshkrimi i artikujve shtesë ndihmës të oxhakut
CONCENTRIC EXTENSION Ø100/150mm Cuttable CONCENTRIC EXTENSION Ø100/150mm PP FIXED
CONCENTRIC BEND 90° Ø100/150mm PP CONCENTRIC BEND 45° Ø100/150mm PP
SAMPLING POINT Ø100/150mm PP WALL CLAMP Ø150 mm

CPM58-77 A=45mm B=62.5mm

Përmasat 500 mm 1000 mm
Shihni Vizatimën Më Poshtë Shihni Vizatimën Më Poshtë
115 mm
CPM58-77 A=95mm B=110mm

CPM96-175 A=128mm B=128mm

CPM96-175 A=223mm B=208mm

Faqja 7 nga 19

KIT TUBËSH PËR PËRDORIM ME OXHAK HORIZONTALE

KITET E MENAXHIMIT TË TUBRAVE LG800008B KITET I MENAXHIMIT TË TUBRAVE Ø80/125mm LG800009B KITET I MENAXHIMIT TË TUBRAVE Ø100/150mm

Nr

Përshkrimi

1 KALIM KONQENTRIK 90°-PP

2 KIT ME 2 TUBE HORIZONTALE KONQENDRIKË TERMINALI -PP

3 ZGJATJE - PP I PRERSHËM (1000 mm)

4 Kthesë 90°-PP

5 KIT MBROJTËS NGA ZOGJTË PLUME

6 KIT DALJE PËR OXHAKËT E TYLLIT - PP

7 MURE CLAMP

Një diametër i brendshëm

DIAMETRI I JASHTËM B

CPM58 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm

CPM77 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm

CPM96 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm

CPM116 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm

CPM144 N/A N/A N/A N/A N/A N/A N/A N/A N/A

CPM175 N/A N/A N/A N/A N/A N/A N/A N/A N/A

Seti i pendëve nuk duhet të përdoret për të korrigjuar një vendndodhje të paligjshme të terminalit.

Faqja 8 nga 19

TIPI VERTIKAL C33

CPMV001 MODELET KONCENTRIKE TË MONTIMIT VERTIKAL TË tymit - CPM58, CPM77

Item No LV310753 LV310745B

Description CONCENTRIC VERTICAL TERMINAL – Ø80/125mm PP CONCENTRIC EXTENSION – Ø80/125mm PP (500mm)

Përfshirë 1 1

CPM58 61.5 5.1

LV310742B CONCENTRIC EXTENSION – Ø80/125mm PP FIXED (1000mm)

1

10.2

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej 76.8

CPM77 109.8 9.05 18.1 136.95

Item No. LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M87195B LV302520

Artikuj shtesë ndihmës të tymit
Description CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP TELESCOPIC CONCENTRIC BEND 45° Ø80/125mm PP CONCENTRIC BEND 90° Ø80/125mm PP WALL CLAMP Ø130mm FLAT ROOF FLASHING Ø140mm ALU

Përmasat 250mm 500mm 1000mm 2000mm
240-360 mm Shihni vizatimin më poshtë Shihni vizatimin më poshtë
N/AN/A

CPMV003 MODELET KONCENTRIKE TË MONTIMIT VERTIKAL TË tymit - CPM96, CPM116

Artikulli Nr

Përshkrimi

Included CPM96

LV310754B

TERMINAL VERTIKAL KONQENTRIK Ø100/150mm PP

1

80

M84405B CONCENTRIC EXTENSION Ø100/150mm (500mm) Cuttable

1

6.5

M84402B CONCENTRIC EXTENSION Ø100/150mm (1000mm) PP FIXED

1

13

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej 99.5

CPM116 115.9 9.45 18.9 144.25

Item No. M84405B M84402B M84412B M84413B M84421B M87196B

Artikuj shtesë ndihmës të tymit
Description CONCENTRIC EXTENSION Ø100/150mm Cuttable CONCENTRIC EXTENSION Ø100/150mm PP FIXED CONCENTRIC BEND 90° Ø100/150mm PP CONCENTRIC BEND 45° Ø100/150mm PP SAMPLING POINT Ø100/150mm PP WALL CLAMP Ø150 mm

Përmasat 500 mm 1000 mm
Shihni Vizatimën Më Poshtë Shihni Vizatimën Më Poshtë
115 mm

CPM58-77 A=45mm B=62.5mm
CPM96-175 A=128mm B=128mm

CPM58-77 A=95mm B=110mm
CPM96-175 A=223mm B=208mm

Concentric flue is unable to be used with CPM175

Faqja 9 nga 19

MADHËSIA/LLOGARITJET KONQENTRIK TË GRIPIT

Rezistenca në Pa

Artikulli

CPM 58 80/125 CPM 77 80/125 CPM 96 100/150 CPM 116 100/150

Terminali i murit

44.8

80.1

58

84

Terminali i çatisë

61.5

109.8

80

115.9

Tub i drejtë (m)

10.2

18.1

13.0

18.9

Bërryl 45°

8.6

15.4

15.5

22.4

Bërryl 90°

16.1

28.7

23.6

34.2

Kompleti i kumbullës

10

10

20

25

Për t’u përdorur vetëm për rezistencën e komponentëve të sistemit të oxhakut M&G të furnizuar nga Lochinvar

CPM 144 100/150 129.9 179.2 29.2 34.7 52.9 n/a

CPM 175 100/150 188 259.3 42.2 50.2 76.5 n/a

Përdorni tabelën e mëposhtme për të llogaritur rezistencën totale të sistemit të tymit

Artikulli

Rezistenca Sasia Totale

Terminal muri Terminal çatie Tub i drejtë (m) Bërryl 45° Bërryl 90° Kit pendësh

Rezistenca totale (Pa)

Rezistenca totale e llogaritur e sistemit duhet të jetë më pak se 200pa

Faqja 10 nga 19

SISTEMET QYRAVE ME DY TUBAT TIPI C53

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM58, CPM77

Oxhak vertikal

Artikulli Nr

Përshkrimi

No Required CPM58 CPM77

LM410084006

1

TERMINAL VERTIKAL – 130mm PP

38.8 38.8

LV305016

1

HYRJE AJRI HORIZONTAL Ø80mm

M28925B

1

PLAKA TE MURIT TERMINAL (CIF)

M85283 LM410084992

EXPANDER Ø80mm – Ø100mm PP
EXPANDER Ø100mm – Ø130mm PP

Rezistencë maksimale në sistemin e oxhakut 200pa

1 1 Gjithsej

38.8 38.8

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM58, CPM77

Oxhak horizontal

Nr

Artikulli Nr

Përshkrimi

Required CPM58

LV310757B

TERMINAL HORIZONTAL KONQENTRIK Ø80/125mm PP

1

29.86

LV305016

HYRJE AJRI HORIZONTAL Ø80mm

1

M28925B

PLAKA TE MURIT TERMINAL (CIF)

1

Maximum resistance in the flue system

200 pa

Gjithsej

29.86

CPM77 53.4
53.4

Nr. i artikullit LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B

Përshkrimi i artikujve shtesë ndihmës të oxhakut
ZGJATJE – Ø80mm PP I PRERË NË GJATËSI ZGJATJE Ø80mm PP I PRERË NË GJATËSI ZGJATJE Ø80mm PP I PRERË NË GJATËSI ZGJATJE – Ø80mm PP I PRERË NË GJATËSI ZGJATJE – Ø80mm PP I PRERË NË GJATËSI ZGJATJE – Ø80mm PP KËRCITJE TELESKOPIKE 45° 80mm KËRCITJE PP 90° 80mm PP MUR I RRYERAMP Ø80 mm

Përmasat 250mm 500mm 1000mm 2000mm
240-360 mm Shihni vizatimin më poshtë Shihni vizatimin më poshtë
N/A

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM96, CPM116

Oxhak vertikal

Item No LM410084006

Përshkrimi
VERTICAL TERMINAL 130MM PP

No Required 1

CPM96 38.8

LV305039

HORIZONTAL AIR INLET

1

Ø100 mm

M28925B

TERMINAL WALL

1

PLATES (PAIR)

LM410084992 EXPANDER Ø100mm –

1

Ø130mm PP

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej

38.8

CPM116 38.8

38.8

Faqja 11 nga 19

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM96, CPM116

Oxhak horizontal

Nr

Artikulli Nr

Përshkrimi

Required CPM96

KONQENTRIK

LV310758B

HORIZONTAL TERMINAL

1

38.66

Ø100/150mm PP

LV305039B

HYRJE AJRI HORIZONTAL Ø100mm ALU

1

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej 38.66

CPM116 56
56

Nr. i artikullit M85176B M85177B M85181B M85182B M87193B

Artikuj shtesë ndihmës të oxhakut Përshkrimi ZGJATIM Ø100mm PP I PRERË NË GJATËSI ZGJATIM Ø100mm PP I PRERË NË GJATËSI LAKË 90° 100mm LAKË PP 45° 100mm SHIRITA MURI PP (100mm)

Përmasat 500 mm 1000 mm
Shihni Vizatimën Më Poshtë Shihni Vizatimën Më Poshtë
n/a

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM144, CPM175

Oxhak vertikal

Artikulli Nr

Përshkrimi

No Required CPM144

LM410084006 VERTICAL TERMINAL –

1

38.8

130MM PP

LV307178

HORIZONTAL AIR INLET

1

Ø130mm ALU

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej

38.8

CPM175 38.8

38.8

Item No M70242 M70251 M70252 M87195

Përshkrimi i artikujve shtesë ndihmës të oxhakut
EXTENSION Ø130mm PP BEND 90° PP BEND 45° PP WALL CLAMP

Përmasat 1000mm 130mm 130mm 130mm

CPM58CPM77 A=72.5mm, B=72.5mm
CPM96CPM116 A=78mm, B=65mm

CPM58CPM77 A=110mm, B=110mm
CPM96CPM116 A=78mm, B=65mm

Faqja 12 nga 19

LLOGARITJET E MADHËSISË / LLOGARITJEVE TË QYPAVE ME DY TUBA

Artikulli

Resistance (Pa) Size (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Tub i drejtë (për metër)

80

4.6

8.2

X

X

Straight tube (per metre) 100

1.3

2.3

3.5

5.0

Straight tube (per metre) 130

0.3

0.6

0.9

1.2

Bërryl 45°

80

4.2

7.6

X

X

Bërryl 45°

100

2.9

5.1

7.9

11.5

Bërryl 45°

130

0.6

1.0

1.6

2.3

Bërryl 90°

80

10.1 18.0

X

X

Bërryl 90°

100

4.6

8.3

12.7

18.4

Bërryl 90°

130

1.4

2.4

3.7

5.4

Për t'u përdorur vetëm për rezistencën e komponentëve të sistemit të hyrjes së ajrit M&G të furnizuar nga Lochinvar

CPM 144 n/a n/a 1.9 n/a n/a 3.5 n/a n/a 8.4

CPM 175 n/a n/a 2.8 n/a n/a 5.1 n/a n/a 12.1

Artikulli

Resistance (Pa) Size (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Tub i drejtë (për metër)

80

4.0

7.1

X

X

Straight tube (per metre) 100

1.1

2.0

3.0

4.4

Straight tube (per metre) 130

0.3

0.5

0.7

1.1

Bërryl 45°

80

3.7

6.5

X

X

Bërryl 45°

100

2.5

4.4

6.8

9.9

Bërryl 45°

130

0.5

0.9

1.4

2.0

Bërryl 90°

80

8.7

15.6

X

X

Bërryl 90°

100

4.0

7.1

11.0

16.0

Bërryl 90°

130

1.2

2.1

3.2

4.7

Vertical exhaust terminal

61.5 109.8

80

115.9

Vertical single terminal

Për t’u përdorur vetëm për rezistencën e komponentëve të sistemit të shkarkimit të oxhakut M&G të furnizuar nga Lochinvar

CPM 144 n/a n/a 1.7 n/a n/a 3.0 n/a n/a 7.2 179.2 38.8

CPM 175 n/a n/a 2.4 n/a n/a 4.4 n/a n/a 10.5 259.3 38.8

Përdorni tabelën e mëposhtme për të llogaritur rezistencën e sistemit të tymit.

Shkarkimi i tymit

Item Straight tube (m) 45° Elbow 90° Elbow

Rezistenca Sasia Totale

Hyrja e ajrit

Terminali koncentrik vertikal

Rezistenca totale e shkarkimit të tymit (Pa)

Artikulli

Rezistenca e Sasisë

Tub i drejtë (m)

Bërryl 45°

Bërryl 90°

Hyrja e ajrit

Rezistenca totale e hyrjes së ajrit (Pa)

Rezistenca totale e hyrjes së ajrit dhe shkarkimit të tymit (Pa)

Gjithsej

Rezistenca totale e llogaritur e sistemit duhet të jetë më pak se 200pa

Faqja 13 nga 19

SISTEMET KONVENCIONALE (VETËM PËR SHKER) GYPI B23

CPM CONVENTIONAL FLUE ASSEMBLY MODELS CPM58, CPM77

Artikulli Nr

Përshkrimi

No Required CPM58

LV305030B

MBROJTJA E MARRJES TË AJRIT TË PAJISJES Ø80/125mm

1

10.8

LM410084006

TERMINAL VERTIKAL – 130mm PP

1

38.8

M85283

EXPANDER Ø80mm – Ø100mm PP

1

LM410084992

EXPANDER Ø100mm Ø130mm PP

1

Maximum resistance in the flue system 200pa Total

51.8

CPM77 19.2 38.8 92.4

Nr. i artikullit LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B

Përshkrimi i artikujve shtesë ndihmës të oxhakut
ZGJATJE – Ø80mm PP I PRERË NË GJATËSI ZGJATJE Ø80mm PP I PRERË NË GJATËSI ZGJATJE Ø80mm PP I PRERË NË GJATËSI ZGJATJE – Ø80mm PP I PRERË NË GJATËSI ZGJATJE – Ø80mm PP I PRERË NË GJATËSI ZGJATJE – Ø80mm PP KËRCITJE TELESKOPIKE 45° 80mm KËRCITJE PP 90° 80mm PP MUR I RRYERAMP Ø80 mm

Përmasat 250mm 500mm 1000mm 2000mm
240-360 mm Shihni vizatimin më poshtë Shihni vizatimin më poshtë
N/A

CPM CONVENTIONAL FLUE ASSEMBLY MODELS CPM96, CPM116

Nr

Artikulli Nr

Përshkrimi

Required CPM96

LV304872B

MBROJTJA E MARRJES TË AJRIT TË PAJISJES Ø100/150mm

1

11.6

LM410084006

VERTICAL TERMINAL 130MM PP

1

38.8

Maximum resistance in the flue system

200 pa

Gjithsej

64.9

CPM116 16.8 38.8
94.06

CPM CONVENTIONAL FLUE ASSEMBLY MODELS CPM144, CPM175

Artikulli Nr

Përshkrimi

No Required CPM144 CPM175

M81660

APPLIANCE AIR INLET

1

GUARD Ø130mm

LM410084006 VERTICAL TERMINAL –

1

130MM PP

8.7

12.6

38.8

38.8

Rezistencë maksimale në sistemin e oxhakut 200pa

Gjithsej

47.5

51.4

Item No M70242 M70251 M70252 M87195

Përshkrimi i artikujve shtesë ndihmës të oxhakut
EXTENSION Ø130mm PP BEND 90° PP BEND 45° PP WALL CLAMP
CPM58-CPM77 A=72.5mm,B=72.5mm CPM96-CPM116 A=78mm, B=65mm

Përmasat 1000mm 130mm 130mm 130mm
CPM58-CPM77 A=110mm, B=110mm CPM96-CPM116 A=78mm, B=65mm

Faqja 14 nga 19

MADHËSIA/LLOGARITJET KONVENCIONALE TË GRIPIT

Artikulli

Resistance (Pa) Size (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Tub i drejtë (për metër)

80

4.0

7.1

X

X

Straight tube (per metre) 100

1.1

2.0

3.0

4.4

Straight tube (per metre) 130

0.3

0.5

0.7

1.1

Bërryl 45°

80

3.7

6.5

X

X

Bërryl 45°

100

2.5

4.4

6.8

9.9

Bërryl 45°

130

0.5

0.9

1.4

2.0

Bërryl 90°

80

8.7

15.6

X

X

Bërryl 90°

100

4.0

7.1

11.0

16.0

Bërryl 90°

130

1.2

2.1

3.2

4.7

Vertical single terminal

Për t'u përdorur vetëm për rezistencën e komponentëve të sistemit të hyrjes së ajrit M&G të furnizuar nga Lochinvar

CPM 144 n/a n/a 1.7 n/a n/a 3.0 n/a n/a 7.2 38.8

CPM 175 n/a n/a 2.4 n/a n/a 4.4 n/a n/a 10.5 38.8

Përdorni tabelën e mëposhtme për të llogaritur rezistencën e sistemit të tymit.

Artikulli

Rezistenca e Sasisë

Tub i drejtë (m)

Bërryl 45°

Bërryl 90°

Terminali koncentrik vertikal

Rezistenca totale e shkarkimit të tymit (Pa)

Gjithsej

Rezistenca totale e llogaritur e sistemit duhet të jetë më pak se 200pa

Faqja 15 nga 19

SISTEMET E GYPIVE QË PËRDORIN GYP NUK FURNIZOHEN NGA LOCHINVAR LLOJI C63
In general, boilers are certified with their own purpose supplied Concentric or Twin Pipe flue systems, C63 certified appliances allow the installer to use other flue systems when installing the boiler however, they must be of a suitable minimum standard as per table below.

Lëndë CE Material gazi tymi
Europea n standard Temperature
clas s Pressure class Resistance to condensate
Corrosio n resistance
clas s Metal: liner specifications
Soot fire resistance
clas s Distance to combustible
material Plastics: Plastics: fire behaviour Plastics:

min. eis PP EN 14471 T120

P1

W

min. eis RVS EN 1856-1 T120

P1

W

1

n/a

O

1

L20040

O

Materiali

Kaldaja

dnom

Jashtë

dinside

Linsert

SS

CPM58-CPM77 80 80 +0,3/ -0,7 81 +0,3/ -0,3 50 +2/ -2

SS

CPM96-CPM116 100 100 +0,3/ -0,7 101 +0,3/ -0,3 50 +2/ -2

SS CPM144-CPM175 130 130 +0,3/ -0,7 131 +0,5/ -0,5 50 +2/ -2

PP

CPM58-CPM77 80 80 +0,6/ -0,6

50 +20/ -2

PP

CPM96-CPM116 100 100 +0,6/ -0,6

50 +20/ -2

PP CPM144-CPM175 130 130 +0,9/ -0,9

50 +20/ -2

30

I of E C/E

L

40

n/an/an/a

Tubi alumini i tymit nuk duhet të përdoret në këtë pajisje pasi mund të çojë në dështim të parakohshëm të shkëmbyesit të nxehtësisë dhe do të zhvlerësojë garancinë.

SISTEMET E PËRBASHKËT TË GRIPIT

Lochinvar mund të furnizojë një kolektor oxhaku të përbashkët PP, shihni udhëzuesin e veçantë të disponueshëm në www.lochinvar.ltd.uk
Si alternativë, instaluesi mund të përdorë një specialist për instalimin e oxhaqeve për të projektuar dhe furnizuar një sistem të veçantë oxhaqesh nën përcaktimin e oxhakut C63 duke përdorur specifikimet e paraqitura në faqen 13 dhe informacionin në tabelën më poshtë.
Any installations using flue type C63 must be designed and installed in compliance with any local Building or planning regulations, but as these systems use a flue system not supplied by Lochinvar, Lochinvar cannot comment / advise or provide support on the design of this type of flue system. To design such a flue system, the installer/contractor must consult a specialist flue supplier who will be responsible for the design and installation of the separate flue system. When designing the type C63 flue system, the instructions in the Installation Manual, provided with the boiler, must be taken into account. Lochinvar will provide pressure loss figures for the specific units, but other than that, Lochinvar cannot provide support on Common Flue requests because flue certification is limited to the certified categories in the table on page 2. Lochinvar cannot accept any responsibility for Flue system design.

Presioni i disponueshëm në daljen e gazit të oxhakut Shkalla e masës së gazit të oxhakut (G20) 96% (g/sek) Shkalla e masës së gazit të oxhakut (G20) 25% (g/sek) Shkalla e masës së gazit të oxhakut (G31) 96% (g/sek) Shkalla e masës së gazit të oxhakut (G31) 25% (g/sek)

CPM 58
200Pa 22.6 5.7 23.2 5.8

CPM 77
200Pa 29.8 7.5 30.6 7.7

CPM 96
200Pa 37.1 9.3 38.8 9.7

CPM 116
200Pa 45.1 11.3 46.2 11.6

CPM 144
200Pa 55.6 13.9 57 14.3

CPM 175
200Pa 67.3 16.8 69 17.3

The CPM boiler range does not have an internal Non Return Valve (NRV) as such any flue must be designed on zero or negative pressure unless a suitable NRV is fitted and if necessary interlocked to the appliance. Non Return Valves are included with the Lochinvar common flue header.

Faqja 16 nga 19

FORMULARI I POROSISË DHE SHËNIMET

Artikulli Nr.

Nuk kërkohet

Shënime - Artikuj për të porositur
Shënime

Kontaktoni shërbimin e klientit të Lochinvar për të porositur artikuj shtesë të tymit në 01295 269981

Faqja 17 nga 19

Faqja 18 e zbrazët nga 19

Faqja 19 nga 19