Ambientika-logo

Ambientka RS485 ፕሮግራሚንግ Sud ነፋስ

Ambientika-RS485-Programming-Sud-wind

የወልና

In installations connecting several ventilation units, serial communication occurs via an RS485 interface. The connection occurs via the differential signal lines A, B and a common earth line (GND). The units are connected to each other in a bus topology. It is mandatory to connect a terminating resistor of 120 ohms between line A and line B on the last physical unit of the bus line, to ensure the signal quality.

Ambientika-RS485-Programming-Sud-wind-1

Terminal 3: B
Terminal 4: A
Terminal 5: GND

In addition to the correct wiring of the RS485 lines, a manufacturer-specific interface module is required for integration into various automation systems: for KNX-based systems, an RS485 extension (e.g. as a KNX-TP/RS485 gateway) is available, which converts the levels and protocols between the KNX bus and the RS485 devices. In Loxone systems, the official Loxone RS485 extension is used instead, which is integrated directly into the Loxone Miniserver environment.

When selecting the appropriate interface, it is particularly important to make sure that it is not a Modbus RS485 gateway, but a transparent, serial RS485 gateway. Südwind uses proprietary protocols that do not match with the Modbus standard.

DIP መቀየሪያ ቅንብሮች

As the central control occurs via KNX or Loxone, the system completely takes over the tasks of the wall panel. The main unit is configured as a master with wall panel.

Ambientika-RS485-Programming-Sud-wind-2

በሲስተሙ ውስጥ ያሉት ሁሉም ሌሎች ክፍሎች በዲአይፒ መቀየሪያዎች እንደ ባሪያ ተቀምጠዋል። በማመልከቻው ላይ በመመስረት, ለ exampእንደ የአቅርቦት እና የጭስ ማውጫ አየር ስርዓቶች፣ የባሪያ ክፍሎቹ በተመሳሰለ ወይም በማይመሳሰል መልኩ ሊሠሩ ይችላሉ።

Ambientika-RS485-Programming-Sud-wind-3

Master mit Fernbedienung = Master with remote control
Master mit Wandpanel = Master with wall panel

Slave gegenläufig Master = Slave – Master operate asynchronously
Slave gleichläufig Master = Slave -Master operate synchronously

ፓራሜትሪዜሽን

በRS485 ቅጥያ ውስጥ የሚዋቀሩ ተከታታይ የግንኙነት መለኪያዎች፡-

  • baud rate 9600 [bit/s]
  • 8 የውሂብ ቢት
  • 1 ማቆሚያ ቢት
  • እኩልነት የለም።

መልእክቶች ከማዕከላዊ መቆጣጠሪያ ወደ ሁሉም የተገናኙ ክፍሎች በ 500 ሚሴ ርቀት ይላካሉ.
These messages consist of a sequence of bytes in hexadecimal numbering (hex-numbers). Each element, such as \x02 or \x30, represents a single byte in hexadecimal format.

Status enquiry

የሁኔታ ጥያቄው ከማዕከላዊ ቁጥጥር ይላካል እና በማስተር ክፍል ይገመገማል። ይህንን ጥያቄ በሚልኩበት ጊዜ የማዕከላዊ መቆጣጠሪያው መስመሩ መኖሩን ለማረጋገጥ ለ 3 ሰከንዶች ያህል መልዕክቶችን መላክ ያቆማል።

ሁኔታ ትዕዛዝ
Status enquiry \x02\x30\x32\x30\x32\x03

If there is no active sensor or status, the Master unit replies with a 11 bytes long message in the following hexadecimal format: \x02\x30\x30\x30\x30\x30\x30\x30\x30\x30\x30\x03.

The first byte \x02 sets the beginning of the message (start frame) and is followed by two bytes \x30\x30 representing the „status message“ (\x30 corresponds to “0” in ASCII-characters).
The following 8 bytes represent the single status registers. Each of these bytes corresponds to a specific message. Only the first four registers are used: The first register stands for the twilight sensor, the second and the third for the filter change alarm and the fourth one for the humidity alarm. A received byte \x30 corresponds to “0” in ASCII code. That means, that the relevant sensor or status is not active. \X31 corresponds to “1” and indicates an active status.

The message ends with the byte \x03 which is a stop bit (end frame) and sets the end of the transmission.
የማጣሪያ ለውጥ ማንቂያው በትእዛዝ ዳግም ሊጀመር ይችላል።

መልዕክቶች

በሚከተለው አንቀጽ ነጠላ ትዕዛዞች እና ተዛማጅ ተግባሮቻቸው ተብራርተዋል. ከላይ እንደተገለፀው ትእዛዞቹን ከማዕከላዊ መቆጣጠሪያ አሃድ ወደ ሁሉም የተገናኙ ክፍሎች በ 500 ms መካከል መላክ ያስፈልጋል.

ሁነታ ትዕዛዝ
Motor off, panel closed \x02\x30\x31\x30\x30\x30\x30\x30\x31\x03
Motor in pause, panel open \x02\x30\x31\x32\x30\x30\x30\x32\x31\x03
Motor off, reset filter change \x02\x30\x31\x30\x30\x30\x31\x30\x30\x03

የማዞሪያው አቅጣጫ - ለ example ከመቀበያ ወደ ማውጣት ሲቀይሩ - ሊለወጥ የሚችለው ከዚህ በፊት ሞተሩ ከጠፋ ብቻ ነው. ሞተሩ በርቶ ከሆነ የኃይል አቅርቦት መበላሸትን ለማስወገድ "ሞተር ማቆም" የሚለው ትዕዛዝ መፈጸም አለበት.
በእጅ ሁነታ: the Slave sets the direction of rotation via DIP-switches according to the predetermined configuration.

Manual mode, humidity level 1 ትዕዛዝ
Extraction Master level 0 \x02\x30\x31\x32\x34\x30\x30\x32\x35\x03
Extraction Master level 1 \x02\x30\x31\x32\x35\x30\x30\x32\x34\x03
Extraction Master level 2 \x02\x30\x31\x32\x36\x30\x30\x32\x37\x03
Extraction Master level 3 \x02\x30\x31\x32\x37\x30\x30\x32\x36\x03
Intake Master level 0 \x02\x30\x31\x32\x38\x30\x30\x32\x39\x03
Intake Master level 1 \x02\x30\x31\x32\x39\x30\x30\x32\x38\x03
Intake Master level 2 \x02\x30\x31\x32\x41\x30\x30\x32\x42\x03
Intake Master level 3 \x02\x30\x31\x32\x42\x30\x30\x32\x41\x03

Mode for Master and Slave intake or extraction: the Slave sets the direction of rotation via DIP-switches opposite to the predetermined configuration.

Extraction / Intake, humidity level 1 ትዕዛዝ
Extraction Master & Slave level 0 \x02\x30\x31\x33\x34\x30\x30\x33\x35\x03
Extraction Master & Slave level 1 \x02\x30\x31\x33\x35\x30\x30\x33\x34\x03
Extraction Master & Slave level 2 \x02\x30\x31\x33\x36\x30\x30\x33\x37\x03
Extraction Master & Slave level 3 \x02\x30\x31\x33\x37\x30\x30\x33\x36\x03
Intake Master & Slave level 0 \x02\x30\x31\x33\x38\x30\x30\x33\x39\x03
Intake Master & Slave level 1 \x02\x30\x31\x33\x39\x30\x30\x33\x38\x03
Intake Master & Slave level 2 \x02\x30\x31\x33\x41\x30\x30\x33\x42\x03
Intake Master & Slave level 3 \x02\x30\x31\x33\x42\x30\x30\x33\x41\x03

ራስ-ሰር ሁነታ: the Slave sets the direction of rotation via DIP-switches according to the predetermined configuration.

Automatic Mode, humidity level 2 ትዕዛዝ
Extraction Master night mode \x02\x30\x31\x36\x34\x30\x30\x36\x35\x03
Extraction Master day mode \x02\x30\x31\x36\x36\x30\x30\x36\x37\x03
Intake Master night mode \x02\x30\x31\x36\x38\x30\x30\x36\x39\x03
Intake Master day mode \x02\x30\x31\x36\x41\x30\x30\x36\x42\x03
Automatic Mode, humidity level 3 ትዕዛዝ
Extraction Master night mode \x02\x30\x31\x41\x34\x30\x30\x41\x35\x03
Extraction Master day mode \x02\x30\x31\x41\x36\x30\x30\x41\x37\x03
Intake Master night mode \x02\x30\x31\x41\x38\x30\x30\x41\x39\x03
Intake Master day mode \x02\x30\x31\x41\x41\x30\x30\x41\x42\x03

የፕሮግራም ፍንጮች
The unit should change the direction of rotation at a specific interval, to obtain the best possible heat recovery: 60 seconds intake followed by 10 seconds pause.
Then 60 seconds extraction followed by another 10 seconds pause. This cycle guarantees an efficient air exchange along with heat recovery. At dusk the integrated twilight sensor allows to switch automatically to the night mode.

መላ መፈለግ

If no communication is set up, the switch of channel A and channel B (A/B lines on the RS485) can help. Moreover, check that the terminating resistor is correctly set in place, especially on the last station in the bus, in order to avoid signal reflections and communication interference

ሰነዶች / መርጃዎች

Ambientka RS485 ፕሮግራሚንግ Sud ነፋስ [pdf] የመጫኛ መመሪያ
RS485-ambientika-ሰኔ-25፣ RS485 ፕሮግራሚንግ ሱድ ንፋስ፣ RS485፣ ፕሮግራሚንግ ሱድ ንፋስ፣ ሱድ ንፋስ

ዋቢዎች