Ambientika RS485 Proqramlaşdırma Sud küləyi
Naqillər
In installations connecting several ventilation units, serial communication occurs via an RS485 interface. The connection occurs via the differential signal lines A, B and a common earth line (GND). The units are connected to each other in a bus topology. It is mandatory to connect a terminating resistor of 120 ohms between line A and line B on the last physical unit of the bus line, to ensure the signal quality.
Terminal 3: B
Terminal 4: A
Terminal 5: GND
In addition to the correct wiring of the RS485 lines, a manufacturer-specific interface module is required for integration into various automation systems: for KNX-based systems, an RS485 extension (e.g. as a KNX-TP/RS485 gateway) is available, which converts the levels and protocols between the KNX bus and the RS485 devices. In Loxone systems, the official Loxone RS485 extension is used instead, which is integrated directly into the Loxone Miniserver environment.
When selecting the appropriate interface, it is particularly important to make sure that it is not a Modbus RS485 gateway, but a transparent, serial RS485 gateway. Südwind uses proprietary protocols that do not match with the Modbus standard.
DIP keçid parametrləri
As the central control occurs via KNX or Loxone, the system completely takes over the tasks of the wall panel. The main unit is configured as a master with wall panel.
Sistemdəki bütün digər bölmələr DIP açarları vasitəsilə qul kimi təyin olunur. Tətbiqdən asılı olaraq, məsələnampTəchizat və egzoz havası sistemləri kimi, köməkçi qurğular sinxron və ya asinxron şəkildə idarə oluna bilər.
Master mit Fernbedienung = Master with remote control
Master mit Wandpanel = Master with wall panel
Slave gegenläufig Master = Slave – Master operate asynchronously
Slave gleichläufig Master = Slave -Master operate synchronously
Parametrləşdirmə
RS485 uzantısında konfiqurasiya ediləcək serial rabitə parametrləri:
- baud rate 9600 [bit/s]
- 8 məlumat biti
- 1 stop bit
- paritet yoxdur
Mesajlar mərkəzi idarəetmədən 500 ms intervalla bütün qoşulmuş bölmələrə göndərilir.
These messages consist of a sequence of bytes in hexadecimal numbering (hex-numbers). Each element, such as \x02 or \x30, represents a single byte in hexadecimal format.
Status enquiry
Status sorğusu mərkəzi idarəetmədən göndərilir və Master bölmə tərəfindən qiymətləndirilir. Bu sorğu göndərilərkən mərkəzi idarəetmə xəttin mövcud olduğundan əmin olmaq üçün 3 saniyə ərzində mesajların göndərilməsini dayandırır.
Vəziyyət | Əmr |
Status enquiry | \x02\x30\x32\x30\x32\x03 |
If there is no active sensor or status, the Master unit replies with a 11 bytes long message in the following hexadecimal format: \x02\x30\x30\x30\x30\x30\x30\x30\x30\x30\x30\x03.
The first byte \x02 sets the beginning of the message (start frame) and is followed by two bytes \x30\x30 representing the „status message“ (\x30 corresponds to “0” in ASCII-characters).
The following 8 bytes represent the single status registers. Each of these bytes corresponds to a specific message. Only the first four registers are used: The first register stands for the twilight sensor, the second and the third for the filter change alarm and the fourth one for the humidity alarm. A received byte \x30 corresponds to “0” in ASCII code. That means, that the relevant sensor or status is not active. \X31 corresponds to “1” and indicates an active status.
The message ends with the byte \x03 which is a stop bit (end frame) and sets the end of the transmission.
Filtr dəyişikliyi siqnalı bir əmrlə sıfırlana bilər.
Mesajlar
Aşağıdakı paraqrafda vahid əmrlər və onların müvafiq funksiyaları izah olunur. Yuxarıda qeyd edildiyi kimi, əmrləri mərkəzi idarəetmə blokundan 500 ms intervalla bütün qoşulmuş bölmələrə göndərmək lazımdır.
Rejim | Əmr |
Motor off, panel closed | \x02\x30\x31\x30\x30\x30\x30\x30\x31\x03 |
Motor in pause, panel open | \x02\x30\x31\x32\x30\x30\x30\x32\x31\x03 |
Motor off, reset filter change | \x02\x30\x31\x30\x30\x30\x31\x30\x30\x03 |
Fırlanma istiqaməti - məsələnample suqəbuledicidən çıxarmaya keçərkən – yalnız mühərrik əvvəllər söndürüldükdə dəyişdirilə bilər. Mühərrik işə salınıbsa, enerji təchizatının zədələnməsinin qarşısını almaq üçün “motor fasiləsi” əmri yerinə yetirilməlidir.
Əl rejimi: the Slave sets the direction of rotation via DIP-switches according to the predetermined configuration.
Manual mode, humidity level 1 | Əmr |
Extraction Master level 0 | \x02\x30\x31\x32\x34\x30\x30\x32\x35\x03 |
Extraction Master level 1 | \x02\x30\x31\x32\x35\x30\x30\x32\x34\x03 |
Extraction Master level 2 | \x02\x30\x31\x32\x36\x30\x30\x32\x37\x03 |
Extraction Master level 3 | \x02\x30\x31\x32\x37\x30\x30\x32\x36\x03 |
Intake Master level 0 | \x02\x30\x31\x32\x38\x30\x30\x32\x39\x03 |
Intake Master level 1 | \x02\x30\x31\x32\x39\x30\x30\x32\x38\x03 |
Intake Master level 2 | \x02\x30\x31\x32\x41\x30\x30\x32\x42\x03 |
Intake Master level 3 | \x02\x30\x31\x32\x42\x30\x30\x32\x41\x03 |
Mode for Master and Slave intake or extraction: the Slave sets the direction of rotation via DIP-switches opposite to the predetermined configuration.
Extraction / Intake, humidity level 1 | Əmr |
Extraction Master & Slave level 0 | \x02\x30\x31\x33\x34\x30\x30\x33\x35\x03 |
Extraction Master & Slave level 1 | \x02\x30\x31\x33\x35\x30\x30\x33\x34\x03 |
Extraction Master & Slave level 2 | \x02\x30\x31\x33\x36\x30\x30\x33\x37\x03 |
Extraction Master & Slave level 3 | \x02\x30\x31\x33\x37\x30\x30\x33\x36\x03 |
Intake Master & Slave level 0 | \x02\x30\x31\x33\x38\x30\x30\x33\x39\x03 |
Intake Master & Slave level 1 | \x02\x30\x31\x33\x39\x30\x30\x33\x38\x03 |
Intake Master & Slave level 2 | \x02\x30\x31\x33\x41\x30\x30\x33\x42\x03 |
Intake Master & Slave level 3 | \x02\x30\x31\x33\x42\x30\x30\x33\x41\x03 |
Avtomatik rejim: the Slave sets the direction of rotation via DIP-switches according to the predetermined configuration.
Automatic Mode, humidity level 2 | Əmr |
Extraction Master night mode | \x02\x30\x31\x36\x34\x30\x30\x36\x35\x03 |
Extraction Master day mode | \x02\x30\x31\x36\x36\x30\x30\x36\x37\x03 |
Intake Master night mode | \x02\x30\x31\x36\x38\x30\x30\x36\x39\x03 |
Intake Master day mode | \x02\x30\x31\x36\x41\x30\x30\x36\x42\x03 |
Automatic Mode, humidity level 3 | Əmr |
Extraction Master night mode | \x02\x30\x31\x41\x34\x30\x30\x41\x35\x03 |
Extraction Master day mode | \x02\x30\x31\x41\x36\x30\x30\x41\x37\x03 |
Intake Master night mode | \x02\x30\x31\x41\x38\x30\x30\x41\x39\x03 |
Intake Master day mode | \x02\x30\x31\x41\x41\x30\x30\x41\x42\x03 |
Proqramlaşdırma göstərişləri
The unit should change the direction of rotation at a specific interval, to obtain the best possible heat recovery: 60 seconds intake followed by 10 seconds pause.
Then 60 seconds extraction followed by another 10 seconds pause. This cycle guarantees an efficient air exchange along with heat recovery. At dusk the integrated twilight sensor allows to switch automatically to the night mode.
Problemlərin aradan qaldırılması
If no communication is set up, the switch of channel A and channel B (A/B lines on the RS485) can help. Moreover, check that the terminating resistor is correctly set in place, especially on the last station in the bus, in order to avoid signal reflections and communication interference