Lochinvar CMP58 Does Include CPM-SP Range User Guide

CMP58 Does Include CPM-SP Range

Sonraíochtaí

  • Models covered: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 (Does
    not include CPM-SP range)
  • Deimhnithe lena úsáid ar chatagóirí simléir: B23, C13, C33, C43, C53,
    C63, C83

Treoracha Úsáide Táirge

Córais Múcháin Dhá Phíopa Cineál C53

For twin-pipe flue systems, follow the sizing and calculation
guidelines provided on page 12 of the manual.

Gnáthchórais Múcháin (Sceite Amháin) Cineál B23

For conventional flue systems, refer to page 15 for sizing and
calculation instructions.

Flue Systems Using Flue Not Supplied by Lochinvar Type C63

If using a flue not supplied by Lochinvar, follow the guidelines
outlined on page 16 for common flue systems.

CCanna

Q: What standards should installations comply with?

A: All installations should comply with BS5440-1:2023 for
appliances up to 70kW net input. Refer to drawing 1 and table 1 for
terminal locations.

“`

CPM Boiler range Flue Guide
Models covered: CMP58 CPM77 CPM96 CPM116 CPM146 CPM176 Does not include CPM-SP range

Clár ábhair
GENERAL………………………………………………………………………………………………………………………………………………… 2 Drawing 1 Boiler terminal locations………………………………………………………………………………………………………….5 Table 1 Boiler terminal locations ……………………………………………………………………………………………………………..5 Table 2 risk assesment …………………………………………………………………………………………………………………………..6 Boiler flue information…………………………………………………………………………………………………………………………..6
CONCENTRIC FLUE SYSTEMS ………………………………………………………………………………………………………………………7 Horizontal Type C13 ……………………………………………………………………………………………………………………………….7 Plume kit for use with horizontal flue……………………………………………………………………………………………………….8 Vertical Type C33……………………………………………………………………………………………………………………………………9 Concentric flue sizing/calculations …………………………………………………………………………………………………………10
TWIN-PIPE FLUE SYSTEMS TYPE C53 ……………………………………………………………………………………………………………11 Twin-Pipe flue sizing/calculations…………………………………………………………………………………………………………..12
CONVENTIONAL (EXHAUST ONLY) FLUE SYSTEMS TYPE B23…………………………………………………………………………….14 Conventional flue sizing/calculations………………………………………………………………………………………………………15
FLUE SYSTEMS USING FLUE NOT SUPPLIED BY LOCHINVAR TYPE C63………………………………………………………………..16 COMMON FLUE SYSTEMS ………………………………………………………………………………………………………………………..16 ORDER FORM AND NOTES ……………………………………………………………………………………………………………………….17
Lch 1 de 19

GINEARÁLTA

Tá coirí CPM Lochinvar deimhnithe le húsáid ar na catagóirí múcháin seo a leanas:

Installation type Category

Cur síos

B23

Múchán oscailte

Feiste a bheartaítear a bheith nasctha le múchán a fhágann na táirgí dócháin go dtí an taobh amuigh den seomra ina bhfuil an fearas. Tarraingítear an t-aer dócháin go díreach ón seomra.

C13

Múchán Dúnta

Fearas atá nasctha le córas múchán comhlárnach nó dhá phíopa le teirminéal múchán Cothrománach. Caithfidh an t-ionraon aeir agus an sceite múcháin a bheith sa chrios brú céanna.

C33

Múchán Dúnta

Fearas atá nasctha le córas múchán comhlárnach nó dhá phíopa le teirminéal múchán Ingearach. Caithfidh an t-ionraon aeir agus an sceite múcháin a bheith sa chrios brú céanna.

An appliance connected to a common air inlet and flue exhaust system, which is designed for more than

C43

Closed Flue one appliance. This common system has a single air inlet and flue exhaust and is part of the building not

an fearas.

C53

Múchán Dúnta

Fearas atá nasctha le córas múcháin dé-phíopa le teirminéal múchán Cothrománach nó Ingearach. Féadfaidh an dá inlet aeir agus sceite múcháin a bheith i gcriosanna brú éagsúla.

An appliance intended to be connected to a separately approved and marketed system for the supply of

C63

Closed Flue combustion air and discharge of combustion products (i.e. other than that supplied by the water heater

monaróir).

An appliance connected via one of its ducts to a single or common duct system. This duct system consists

C83

Múchán Dúnta

of a single natural draught duct (i.e. not incorporating a fan) that evacuates the products of combustion. The appliance is connected via a second of its ducts to a terminal, which supplies air to the appliance

ón taobh amuigh den fhoirgneamh.

Ba cheart do gach suiteáil cloí leis na ceanglais seo a leanas:
1. For appliances up to 70kW net input- BS5440-1:2023- Flueing and ventilation for gas appliances of rated input not exceeding 70 kW net (1st, 2nd and 3rd family gases). Specification for installation of gas appliances to chimneys and for maintenance of chimneys. a. Refer to drawing 1 and table 1 for details of terminal locations.
2. For appliances over 70kW net input- IGEM/UP/10 Edition 4 +A: 2016 – Installation of flued gas appliances in industrial and commercial premises, specific attention should be paid to the following sections. a. Refer to drawing 1 and table 1 for details of terminal locations. b. Horizontal terminations shall be located according to the minimum distances given in table 1, and subject to the risk assessment criteria shown in table 2. c. Horizontal flue terminations (other than for fan dilution systems) must not be installed for any single appliance or group of appliances with a total nett input exceeding 333kW net heat input. d. For any single appliance or group of appliances with a total net heat input exceeding 333 kW, the general requirements of IGEM/UP/10 Edition 4 +A: 2016 shall apply and approval must be sought from the Local Authority prior to commencement of the installation.
3. The Clean Air Act for installations exceeding 333kW nett input.

Lch 2 de 19

DRAWING 1 BOILER TERMINAL LOCATIONS ACCORDING TO BS5440-1-2023

TABLE 1 BOILER TERMINAL LOCATIONS ACOORDING TO BS5440-1-2023

Cur síos ar an Suíomh

A

Díreach faoi bhun oscailt, bríce aeir, fuinneoga a oscailt etc.

B

Os cionn oscailt, bríce aeir, oscailt fuinneoga etc.

C

Go cothrománach chuig oscailt, bríce aeir, oscailt fuinneoga etc.

D

Thíos gáitéir nó píopaí sláintíochta

E

Faoi na sceimhleacha

F

Thíos balcóin nó díon port cairr

G

Ó dhraenáil ingearach nó píopa ithreach

H

Ó choirnéal inmheánach nó seachtrach

I

Os cionn leibhéal na talún, an dín nó an bhalcóin

J

Ó dhromchla os comhair an teirminéil

K

Ó teirminéal atá os comhair an teirminéil

L

Ó oscailt sa charr port (m.sh., doras, fuinneog) isteach sa teaghais

M

Go hingearach ó chríochfort ar an mballa céanna

N

Go cothrománach ó chríochfort ar an mballa céanna

O

Horizontally from a mechanical air inlet on the same wall

P

Ó struchtúr ingearach ar an díon

Q

Os cionn a dtrasnaíonn an díon

R

Diagonally across from an opening into a building on a different wall

S

Vertical terminal from another vertical terminal

T

Vertical terminal adjacent to an opening into a building

U

Vertical terminal from a wall

V

Terminal alongside a boundary

W

Terminal facing a boundary

X

Adjacent to an opening into a building on a pitched roof

Y

Terminal facing an opening into a building

* Contact Lochinvar technical support for help.

CPM58

mm

300

mm

300

mm

300

mm

75

mm

300

mm

200

mm

150

mm

300

mm

300

mm

600

mm

1200

mm

1200

mm

1500

mm

300

mm

1000

mm

N/B

mm

300

mm

600

mm

600

mm

1500

mm

500

mm

300

mm

600

mm

*

mm

2000

Lch 3 de 19

TABLE 2 RISK ASSESSMENT ACCORDING TO BS5440-1-2023
Further to the requirements in BS5440-1:2023 Annex D and Figure C.8, table C.1 the following risk assessment gives guidance for the positioning of horizontal flues. This form should be completed before work commences and undertaken by a person who is competent to undertake the risk assessment.

Type C appliances with net heat input not exceeding 70kW Low level flue discharge risk assessment (including net heat input for groups of appliances)

No. Regarding the flue position

Níl Tá

1 Will the flue terminal contravene the positions set out in table C.1 for room sealed chimney outlets?

Níl Tá

2

Will the terminal be sited in a position that will likely allow products of combustion to build up (e.g., enclosed by adjacent structures)?

Níl

3 Is the termination in a light well?

Níl Tá

4 Is the termination within a carport without two unobstructed sides?

Níl Tá

5 Will the termination be in an area that might have combustible material in the vicinity?

Níl Tá

6 Will the termination be in an area that might have hazardous material in the vicinity (e.g., petrochemicals)?

Níl Tá

7 Will the termination be sited within a covered walkway? 8 Are there any restrictions stopping the fitting of a terminal guard if required? 9 Will the termination discharge over a boundary?

Níl Tá Níl Tá Níl Tá

10 Is a plume management kit required to circumvent the termination distances as required in table C.1?

Níl Tá

Uimh. 11 12
Níl.

Nuisance considerations Is the termination sited over a pathway that is likely to cause nuisance (e.g., head height or pluming towards users)? Is the termination likely to cause a nuisance to neighbours? Chimney/flue routes Will the flue be installed in a void that will not be able to satisfy a full visual inspection?

Níl Tá
Níl Tá
Níl Tá Níl Tá Níl Tá

Are there any restrictions that will prevent the flue from being supported throughout its entire length?

Níl Tá

Do the flue materials contravene building regulations (e.g., high risk buildings)?

Níl Tá

Will the flue route pass through any fire protected areas without the ability to maintain its protection?

Níl Tá

Will the flue pass through another dwelling?
Is the flue likely to be damaged due to its route/location (e.g., materials stored on it in a plantroom or storeroom)?

Níl Tá Níl Tá

Does the flue affect the integrity of the structure it is in (e.g., lintels, cavity trays, barriers, or membranes)?

Níl Tá

Má tá na freagraí go léir Gorm, ba chóir go mbeadh suíomh an mhúchán oiriúnach

Más Oráiste an freagra, níl an suíomh múcháin mí-oiriúnach, smaoinigh ar an suíomh nó ar an gcineál asraon múcháin a athbhreithniú nó déan teagmháil leis an Oifigeach Sláinte Comhshaoil ​​áitiúil chun cúnamh agus/nó faomhadh a fháil.

Lch 4 de 19

DRAWING 2 BOILER TERMINAL LOCATIONS ACCORDING TO IGEM/UP/10 EDITION 4 +A: 2016

TABLE 3 BOILER TERMINAL LOCATIONS ACORDING TO IGEM/UP/10 EDITION 4 +A: 2016

Cur síos ar an Suíomh

A

Díreach faoi bhun oscailt, bríce aeir, fuinneoga oscailte etc.#

B

Os cionn oscailt, bríce aeir, oscailt fuinneoga etc.

C

Go cothrománach chuig oscailt, bríce aeir, oscailt fuinneoga srl.#

D

Thíos gáitéir nó píopaí sláintíochta

E

Faoi na sceimhleacha

F

Thíos balcóin nó díon port cairr

G

Ó dhraenáil ingearach nó píopa ithreach

H

Ó choirnéal inmheánach nó seachtrach

I

Os cionn leibhéal na talún, an dín nó an bhalcóin

J

Ó dhromchla os comhair an teirminéil

K

Ó teirminéal atá os comhair an teirminéil

L

Ó oscailt sa charr port (m.sh. doras, fuinneog) isteach sa teaghais

M

Go hingearach ó chríochfort ar an mballa céanna

N

Go cothrománach ó chríochfort ar an mballa céanna

N+

Go hingearach ó chríochfort ar an díon céanna

P

Ó struchtúr ingearach ar an díon

Q

Os cionn a dtrasnaíonn an díon

CPM77 CPM96 CPM116 CPM144 CPM175

mm 2500

2500

2500

2500

2500

mm

631

760

896

1092

1294

mm

631

760

896

1092

1294

mm

200

200

200

200

200

mm

200

200

200

200

200

mm

Ní mholtar féach measúnú riosca UP10

mm

150

150

150

150

150

mm 1099

1513

1948

2573

3220

mm

300

300

300

300

300

mm 1100

1514

1948

2573

3220

mm 2083

2429

2792

3314

3855

mm

Ní mholtar féach measúnú riosca UP10

mm 2500

2500

2500

2500

2500

mm

600

600

900

900

n/a*

600

600

900

900

n/a*

mm 1500

1500

1500

1500

1500

mm

311

359

409

481

556

*Please contact Lochinvar technical support for guidance on CPM175 termination.
The table above should be used in conjunction with the following notes: · Distances shown ensure the boiler will operate without problems under most conditions, these distances can be reduced in certain circumstances · The above should be read in conjunction with the latest edition of BS5440-1 and IGEM UP10 · For boiler installation above 333kW nett input the table above should not be used, these installations are covered by the clean air act and must comply with its requirements in full, contact your local environmental health team for further guidance
For further guidance please contact Lochinvar Technical support
Lch 5 de 19

Table 4 risk assesment The table below is an excerpt from IGEMUP10 and should be used in conjunction with that document
De bhreis ar na ceanglais in IGEM/UP/10 Eagrán 4 +A: 2016 Roinn 8 faoi chlásal 8.7.3.3 agus Fíor 7 tugann an measúnú riosca seo a leanas treoir maidir le múcháin cothrománacha a shuíomh. Ba chóir an fhoirm seo a chomhlánú sula gcuirtear tús leis an obair agus ba chóir go ndéanfadh duine atá inniúil ar an measúnú riosca a dhéanamh.

Fearais Chineál C a bhfuil glan-ionchur teasa acu ar mó é ná 70 kW agus nach mó é ná 333 kW measúnú riosca um sceitheadh ​​múcháin ar leibhéal íseal (lena n-áirítear glan-ionchur teasa do ghrúpaí fearas)

Níl.

Maidir leis an suíomh múchán

Níl

Is the proposed flue termination within the distance in Figure K of a road, path,

1

track, thoroughfare, walkway, property boundary or area, which is used for general

Níl

rochtain phoiblí seachas chun críocha cothabhála?

2

Is the proposed flue termination within the distance in Figure K to a playground,

Níl

school, yard, seating area, or area where there may be a public gathering

3

If the proposed flue termination enclosed on more than two sides then does it

Níl

comply with the requirements of Figure 11B?

Is the proposed flue termination within the distance in Figure K of a surface or

4

building element that may be affected by corrosion or deterioration from plume

Níl

comhdhlúthán?

5

Is the proposed flue position in an area where vehicles could be parked within

Níl

distances from Figure 12 Line G to the flue?

6

Are there shrubs or trees within minimum distances shown on Figure K of the

Níl

proposed terminal position?

7

An bhfuil deireadh leis an múchán molta laistigh de thobar solais?

Níl

Are the products of combustion from the proposed flue position likely to build up

8

under unfavourable atmospheric conditions, due to poor cross flow of air caused by

Níl

enclosures or adjacent structures and/or likely to cause nuisance?

9

An dócha go mbeidh suíomh foirceannadh an mhúcháin ina núis d’áitribh in aice láimhe?

Níl

Rialacháin Foirgníochta Cuid J

10

An bhfuil an foirceannadh molta múcháin níos lú ná 300 mm ó theorainn an áitribh, arna thomhas ó thaobh an chríochfoirt go dtí an teorainn?

Níl

Maidir leis an Acht um Aer Glan

11

An bhfuil aschur iomlán na gcríochfort múcháin aonair, nó an ghrúpa teirminéil múcháin (má tá sé laistigh de 5U (féach A3.7)), níos mó ná 333 kW glan-ionchur teasa?

Níl

Ginearálta

12

An bhfuil aon bhreithnithe eile a theastaíonn don mheasúnú riosca seo, féach bileog ar leith.

Níl

13

Nótaí tráchta:

If all answers are Blue then the flue position should be suitable If any answer is Orange then the flue position is unsuitable, consider revising the position or type of flue outlet or contac t the local Environmental Health officer for assistance and/or approval
FAISNÉIS MHÚCHÁIN COIRE

Model Number FLUE DATA TYPE B23 Nominal flue diameter Maximum flue gas temp Flue gas temperature Flue draught requirements Available pressure for the flue system Maximum flue gas volume FLUE DATA TYPE C13 & C33 Nominal flue diameter Maximum flue gas temp FLUE DATA TYPE C43 & C53 Nominal flue diameter Maximum flue gas temp

mm °C °C mbar Pa g/s
mm °C
mm °C

CPM58

CPM77

80

5.59 to 28.9 6.52 to 38.6 80/125
80

CPM96

CPM116

CPM144

CPM175

100 95 85-95 -0.03 to -0.1 200 7.69 to 47.9 11.6 to 57.7

130 15.2 go 71.7 20.1 go 86.2

100/150 95

100

130

95

Lch 6 de 19

CÓRAIS MÚCHÁIN TEANGAINNEACH

CINEÁL COthrománach C13

CPMH001 CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS – CPM58, CPM77

Mír Uimh

Cur síos

Included CPM58

LV310757 CONCENTRIC HORIZONTAL TERMINAL – Ø80/125mm PP

1

44.8

M28925B

PLÁTAÍ MALLA TERMINAL

1

LV310735

Bend comhlárnacha 90° Ø80/125mm PP

1

16.1

Maximum resistance in the flue system 200pa

Iomlán 60.9

CPM77 80.1 28.7 108.8

Item No. LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M84481B

Additional Flue Ancillary Items Description CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP TELESCOPIC CONCENTRIC BEND 45° Ø80/125mm PP CONCENTRIC BEND 90° Ø80/125mm PP WALL CLAMP Ø125mm

Dimensions 250mm 500mm 1000mm 2000mm
240mm-360mm See Drawing Below See Drawing Below
N/B

CPMH003 CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS – CPM96, CPM116

Mír Uimh

Cur síos

Included CPM96 CPM116

LV310758B CONCENTRIC HORIZONTAL TERMINAL Ø100/150mm PP

1

58

84

M84410B CONCENTRIC BEND 90° Ø100/150mm PP SHORT RADIUS

1

23.6

34.2

Maximum resistance in the flue system 200pa

Iomlán 81.6 118.2

CPMH004 CONCENTRIC HORIZONTAL FLUE ASSEMBLY MODELS – CPM144

Mír Uimh

Cur síos

San áireamh

LV310758B

TERMINAL COMHTHREONACH TOMHÁNACHA Ø100/150mm PP

1

E61-001-172B

FEARAS COMHTHÓTHAITHE TEANGAINN

1

M84410B

Bend comhlárnach 90° Ø100/150mm PP GA GHEARR

1

Maximum resistance in the flue system 200pa

Iomlán

CPM144 129.9 52.9 182.8

Item No. M84405B M84402B M84412B M84413B M84421B M87196B

Additional Flue Ancillary Items Description
CONCENTRIC EXTENSION Ø100/150mm Cuttable CONCENTRIC EXTENSION Ø100/150mm PP FIXED
CONCENTRIC BEND 90° Ø100/150mm PP CONCENTRIC BEND 45° Ø100/150mm PP
SAMPLING POINT Ø100/150mm PP WALL CLAMP Ø150mm

CPM58-77 A=45mm B=62.5mm

Dimensions 500mm 1000mm
See Drawing Below See Drawing Below
115mm
CPM58-77 A=95mm B=110mm

CPM96-175 A=128mm B=128mm

CPM96-175 A=223mm B=208mm

Lch 7 de 19

PLUME KIT FOR USE WITH HORIZONTAL FLUE

PLUME MANAGEMENT KITS LG800008B PLUME MANAGEMENT KIT Ø80/125mm LG800009B PLUME MANAGEMENT KIT Ø100/150mm

Níl

Cur síos

1 CONCENTRIC BEND 90°-PP

2 CONCENTRIC HORIZONTAL PLUME KIT TERMINAL -PP

3 EXTENSION -PP CUTABLE (1000mm)

4 BEND 90°-PP

5 PLUME KIT BIRD GUARD

6 PLUME KIT FLUE EXIT-PP

7 WALL CLAMP

A INTERNAL DIAMETER

B EXTERNAL DIAMETER

CPM58 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm

CPM77 Ø80/125mm Ø80/125mm
Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø80mm Ø125mm

CPM96 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm

CPM116 Ø100/150mm Ø100/150mm
Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø100mm Ø150mm

CPM144 N/A N/A N/A N/A N/A N/A N/A N/A N/A

CPM175 N/A N/A N/A N/A N/A N/A N/A N/A N/A

The plume kit must not be used to correct an illegal terminal location

Lch 8 de 19

CINEÁL ingearach C33

CPMV001 SAMHAIL CHÓRTHA MÚCHÁIN ingearacha ingearacha – CPM58, CPM77

Item No LV310753 LV310745B

Description CONCENTRIC VERTICAL TERMINAL – Ø80/125mm PP CONCENTRIC EXTENSION – Ø80/125mm PP (500mm)

Included 1 1

CPM58 61.5 5.1

LV310742B CONCENTRIC EXTENSION – Ø80/125mm PP FIXED (1000mm)

1

10.2

Maximum resistance in the flue system 200pa

Iomlán 76.8

CPM77 109.8 9.05 18.1 136.95

Item No. LV310740B LV310745B LV310742B LV310743B LV310744B LV310734B LV310735B M87195B LV302520

Míreanna Coimhdeacha Múchán Breise
Description CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP FIXED CONCENTRIC EXTENSION – Ø80/125mm PP TELESCOPIC CONCENTRIC BEND 45° Ø80/125mm PP CONCENTRIC BEND 90° Ø80/125mm PP WALL CLAMP Ø130mm FLAT ROOF FLASHING Ø140mm ALU

Dimensions 250mm 500mm 1000mm 2000mm
240-360mm See Drawing Below See Drawing Below
N/AN/B

CPMV003 SAMHAIL CHÓRTHA MÚCHÁIN ingearacha ingearacha – CPM96, CPM116

Mír Uimh

Cur síos

Included CPM96

LV310754B

TERMINAL ingearach CONlárnach Ø100/150mm PP

1

80

M84405B CONCENTRIC EXTENSION Ø100/150mm (500mm) Cuttable

1

6.5

M84402B CONCENTRIC EXTENSION Ø100/150mm (1000mm) PP FIXED

1

13

Maximum resistance in the flue system 200pa

Iomlán 99.5

CPM116 115.9 9.45 18.9 144.25

Item No. M84405B M84402B M84412B M84413B M84421B M87196B

Míreanna Coimhdeacha Múchán Breise
Description CONCENTRIC EXTENSION Ø100/150mm Cuttable CONCENTRIC EXTENSION Ø100/150mm PP FIXED CONCENTRIC BEND 90° Ø100/150mm PP CONCENTRIC BEND 45° Ø100/150mm PP SAMPLING POINT Ø100/150mm PP WALL CLAMP Ø150mm

Dimensions 500mm 1000mm
See Drawing Below See Drawing Below
115mm

CPM58-77 A=45mm B=62.5mm
CPM96-175 A=128mm B=128mm

CPM58-77 A=95mm B=110mm
CPM96-175 A=223mm B=208mm

Concentric flue is unable to be used with CPM175

Lch 9 de 19

MÉID/RÍOMHAÍOCHTAÍ TIÚCHÁIN MÚCHÁIN

Friotaíocht in Pa

Mír

CPM 58 80/125 CPM 77 80/125 CPM 96 100/150 CPM 116 100/150

Críochfort balla

44.8

80.1

58

84

Críochfort díon

61.5

109.8

80

115.9

Feadán díreach (m)

10.2

18.1

13.0

18.9

45° Elbow

8.6

15.4

15.5

22.4

90° Elbow

16.1

28.7

23.6

34.2

Kit pluma

10

10

20

25

To be used for Lochinvar supplied M&G flue system components resistance only

CPM 144 100/150 129.9 179.2 29.2 34.7 52.9 n/a

CPM 175 100/150 188 259.3 42.2 50.2 76.5 n/a

Úsáid an tábla thíos chun friotaíocht iomlán an chórais múcháin a ríomh

Mír

Quantity Resistance Total

Wall terminal Roof terminal Straight tube (m) 45° Elbow 90° Elbow Plume kit

Friotaíocht Iomlán (Pa)

Total calculated system resistance must be less than 200pa

Lch 10 de 19

CÓRAIS MÚCHÁIN DHÚBHÁLACHTA CINEÁL C53

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM58, CPM77

Vertical Flue

Mír Uimh

Cur síos

No Required CPM58 CPM77

LM410084006

1

Críochfort ingearach - 130MM PP

38.8 38.8

LV305016

1

INLET AER Cothrománach Ø80mm

M28925B

1

PLÁTAÍ MALLA TERMINAL (PAIRE)

M85283 LM410084992

Leathnaitheoir Ø80mm – Ø100mm PP
Leathnaitheoir Ø100mm – Ø130mm PP

Maximum resistance in the flue system 200pa

1 1 Total

38.8 38.8

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM58, CPM77

Horizontal Flue

Níl

Mír Uimh

Cur síos

Required CPM58

LV310757B

TERMINAL COMHTHREONACH TOMHÁNACHA Ø80/125mm PP

1

29.86

LV305016

INLET AER Cothrománach Ø80mm

1

M28925B

PLÁTAÍ MALLA TERMINAL (PAIRE)

1

Maximum resistance in the flue system

200p

Iomlán

29.86

CPM77 53.4
53.4

Item No. LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B

Additional Flue Ancillary Items Description
EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP TELESCOPIC BEND 45° 80mm PP BEND 90° 80mm PP WALL CLAMP Ø80mm

Dimensions 250mm 500mm 1000mm 2000mm
240-360mm See Drawing Below See Drawing Below
N/B

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM96, CPM116

Vertical Flue

Item No LM410084006

Cur síos
VERTICAL TERMINAL 130MM PP

No Required 1

CPM96 38.8

LV305039

HORIZONTAL AIR INLET

1

Ø100mm

M28925B

TERMINAL WALL

1

PLATES (PAIR)

LM410084992 EXPANDER Ø100mm –

1

Ø130mm PP

Maximum resistance in the flue system 200pa

Iomlán

38.8

CPM116 38.8

38.8

Lch 11 de 19

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM96, CPM116

Horizontal Flue

Níl

Mír Uimh

Cur síos

Required CPM96

CONCENTRIC

LV310758B

HORIZONTAL TERMINAL

1

38.66

Ø100/150mm PP

LV305039B

INLET AER COTHROMACH Ø100mm ALU

1

Maximum resistance in the flue system 200pa

Iomlán 38.66

CPM116 56
56

Item No. M85176B M85177B M85181B M85182B M87193B

Additional Flue Ancillary Items Description EXTENSION Ø100mm PP CUT TO LENGTH EXTENSION Ø100mm PP CUT TO LENGTH BEND 90° 100mm PP BEND 45° 100mm PP WALL BAND (100mm)

Dimensions 500mm 1000mm
See Drawing Below See Drawing Below
n/a

CPM TWIN-PIPE FLUE ASSEMBLY MODELS CPM144, CPM175

Vertical Flue

Mír Uimh

Cur síos

No Required CPM144

LM410084006 VERTICAL TERMINAL –

1

38.8

130MM PP

LV307178

HORIZONTAL AIR INLET

1

Ø130mm ALU

Maximum resistance in the flue system 200pa

Iomlán

38.8

CPM175 38.8

38.8

Item No M70242 M70251 M70252 M87195

Additional Flue Ancillary Items Description
EXTENSION Ø130mm PP BEND 90° PP BEND 45° PP WALL CLAMP

Dimensions 1000mm 130mm 130mm 130mm

CPM58CPM77 A=72.5mm, B=72.5mm
CPM96CPM116 A=78mm, B=65mm

CPM58CPM77 A=110mm, B=110mm
CPM96CPM116 A=78mm, B=65mm

Lch 12 de 19

MÉID/RÍOMHAÍOCHTAÍ MÚCHÁIN MHÚCHÁIN Píobáin

Mír

Resistance (Pa) Size (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Feadán díreach (in aghaidh an mhéadair)

80

4.6

8.2

X

X

Straight tube (per metre) 100

1.3

2.3

3.5

5.0

Straight tube (per metre) 130

0.3

0.6

0.9

1.2

45° Elbow

80

4.2

7.6

X

X

45° Elbow

100

2.9

5.1

7.9

11.5

45° Elbow

130

0.6

1.0

1.6

2.3

90° Elbow

80

10.1 18.0

X

X

90° Elbow

100

4.6

8.3

12.7

18.4

90° Elbow

130

1.4

2.4

3.7

5.4

Le húsáid le haghaidh friotaíocht comhpháirteanna an chórais inlet aeir M&G amháin a sholáthair Lochinvar

CPM 144 n/a n/a 1.9 n/a n/a 3.5 n/a n/a 8.4

CPM 175 n/a n/a 2.8 n/a n/a 5.1 n/a n/a 12.1

Mír

Resistance (Pa) Size (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Feadán díreach (in aghaidh an mhéadair)

80

4.0

7.1

X

X

Straight tube (per metre) 100

1.1

2.0

3.0

4.4

Straight tube (per metre) 130

0.3

0.5

0.7

1.1

45° Elbow

80

3.7

6.5

X

X

45° Elbow

100

2.5

4.4

6.8

9.9

45° Elbow

130

0.5

0.9

1.4

2.0

90° Elbow

80

8.7

15.6

X

X

90° Elbow

100

4.0

7.1

11.0

16.0

90° Elbow

130

1.2

2.1

3.2

4.7

Vertical exhaust terminal

61.5 109.8

80

115.9

Vertical single terminal

To be used for Lochinvar supplied M&G flue exhaust system components resistance only

CPM 144 n/a n/a 1.7 n/a n/a 3.0 n/a n/a 7.2 179.2 38.8

CPM 175 n/a n/a 2.4 n/a n/a 4.4 n/a n/a 10.5 259.3 38.8

Úsáid an tábla thíos chun friotaíocht an chórais múcháin a ríomh.

Múchán sceite

Item Straight tube (m) 45° Elbow 90° Elbow

Quantity Resistance Total

Inlet Aeir

Teirminéal Ingearach Comhlárnach

sceite múchán Iomlán Friotaíocht (Pa)

Mír

Friotaíocht Cainníochta

Feadán díreach (m)

45° Elbow

90° Elbow

Inlet Aeir

Inlet aeir Iomlán Friotaíocht (Pa)

Ionraon aeir agus sceite múchán Iomlán Friotaíocht (Pa)

Iomlán

Total calculated system resistance must be less than 200pa

Lch 13 de 19

COINBHINSIÚIN (Sceite AMHÁIN) CÓRAIS MHLÚCHÁIN CINEÁL B23

CPM CONVENTIONAL FLUE ASSEMBLY MODELS CPM58, CPM77

Mír Uimh

Cur síos

No Required CPM58

LV305030B

GHARDA IONTÓGÁLA AER FEARAIS Ø80/125mm

1

10.8

LM410084006

Críochfort ingearach - 130MM PP

1

38.8

M85283

Leathnaitheoir Ø80mm – Ø100mm PP

1

LM410084992

EXPANDER Ø100mm Ø130mm PP

1

Maximum resistance in the flue system 200pa Total

51.8

CPM77 19.2 38.8 92.4

Item No. LV310718B M85271B M85272B LV310721B LV310722B M85292B M85291B M87191B

Additional Flue Ancillary Items Description
EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP CUT TO LENGTH EXTENSION – Ø80mm PP TELESCOPIC BEND 45° 80mm PP BEND 90° 80mm PP WALL CLAMP Ø80mm

Dimensions 250mm 500mm 1000mm 2000mm
240-360mm See Drawing Below See Drawing Below
N/B

CPM CONVENTIONAL FLUE ASSEMBLY MODELS CPM96, CPM116

Níl

Mír Uimh

Cur síos

Required CPM96

LV304872B

GHARDA IONTÓGÁLA AER FEARAIS Ø100/150mm

1

11.6

LM410084006

VERTICAL TERMINAL 130MM PP

1

38.8

Maximum resistance in the flue system

200p

Iomlán

64.9

CPM116 16.8 38.8
94.06

CPM CONVENTIONAL FLUE ASSEMBLY MODELS CPM144, CPM175

Mír Uimh

Cur síos

No Required CPM144 CPM175

M81660

APPLIANCE AIR INLET

1

GUARD Ø130mm

LM410084006 VERTICAL TERMINAL –

1

130MM PP

8.7

12.6

38.8

38.8

Maximum resistance in the flue system 200pa

Iomlán

47.5

51.4

Item No M70242 M70251 M70252 M87195

Additional Flue Ancillary Items Description
EXTENSION Ø130mm PP BEND 90° PP BEND 45° PP WALL CLAMP
CPM58-CPM77 A=72.5mm,B=72.5mm CPM96-CPM116 A=78mm, B=65mm

Dimensions 1000mm 130mm 130mm 130mm
CPM58-CPM77 A=110mm, B=110mm CPM96-CPM116 A=78mm, B=65mm

Lch 14 de 19

MÉID/RÍOMHAÍOCHTAÍ COINBHINSIÚNTA MÚCHÁIN

Mír

Resistance (Pa) Size (mm)
CPM 58 CPM 77 CPM 96 CPM 116

Feadán díreach (in aghaidh an mhéadair)

80

4.0

7.1

X

X

Straight tube (per metre) 100

1.1

2.0

3.0

4.4

Straight tube (per metre) 130

0.3

0.5

0.7

1.1

45° Elbow

80

3.7

6.5

X

X

45° Elbow

100

2.5

4.4

6.8

9.9

45° Elbow

130

0.5

0.9

1.4

2.0

90° Elbow

80

8.7

15.6

X

X

90° Elbow

100

4.0

7.1

11.0

16.0

90° Elbow

130

1.2

2.1

3.2

4.7

Vertical single terminal

Le húsáid le haghaidh friotaíocht comhpháirteanna an chórais inlet aeir M&G amháin a sholáthair Lochinvar

CPM 144 n/a n/a 1.7 n/a n/a 3.0 n/a n/a 7.2 38.8

CPM 175 n/a n/a 2.4 n/a n/a 4.4 n/a n/a 10.5 38.8

Úsáid an tábla thíos chun friotaíocht an chórais múcháin a ríomh.

Mír

Friotaíocht Cainníochta

Feadán díreach (m)

45° Elbow

90° Elbow

Teirminéal Ingearach Comhlárnach

sceite múchán Iomlán Friotaíocht (Pa)

Iomlán

Total calculated system resistance must be less than 200pa

Lch 15 de 19

CÓRAIS MHLÚCHÁIN A ÚSÁIDEANN MÚCHÁN NACH BHFUIL SOLÁTHAIR GAN CHINEÁL LOCHINVAR C63
In general, boilers are certified with their own purpose supplied Concentric or Twin Pipe flue systems, C63 certified appliances allow the installer to use other flue systems when installing the boiler however, they must be of a suitable minimum standard as per table below.

Teaghrán CE Ábhar gáis múcháin
Europea n standard Temperature
clas s Pressure class Resistance to condensate
Corrosio n resistance
clas s Metal: liner specifications
Soot fire resistance
clas s Distance to combustible
material Plastics: Plastics: fire behaviour Plastics:

min. eis PP EN 14471 T120

P1

W

min. eis RVS EN 1856-1 T120

P1

W

1

n/a

O

1

L20040

O

Ábhar

coire

dnom

Doutside

dinside

Linsert

SS

CPM58-CPM77 80 80 +0,3/ -0,7 81 +0,3/ -0,3 50 +2/ -2

SS

CPM96-CPM116 100 100 +0,3/ -0,7 101 +0,3/ -0,3 50 +2/ -2

SS CPM144-CPM175 130 130 +0,3/ -0,7 131 +0,5/ -0,5 50 +2/ -2

PP

CPM58-CPM77 80 80 +0,6/ -0,6

50 +20/-2

PP

CPM96-CPM116 100 100 +0,6/ -0,6

50 +20/-2

PP CPM144-CPM175 130 130 +0,9/ -0,9

50 +20/-2

30

I of E C/E

L

40

n/an/an/a

Níor cheart píobán múchán alúmanaim a úsáid ar an bhfearas seo mar d'fhéadfadh teip roimh am ar an malartóir teasa a bheith mar thoradh air agus go n-eascróidh sé an bharántas.

COMHCHÓRAIS MHUITHE

Lochinvar can supply a PP common flue header see separate guide available at www.lochinvar.ltd.uk
Alternatively the installer can use a flue installation specialist to design and supply a separate flue system under the flue designation C63 using the specifications shown on page 13 and information in the table below.
Any installations using flue type C63 must be designed and installed in compliance with any local Building or planning regulations, but as these systems use a flue system not supplied by Lochinvar, Lochinvar cannot comment / advise or provide support on the design of this type of flue system. To design such a flue system, the installer/contractor must consult a specialist flue supplier who will be responsible for the design and installation of the separate flue system. When designing the type C63 flue system, the instructions in the Installation Manual, provided with the boiler, must be taken into account. Lochinvar will provide pressure loss figures for the specific units, but other than that, Lochinvar cannot provide support on Common Flue requests because flue certification is limited to the certified categories in the table on page 2. Lochinvar cannot accept any responsibility for Flue system design.

Available pressure at the flue gas outlet Flue Gas Mass Rate (G20) 96% (g/sec) Flue Gas Mass Rate (G20) 25% (g/sec) Flue Gas Mass Rate (G31) 96% (g/sec) Flue Gas Mass Rate (G31) 25% (g/sec)

CPM 58
200Pa 22.6 5.7 23.2 5.8

CPM 77
200Pa 29.8 7.5 30.6 7.7

CPM 96
200Pa 37.1 9.3 38.8 9.7

CPM 116
200Pa 45.1 11.3 46.2 11.6

CPM 144
200Pa 55.6 13.9 57 14.3

CPM 175
200Pa 67.3 16.8 69 17.3

The CPM boiler range does not have an internal Non Return Valve (NRV) as such any flue must be designed on zero or negative pressure unless a suitable NRV is fitted and if necessary interlocked to the appliance. Non Return Valves are included with the Lochinvar common flue header.

Lch 16 de 19

FOIRM ORDUITHE AGUS NÓTAÍ

Mír Uimh.

Níl gá

Nótaí-Míreanna le hordú
Nótaí

Déan teagmháil le seirbhís do chustaiméirí Lochinvar chun míreanna múcháin breise a ordú ar 01295 269981

Lch 17 de 19