SP100 Display and Controller
“
Specifications
- Model: Level Display | Controller
- Part Number: SP100
- Enclosure: NEMA 4X
- Display: Bright LED
- Mounting: Pipe | Pole Mount Brackets
- Features: Push Buttons, Polycarbonate Cover
- Output Options: SP100-A, SP100-V, SP100-A-V
Product Usage Instructions
Safety Information
It is crucial to follow the safety guidelines provided to ensure
safe operation and prevent accidents or damage to the unit:
- Do not exceed maximum temperature or pressure
specifications. - Always wear safety goggles or face-shield during installation
and service. - Do not alter product construction.
Basic Requirements & User Safety
Follow these guidelines for proper usage and maintenance of the
unit:
- Avoid using the unit in areas with excessive shocks,
vibrations, dust, humidity, corrosive gasses, or oils. - Avoid areas with explosion risks, significant temperature
variations, condensation, ice, or direct sunlight. - Maintain ambient temperature within recommended values;
consider forced cooling if needed. - Installation should be done by qualified personnel following
safety and EMC regulations. - Properly connect GND input to PE wire.
- Ensure correct unit setup according to the application to
prevent operation issues. - In case of malfunction, use additional safety systems to
prevent threats. - Switch off and disconnect power before troubleshooting or
maintenance. - Neighboring equipment should meet safety standards and have
overvoltage protection. - Do not attempt to repair or modify the unit yourself; submit
defective units for repairs at an authorized center.
Installation and Environment
The unit is designed for industrial environments and must not be
used in households:
- Designed for harsh corrosive environments with NEMA 4X
enclosure. - Mount using pipe or pole brackets for stability.
- Bright LED display for clear visibility.
- Multiple output options available for flexibility in
applications.
FAQ
Q: Can I repair the unit myself if it malfunctions?
A: No, do not attempt to repair the unit yourself as it has no
user-serviceable parts. Submit defective units for repairs at an
authorized service center.
Q: What should I do if the unit exceeds recommended temperature
values?
A: If the ambient temperature exceeds recommended values,
consider using forced cooling methods such as a ventilator to
maintain proper operating conditions.
“`
LevelPro® — ShoPro® SP100
Level Display | Controller
Quick Start Manual
Read the user’s manual carefully before starting to use the unit. Producer reserves the right to implement changes without prior notice.
25-0657 © Icon Process Controls Ltd.
1
LevelPro® — ShoPro® SP100
Level Display | Controller
Safety Information
DO NOT exceed maximum temperature or pressure specifications!
ALWAYS wear safety goggles or face-shield during installation and/or service!
DO NOT alter product construction!
Warning | Caution | Danger
Indicates a potential hazard. Failure to follow all warnings may lead to equipment damage, or failure, injury, or death.
Note | Technical Notes
Highlights additional information or detailed procedure.
Basic Requirements & User Safety
? Do not use the unit in areas threatened with excessive shocks, vibrations, dust, humidity, corrosive gasses and oils.
? Do not use the unit in areas where there is risk of explosions.
? Do not use the unit in areas with significant temperature variations, exposure to condensation or ice. ? Do not use the unit in areas exposed to direct sunlight.
? Make sure that the ambient temperature (e.g. inside the control box) does not exceed the recommended values. In such cases forced cooling of the unit must be considered (e.g. by using a ventilator).
? The manufacturer is not responsible for any damages caused by inappropriate installation, not maintaining the proper environmental conditions and using the unit contrary to its assignment.
? Installation should be conducted by qualified personnel . During installation all available safety requirements should be considered. The fitter is responsible for executing the installation according to this manual, local safety and EMC regulations.
? GND input of device should be connected to PE wire. ? The unit must be properly set-up, according to the application. Incorrect configuration can cause defective operation, which
can lead to unit damage or an accident.
? If in the case of a unit malfunction there is a risk of a serious threat to the safety of people or property additional, independent systems and solutions to prevent such a threat must be used.
? The unit uses dangerous voltage that can cause a lethal accident. The unit must be switched off and disconnected from the power supply prior to starting installation of troubleshooting (in the case of malfunction).
? Neighboring and connected equipment must meet the appropriate standards and regulations concerning safety and be equipped with adequate overvoltage and interference filters.
? Do not attempt to disassemble, repair or modify the unit yourself. The unit has no user serviceable parts. Defective units must be disconnected and submitted for repairs at an authorized service center.
The unit is designed for operation in an industrial environment and must not be used in a household environment or similar.
25-0657 © Icon Process Controls Ltd.
2
LevelPro® — ShoPro® SP100
Level Display | Controller
Pipe | Pole Mount Brackets
NEMA 4X Enclosure
Bright LED Display
The ShoPro® Series Level Display | Controller is engineered to be the most durable and dependable wall or pipe-mount remote display in the industry. This all-in-one unit is ready to use straight out of the box, featuring a bright LED display, NEMA 4X enclosure, polycarbonate cover, cord grips, and plastic captive screws.
Designed for industrial applications, it withstands even the harshest corrosive environments and is available with multiple output options.
Features
? All-in-one | Out of the Box Ready to Use ? Visual Alarm — High | Low Level ? NEMA 4X Enclosure ? Corrosion Resistant Thermoplastic ? Cord Grips Included No Tools Required
Push Buttons
Polycarbonate Cover
Model Selection
ShoPro® SP100 — Liquid Level LED Display
Part Number SP100
SP100-A SP100-V SP100-A-V
Input 4-20mA 4-20mA 4-20mA 4-20mA
Output 4-20mA 4-20mA + Audible 4-20mA + Visual 4-20mA + Audible & Visual
Technical Specifications
General
Display Displayed Values Transmission Parameters Stability
LED | 5 x 13mm High | Red -19999 ~ 19999 1200…115200 bit/s, 8N1 / 8N2 50 ppm | °C
Housing Material
Polycarbonate
Protection Class
NEMA 4X | IP67
Input Signal | Supply
Standard Voltage
Current: 4-20mA 85 – 260V AC/DC | 16 – 35V AC, 19 – 50V DC*
Output Signal | Supply
Standard Voltage Passive Current Output *
4-20mA 24VDC 4-20mA | (Operating Range Max. 2.8 – 24mA)
Performance
Accuracy
0.1% @ 25°C One Digit
Accuracy According to IEC 60770 – Limit Point Adjustment | Non-Linearity | Hysteresis | Repeatability
Temperatures
Operating Temperatures
-20 to 158°F | -29 to 70°C
*Optional
25-0657 © Icon Process Controls Ltd.
3
LevelPro® — ShoPro® SP100
Level Display | Controller
Installation Instructions
The unit has been designed and manufactured in a way assuring a high level of user safety and resistance to interference occurring in a typical industrial environment. In order to take full advantage of these characteristics installation of the unit must be conducted correctly and according to the local regulations. ? Read the basic safety requirements on page 2 prior to starting the installation. ? Ensure that the power supply network voltage corresponds to the nominal voltage stated on the unit’s identification label.
The load must correspond to the requirements listed in the technical data. ? All installation works must be conducted with a disconnected power supply. ? Protecting the power supply connections against unauthorized persons must be taken into consideration.
Package Contents
Please verify that all listed parts are consistent, undamaged and included in the delivery / your specified order. After removing the unit from the protective packaging, please verify that all listed parts are consistent, undamaged and included in the delivery/your specified order.
Any transportation damage must be immediately reported to the carrier. Also, write down the unit serial number located on the housing and report the damage to the manufacturer.
Wall Mounting
1
2
3
111.75 mm
62.5mm
Ø4.4
To install device on the wall, pinholes should be made. The distances between holes are mentioned above. This part of the case should be mounted to a wall by screws.
R
dSP
SET
F
Sht
www.iconprocon.com
AL R1 SP100 R2
Loosen Box Screws & Open Display Cover
4
5
6
R
dSP SET F
Sht
www.iconprocon.com
AL R1 SP100 R2
Remove Display Cover
R
dSP SET F
Sht
www.iconprocon.com
AL R1 SP100 R2
Mount on Wall using Screws
25-0657 © Icon Process Controls Ltd.
R
dSP SET F
Sht
www.iconprocon.com
AL R1 SP100 R2
Tighten Srews
R
dSP SET F
Sht
www.iconprocon.com
AL R1 SP100 R2
Place Display Cover and Tighten Box Screws
4
LevelPro® — ShoPro® SP100
Level Display | Controller
Pipe | Pole Clamp Installation
1
2
3
Do Not Use Tools
Do Not Use Tools
Open Clamp
Wiring
1
R
SP100
ddSSPP SSEETT F
SShhtt
www.iconprocon.com
AL
AL
R R1
1
SP100
RR2 2
2
R
SP100
dSP dSP
SET SET
F
F
Sht Sht
w w www.wi.cicoonpnropcorn.ococm o n . c o m
AL AL
R1 SP100 R2 R 1
R2
Lock Clamp on Pipe
3
R
SP100
dSP dSP
SET SET
F
F
Sht Sht
w w w ww.wi.cicoonpnropcorn.ococmo n . c o m
AL R1 SAPL100 R2 R 1
R2
Wire Clamp Open
Turn Cord Grip Counter-Clockwise
4
R SP100
dSP
SET
F
dSP SET
F
Sht Sht
w w w ww.wi.cicoonpnropcorn.ococm o n . c o m
AL AL
R1 SP100 R2 R 1
R2
Power Red Tab : 120VAC wire Blue Terminals : 0VAC wire
4-20mA Output
Sensor Red Tab : +mA Blue Tab : -mA
Remove Cord Grip
5
R
SP100
dSP dSP
SET SET
F
F
Sht Sht
w w www.wi .cicoonpnropcorn.ococmo n . c o m
AL R1 SAPL100 R2 R 1
R2
Insert Wire into Cord Grip
6
R
SP100
dSP
SET
F
dSP SET
F
Sht Sht
w w w ww.wi.cicoonpnropconr.coom c o n . c o m
AL R1 SP A1L 00 R2 R 1
R2
Insert Wire in theTerminals & Close Tabs
Turn Cable Grip Clockwise to Tighten
25-0657 © Icon Process Controls Ltd.
5
LevelPro® — ShoPro® SP100
Level Display | Controller
Dimensions
130.00
85.25
80.00
127.00
111.75
62.50
85.25
Wiring Diagram
130.00
SP100
dSP SET F
AL R1 R2
Sht
www.iconprocon.com
Power
Yellow
Output
Yellow
Input
Yellow
Red
Blue
Red
Blue
Red
Blue
25-0657 © Icon Process Controls Ltd.
6
LevelPro® — ShoPro® SP100
Level Display | Controller
Wiring – ShoPro + 100 Series Submersible Level Sensor
SP-100
ShoPro Tank Level Display
Tab 2 : -mA from Sensor (Black) Tab 3 : +mA from Sensor (Red)
34 12
LP100
Junction Box
SP100
dSP SET F
AL R1 R2
Sht
www.iconprocon.com
Power Supply 120VAC
Red Tab : +ve from Junction Box (Green) Blue Tab : -ve from Junction Box (Blue)
Red Black
+mA
-mA
100 Series
Submersible Liquid Level Sensor
Wiring – ShoPro + ProScan®3 Radar Level Sensor
SP-100
ShoPro Tank Level Display
SP100
dSP SET F
AL R1 R2
Sht
www.iconprocon.com
Power Supply 120VAC
Red Tab : +ve from Junction Box (Red) Blue Tab : -ve from Junction Box (Black)
Red Wire : +ve Terminal Black Wire : -ve Terminal
Rotate display anti-clockwise to access wiring terminals
ProScan®3
Radar Liquid Level Sensor
25-0657 © Icon Process Controls Ltd.
7
LevelPro® — ShoPro® SP100
Level Display | Controller
Display Description & Button Functions
Bright Large Display
Alarm LED Indicator (AL)
Programming Push Buttons
SP100
dSP SET F
AL R1 R2
Sht
www.iconprocon.com
dSP = Display Programming Menu (Press + Hold for 3 sec.)
SET = Save the Value
F
=
[F] []Press & Hold Back Menu
for
3
SEC
for
Alarm
Set
= Changing the Values
Sht = [F] Back to Main Display [ ] Changing Menu
Programming 4-20mA
STEPS
1
Main Menu
dSP
3 Sec.
2
4mA Settings
SET
3
Enter 4mA Value
SET
F DISPLAY
Move Selection Left
Sht
Change Digit Value
OPERATION
Main Display
R
SP100
ddSSPP SSEETT FF
FSht
www.iconprocon.com www.iconprocon.com
AL
AL R1 R1 SP100 RR22
4mA Settings 4mA = Low Level
Enter 4mA Value Factory Default = 0
4mA Empty
4
20mA Settings
SET
5
Enter 20mA Value
SET
20mA Settings 20mA = High Level
Enter 20mA Value
20mA
R
SP100
ddSSPP SSEETT FF
SFht
www.iwcwow.incopnprroococn.oconm .com
AL AL RR1 1SP100 RR2 2
6
Main Display
Main Display
dSPL = Low Level Value | Empty or Lowest Liquid Level | Factory Default = 0. dSPH = High Level Value | Enter Maximum Level.
25-0657 © Icon Process Controls Ltd.
8
LevelPro® — ShoPro® SP100
Level Display | Controller
Alarm Programming
STEPS
1
Main Display
F
3 Sec.
2
Alarm 1 Settings
SET
3
Alarm 1 Value
SET
4
Alarm 2 Settings
SET
5
Alarm 2 Value
SET
6
Hysteresis
SET
7
Hysteresis Value
SET
8
Main Display
DISPLAY
Main Display
F Move Selection Left OPERATION
Sht Change Digit Value
Alarm 1 Settings
Alarm 1 Value Enter Alarm 1 Value
Alarm 2 Settings
Alarm 2 Value Enter Alarm 2 Value
Hysteresis
Hysteresis Value Enter Hysteresis Value
Main Display
Alarm Mode Selection
ALt No.
ALt = 1 ALt = 2 ALt = 3
· CV AL1 AL1 ON · CV < (AL1-HYS) AL1 OFF
Description
· CV AL2 AL2 ON · CV < (AL2-HYS) AL2 OFF
· CV AL1 AL1 ON · CV < (AL1-HYS) AL1 OFF
· CV AL2 AL2 ON · CV > (AL2+HYS) AL2 OFF
· CV AL1 AL1 ON · CV > (AL1+HYS) AL1 OFF
· CV AL2 AL2 ON · CV > (AL2+HYS) AL2 OFF
CV = Current Value
25-0657 © Icon Process Controls Ltd.
Note:
To access the Alarm Mode Selection Menu, press
SET + F
3 Sec.
And then press
SET X 6
9
LevelPro® — ShoPro® SP100
Level Display | Controller
Reset Programming
STEPS
1
Main Display
SET + F
3 Sec.
2
Lock Settings
SET X 2
3
Input Settings
SET X 7
4
Home Screen
SET + F
3 Sec.
5
Lock Settings
SET X 2
6
Input Settings
SET X 7
DISPLAY
Main Display
F Move Selection Left OPERATION
Sht Change Digit Value
Lock Settings
Factory Default : Lk.10 Otherwise meter will enter Lockout Mode*
Input Settings
Int.2 will be displayed. Change Int.2 to Int.4 using
or Sht button.
Main Display
The Value displayed will be 0.00. This value is equal to 4mA output from the sensor
Lock Settings
Input Settings
Int.4 will be displayed. Change Int.4 to Int.2 using
or Sht button.
7
Main Display
SET + F
3 Sec.
8
Lock Settings
SET X 3
Main Display The value displayed is equal to 20mA output from the sensor.
Lock Settings
9
Decimal Point
SET X 6
Decimal Point Change decimal point to 0. (dP.0)
10
Main Display
Main Display Reset Completed
After reset, the dSPL (4mA) and dSPH (20mA) values must be reconfigured. See “Programming 4-20mA” (Page 8) for details.
25-0657 © Icon Process Controls Ltd.
10
LevelPro® — ShoPro® SP100
Level Display | Controller
Warranty, Returns and Limitations
Warranty
Icon Process Controls Ltd warrants to the original purchaser of its products that such products will be free from defects in material and workmanship under normal use and service in accordance with instructions furnished by Icon Process Controls Ltd for a period of one year from the date of sale of such products. Icon Process Controls Ltd obligation under this warranty is solely and exclusively limited to the repair or replacement, at Icon Process Controls Ltd option, of the products or components, which Icon Process Controls Ltd examination determines to its satisfaction to be defective in material or workmanship within the warranty period. Icon Process Controls Ltd must be notified pursuant to the instructions below of any claim under this warranty within thirty (30) days of any claimed lack of conformity of the product. Any product repaired under this warranty will be warranted only for the remainder of the original warranty period. Any product provided as a replacement under this warranty will be warranted for the one year from the date of replacement.
Returns
Products cannot be returned to Icon Process Controls Ltd without prior authorization. To return a product that is thought to be defective, go to www.iconprocon.com, and submit a customer return (MRA) request form and follow the instructions therein. All warranty and non-warranty product returns to Icon Process Controls Ltd must be shipped prepaid and insured. Icon Process Controls Ltd will not be responsible for any products lost or damaged in shipment.
Limitations
This warranty does not apply to products which: 1) are beyond the warranty period or are products for which the original purchaser does not follow the warranty procedures outlined above; 2) have been subjected to electrical, mechanical or chemical damage due to improper, accidental or negligent use; 3) have been modified or altered; 4) anyone other than service personnel authorized by Icon Process Controls Ltd have attempted to repair; 5) have been involved in accidents or natural disasters; or 6) are damaged during return shipment to Icon Process Controls Ltd reserves the right to unilaterally waive this warranty and dispose of any product returned to Icon Process Controls Ltd where: 1) there is evidence of a potentially hazardous material present with the product; or 2) the product has remained unclaimed at Icon Process Controls Ltd for more than 30 days after Icon Process Controls Ltd has dutifully requested disposition. This warranty contains the sole express warranty made by Icon Process Controls Ltd in connection with its products. ALL IMPLIED WARRANTIES, INCLUDING WITHOUT LIMITATION, THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE, ARE EXPRESSLY DISCLAIMED. The remedies of repair or replacement as stated above are the exclusive remedies for the breach of this warranty. IN NO EVENT SHALL Icon Process Controls Ltd BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES OF ANY KIND INCLUDING PERSONAL OR REAL PROPERTY OR FOR INJURY TO ANY PERSON. THIS WARRANTY CONSTITUTES THE FINAL, COMPLETE AND EXCLUSIVE STATEMENT OF WARRANTY TERMS AND NO PERSON IS AUTHORIZED TO MAKE ANY OTHER WARRANTIES OR REPRESENTATIONS ON BEHALF OF Icon Process Controls Ltd. This warranty will be interpreted pursuant to the laws of the province of Ontario, Canada.
If any portion of this warranty is held to be invalid or unenforceable for any reason, such finding will not invalidate any other provision of this warranty.
For additional product documentation and technical support visit:
www.iconprocon.com | e-mail: sales@iconprocon.com or support@iconprocon.com | Ph: 905.469.9283
by
Phone: 905.469.9283 · Sales: sales@iconprocon.com · Support: support@iconprocon.com
25-0657 © Icon Process Controls Ltd.
11