AS-10 Switch Operator
“
Litlhaloso tsa Sehlahisoa
- Product Name: Type AS-10 Switch Operator
- Moetsi: S&C
- Mohlala: AS-10
- Application: Overhead and underground electric distribution
thepa - Available Format: PDF online at sandc.com
Litaelo tsa Tšebeliso ea Sehlahisoa
Litlhokomelo tsa Tšireletso
Ho bohlokoa ho latela mehato eohle ea tšireletso e boletsoeng ho
user manual before operating the Type AS-10 Switch Operator.
Familiarize yourself with the safety information provided on pages
3 ho isa ho 4.
Fetileview
The Type AS-10 Switch Operator is designed for specific
applications within the provided ratings. Ensure that the
application aligns with the equipment’s ratings as listed in
Specification Bulletin 769-31 and on the product’s nameplate.
Tlhahlobo
Prior to operation, conduct a thorough inspection of the Type
AS-10 Switch Operator as outlined in the user manual. Check for any
visible damage or irregularities that may affect its
tshebetso.
Tshebetso
Only qualified persons should install, operate, and maintain the
Type AS-10 Switch Operator. These individuals must be knowledgeable
in electrical equipment installation, operation, and maintenance,
along with associated hazards. Refer to the instruction sheet for
tataiso e qaqileng.
LBH
What should I do before operating the Type AS-10 Switch
Opereishene?
Prior to operation, read and understand all safety precautions
and instructions provided in the user manual. Conduct a thorough
inspection of the equipment to ensure it is in proper working
boemo.
Who can operate the Type AS-10 Switch Operator?
Only qualified persons trained in electrical equipment
installation, operation, and maintenance should operate the Type
AS-10 Switch Operator. These individuals must be competent in
handling live parts and following safety procedures.
"`
Type AS-10 Switch Operator
Tshebetso
Tafole ea likateng
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 Qualified Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Read this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Retain this Instruction Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Proper Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Boitsebiso ba Tšireletseho . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 Ho Utloisisa Melaetsa ea Tlhokomeliso ka Tšireletseho . . . . . . . . . . . . . . . 3 Ho Latela Litaelo Tsa Tšireletseho . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Litaelo le Li-Labels tsa Phetolo. . . . . . . . . . . . . . . . 3 Sebaka sa Li-Labels tsa Tšireletso. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Mehato ea Tšireletso . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
Fetileview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Checking the Switch Operator and Alduti-Rupter® Switch Positions Before Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Electrical Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Using the Manual Operating Handle . . . . . . . . . . . . . . . . . 11 Using the Selector Handle (Coupling and Decoupling) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Final Checks Before Walking Away . . . . . . . . . . . . . . . . . . 13
Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
August 18, 2025 © S&C Electric Company 19762025, all rights reserved
Leqephe la Litaelo 769-511
Selelekela
Batho ba Tšoanelehang
Bala Leqephe lena la Litaelo Boloka Leqephe lena la Litaelo Tšebeliso e Nepahetseng
TLHOKOMELO
Ke batho ba nang le tsebo feela ba nang le tsebo mabapi le ho kenya, ho sebetsa le ho hlokomela thepa ea kabo ea motlakase holim'a lefatše le ka tlas'a lefatše, hammoho le likotsi tsohle tse amanang le tsona, ba ka kenyang, ho sebetsa le ho hlokomela thepa e kenyellelitsoeng khatisong ena. Motho ea tšoanelehang ke motho ea koetlisitsoeng le ea nang le bokhoni ho: Tsebo le mekhoa e hlokahalang ho khetholla likarolo tse phelang tse pepenene ho
likarolo tse sa pheleng tsa lisebelisoa tsa motlakase Tsebo le mekhoa e hlokahalang ho fumana sebaka se nepahetseng sa ho atamela
e tsamaellanang le voltagtseo motho ea tšoanelehang a tla pepesetsoa ho tsona Tšebeliso e nepahetseng ea mekhoa e khethehileng ea ho itšireletsa, tšireletso ea botho.
lisebelisoa, lisebelisoa tse sirelelitsoeng le tse sireletsang, le lisebelisoa tse sirelelitsoeng bakeng sa ho sebetsa kapa haufi le likarolo tse matlafatsoang tsa lisebelisoa tsa motlakase.
Litaelo tsena li reretsoe feela batho ba joalo ba tšoanelehang . Ha lia rereloa ho nka sebaka sa koetliso e lekaneng le boiphihlelo mekhoeng ea polokeho ea mofuta ona oa lisebelisoa .
TSEBISO
Thoroughly and carefully read this instruction sheet and all materials included in the product’s instruction handbook before operating the Type AS-10 Switch Operator . Become familiar with the Safety Information on pages 3 through 4 and Safety Precautions on page 5 . The latest version of this publication is available online in PDF format at sandc .com/en/contact-us/product-literature/ .
This instruction sheet is a permanent part of the S&C Type AS-10 Switch Operator. Designate a location where users can easily retrieve and refer to this publication.
TLHOKOMELO
The equipment in this publication is only intended for a specific application . The application must be within the ratings furnished for the equipment . Ratings for the Type AS-10 Switch Operator are listed in the ratings table in Specification Bulletin 769-31 . The ratings are also on the nameplate affixed to the product .
2 S&C Leqephe la Taelo 769-511 .
Ho utloisisa Melaetsa ea Tlhokomeliso ka Tšireletseho
Ho Latela Litaelo Tsa Tšireletseho
Boitsebiso ba Tšireletseho
Mefuta e mengata ea melaetsa ea tlhokomeliso ea polokeho e ka hlaha hohle leqepheng lena la litaelo le lileiboleng le tags e khomaretsoeng ho sehlahisoa. Itloaetse mefuta ena ea melaetsa le bohlokoa ba mantsoe ana a matšoao:
KOTSI
“KOTSI” e khetholla likotsi tse tebileng le tse potlakileng tse ka ’nang tsa fella ka kotsi e tebileng ea botho kapa lefu haeba litaelo, ho kopanyelletsa le mehato e khothalletsoang ea ho itšireletsa, li sa lateloe .
TLHOKOMELO
“TEMOSO” e supa likotsi kapa mekhoa e sa sireletsehang e ka bakang kotsi e mpe ea botho kapa lefu haeba litaelo, ho kopanyelletsa le mehato e khothaletsoang ea ho itšireletsa, li sa lateloe .
TLHOKOMELO
“TEMOHI” e supa likotsi kapa mekhoa e sa sireletsehang e ka bakang kotsi e fokolang ea botho haeba litaelo, ho kenyeletsoa le litemoso tse khothaletsoang, li sa lateloe .
TSEBISO
"TSEBISO" e supa mekhoa kapa litlhokahalo tsa bohlokoa tse ka bakang tšenyo ea sehlahisoa kapa thepa haeba litaelo li sa lateloe .
Haeba karolo efe kapa efe ea leqephe lena la litaelo e sa hlaka 'me ho hlokahala thuso, ikopanye le S&C Sales Office e haufi kapa S&C Authorized Distributor. Linomoro tsa bona tsa mohala li thathamisitsoe ho S&C's website sandc.com, kapa letsetsa S&C Global Support and Monitoring Center ho 1-888-762-1100.
TSEBISO
Read this instruction sheet thoroughly and carefully before operating the Type AS-10 Switch Operator .
Litaelo le Li-Labels tsa Phetolo
Haeba ho hlokahala likopi tse ling tsa leqephe lena la litaelo, ikopanye le S&C Sales Office e haufinyane, S&C Authorized Distributor, S&C Headquarters, kapa S&C Electric Canada Ltd.
Ho bohlokoa hore lileibole life kapa life tse sieo, tse senyehileng, kapa tse felletseng mochining li nkeloe sebaka hang hang. Li-labels tse ling li fumaneha ka ho ikopanya le Ofisi e haufi ea S&C Sales, S&C Authorized Distributor, S&C Headquarters, kapa S&C Electric Canada Ltd.
. Leqephe la Litaelo tsa S&C 769-511 3
Lintlha tsa Tšireletseho Sebaka sa Li-Labels tsa Polokeho
A
BC
D
Hlophisa Litaba bocha bakeng sa Li-Labels tsa Polokeho
Sebaka
A
Molaetsa oa Tlhokomeliso ea Tšireletso
TLHOKOMELO
Description Use pushbuttons to open or close the switch . . .
B
TSEBISO
The S&C Instruction Sheet is a permanent part of your S&C Equipment . . . .
C
TSEBISO
Lik'hamera tse thusang li ka fetoloa ka bonngoe. Sheba lik'hamera tse thusang. . .
D
TSEBISO
Khokahano ena kapa relay e koetsoe ho thibela tšenyo nakong ea thomello.
Sena tag e tlameha ho ntšoa le ho lahloa ka mor'a hore mochini oa switch o kenngoe le ho lokisoa.
Part Number G-4892R2 G-3733R2 G-4747R2 G-3684
4 S&C Leqephe la Taelo 769-511 .
Litlhokomelo tsa Tšireletso
KOTSI
Alduti-Rupter Switches operate at high voltage . Ho hloleha ho ela hloko litemoso tse ka tlase ho tla fella ka kotsi e mpe ea botho kapa lefu .
Tse ling tsa litemoso tsena li ka fapana le mekhoa le melao ea ts'ebetso ea k'hamphani ea hau . Moo ho nang le phapang, latela mekhoa le melao ea ts'ebetso ea k'hamphani ea hau .
1 . QUALIFIED PERSONS . Access to Alduti-Rupter Switches must be restricted only to qualified persons . See the “Qualified Persons” section on page 2 .
2 . MEKHOA EA TŠEBELETSO . Kamehla latela mekhoa e sireletsehileng ea ts'ebetso le melao.
3 . SEHLOOHO SA TŠIRELETSO . Kamehla sebelisa lisebelisoa tse loketseng tsa ho itšireletsa, tse kang liatlana tsa rabara, meseme ea rabara, likatiba tse thata, likhalase tsa tšireletso le liaparo tsa flash, ho latela mekhoa le melao e sireletsehileng ea ho sebetsa .
4 . MABAKA A TŠIRELETSO . Se ke oa tlosa kapa oa pata leha e le efe ea mabitso a "KOTSI," "TEMOSO," "CAUTION," kapa "NOTICE" .
5 . OPERATING MECHANISM . Power-operated Alduti-Rupter Switches contain fast-moving parts that can severely injure fingers . Do not remove or disassemble unless directed to do so by S&C Electric Company .
6 . ENERGIZED COMPONENTS . Always consider all parts of the Alduti-Rupter Switch live until de-energized, tested, and grounded . VoltagMaemo a e a ka ba holimo joalo ka molumo oa tlhoro ea line-to-groundtage last applied to the switch . Switches energized or
installed near energized lines should be considered live until tested and grounded .
7 . GROUNDING . The Alduti-Rupter Switch must be connected to a suitable earth ground at the base of the utility pole, or to a suitable building ground for testing, before energizing the switch and at all times when energized . The vertical operating shaft above the Type AS-10 Switch Operator must also be connected to a suitable earth ground .
Lithapo tsa fatše li tlameha ho kopanngoa le sistimi e sa nke lehlakore, haeba e teng . Haeba tsamaiso e sa nke lehlakore e le sieo, mehato e nepahetseng e lokela ho nkoa ho etsa bonnete ba hore mobu oa sebaka sa heno, kapa sebaka sa mohaho, se ke ke sa khaoloa kapa sa tlosoa.
8 . SEEMO SA HO FIHLELA MOJALO-HOLO . Kamehla netefatsa boemo ba Bula/Koala ba switjha ka 'ngoe.
Li-switch le li-terminal pads li ka matlafatsoa ka mahlakoreng ka bobeli .
Li-switches le li-pads tsa terminal li ka matlafatsoa ke li-switches sebakeng sefe kapa sefe .
9 . HO BOLOKA TLHOKOMELO E NEPAHETSENG . Kamehla u boloke sebaka se nepahetseng ho tloha likarolong tse matlafalitsoeng.
. Leqephe la Litaelo tsa S&C 769-511 5
Fetileview
The Type AS-10 Switch Operator is a high-speed operator, with an operating time of 1.2 seconds maximum. It is expressly designed for power operation of outdoor distribution Alduti-Rupter Switches and outdoor distribution Alduti-Rupter Switches with Power Fuses, having reciprocating type operating mechanisms.
The high operating speed of the Type AS-10 Switch Operator provides sufficient moving-contact velocity in the Alduti-Rupter Switch interrupters to ensure full interrupting capability and long operating life. The operator’s high operating speed also provides adequate closing velocity for 25/34.5-kV and 34.5-kV three-pole side-break integer style and three-pole vertical-break integer style switches such that the side-break integer style switches have a one-time duty-cycle fault-closing rating of 15,000 amperes RMS, asymmetrical, and the vertical-break integer style have one-time duty-cycle fault-closing ratings of 20,000 or 30,000 amperes rms asymmetrical for switches rated 600 amperes kapa 1200 amperes, respectively.
For power operation of outdoor distribution Alduti-Rupter Switches and outdoor distribution Alduti-Rupter Switches with Power Fuses, having rotating type operating mechanisms, the Type AS-1A Switch Operator is offered. See S&C Instruction Sheet 769-500.
S&C Switch Operators catalog numbers 38855R4 and 38856R4 include a 12-volt dc battery and constant-burden battery charger for connection to an S&C 30-Volt-Ampere Potential Device or other 120-volt, 60-hertz source.
Switch operator catalog numbers are suffixed with one or more letters. The first letter following the catalog
number designates the motor and control voltage (except for catalog numbers 38855R4 and 38856R4):
Suffix Voltage
-A
48vc
-B
125vc
-D
115 Volts, 60 hertz
-E
230 Volts, 60 hertz
Use Table 1 on page 7 to identify the proper wiring diagram for the catalog number of switch operator being operated. Become familiar with the parts of the switch operator as shown in Figure 1 on page 8 and Figure 2 on page 9.
6 S&C Leqephe la Taelo 769-511 .
Fetileview
Table 1 . Type AS-10 Switch Operators for Reciprocating Operation of Alduti-Rupter Switches
Switch Rating, kV
Enjene le Taolo Moqtage
Lever e sebetsang
Lekala
Length, Inches (mm)
Maximum Opereishene
Nako, Metsotsoana
Minimum LockedRotor Torque at Rated Control Voltage, Inch-Lbs .
Ho potlakisa hona joale, Amperes
Operator Catalog Number
Nomoro ea Sets'oants'o sa Sets'oants'o sa Wiring
12vc
LH
4 (117)
1 .2
18500
38855R4 CDR-3127R1
48vc
LH
4 (117)
1 .2
21500
80
38852R4-A CDR-3113R1
125vc
LH
4 (117)
1 .2
21500
30
38852R4-B CDR-3113R1
115 V, 60 Hz
LH
4 (117)
1 .2
18000
46
38852R4-D CDR-3128R1
230 V, 60 Hz
LH
4 (117)
1 .2
7 .2 46
12vc
RH
4 (117)
1 .2
18000 18500
23
38852R4-E CDR-3128R1
38856R4 CDR-3127R1
48vc
RH
4 (117)
1 .2
21500
80
38853R4-A CDR-3113R1
125vc
RH
4 (117)
1 .2
21500
30
38853R4-B CDR-3113R1
115 V, 60 Hz
RH
4 (117)
1 .2
18000
46
38853R4-D CDR-3128R1
230 V, 60 Hz
RH
4 (117)
1 .2
18000
23
38853R4-E CDR-3128R1
This switch operator has output characteristics equivalent to a linear actuator having a stalled-force rating of 4000 pounds (for 12-Volt dc models), 4600 pounds (for 48-Volt dc and 125-Volt dc models), or 3800 pounds (for 115-Volt, 60-hertz and 230-Volt, 60-hertz models); a stroke length of 9 inches (23 cm); and a typical operating speed of 12 inches (30 cm) per second at midstroke .
Operating lever travels in left-hand or right-hand sector as indicated, viewed from front (door side) of switch operator . Operating lever in the Up position corresponds to the Closed position of the Alduti-Rupter Switch .
Based on minimum battery and external control wire size requirements specified in S&C Information Bulletin 769-60; operating time will be less if larger-than-minimum battery size and/or external control wire size is used .
Includes 12-Vdc battery and constant-burden battery charger for connection to an S&C 30-VA Potential Device or other 120-Volt, 60-hertz source .
CDR-3205R1 for Catalog Numbers 38852R4-D, 38852R4-E, 38853R4-D, and 38853R4-E when furnished with source-transfer control compatibility (suffix “-U1”) .
. Leqephe la Litaelo tsa S&C 769-511 7
Fetileview
Sekoahelo se sirelletsang Pushbutton
Koto ea latch
Clevis fitting (in switch Closed position)
Manual operating handle (in switch Storage position)
Clevis fitting (in switch Open position)
Mokhethi oa ho khetha
Peipi e sebetsang e otlolohileng
Letlapa la mabitso
Fetola shaft e hlahisoang ke opareitara
Switch operator operating lever
Mohatla oa monyako
Setšoantšo sa 1. Bokantle view of Type AS-10 Switch Operator .
8 S&C Leqephe la Taelo 769-511 .
Fetileview
Sekoahelo se sirelletsang Pushbutton
Bula/Koala li-pushbuttons
Motor
Motor contactor opening
Motor contactor closing
Latch ea monyako
Sets'oants'o sa litaelo
Counter ea ts'ebetso
Phetoho e thusang, 8-PST
Extra auxiliary switch, 8-PST (catalog number suffix “-W”); 12-PST version (catalog number suffix “-Z”) is similar
Position indicating lamps (sehlongoa sa nomoro ea lethathamo “-M”)
Motor circuit two-pole pullout fuseholder
Mohaho oa Duplex le bonolo-lebone lamp holder with switch (catalog number suffix “-V”)
Instructions for auxiliary switch adjustment
Conduit entrance plate
Swichi ya interlock e sebetsang ka letsoho le melamu e thibelang ka metjhini
Brakerelease solenoid
TSEBISO
These illustrations are not applicable to 12-Vdc models . 12-Vdc models use different component parts and a different internal layout . The differences include a constant-burden battery charger mounted on a swingout panel, as well as the use of a separate two-pole control-source disconnect switch in series with control-source fuses (located on the inside rear wall) instead of the motor-circuit two-pole pull-out fuseholder . The 12-Vdc models include a separate compartment beneath the enclosure to house the 12-Vdc battery .
Li-fuse tse setseng
Sets'oants'o sa sefe
Space heater fuseholder
Setšoantšo sa 2. Hare-hare view of Type AS-10 Switch Operator .
Sefuthumatsa sebaka
. Leqephe la Litaelo tsa S&C 769-511 9
Tshebetso
Checking the Switch Operator and Alduti-Rupter® Switch Positions Before Operation
Do not assume the switch operator position necessarily indicates the Open or Closed position of the Alduti-Rupter Switch. Upon completion of an opening or closing operation (electrical or manual), make sure the following conditions exist:
The switch operator position indicator, Figure 5 on page 13, signals “OPEN” or “CLOSED” to indicate that the switch operator has moved through a complete operation. Also note the POSITION INDICATING lamps, Figure 2 on page 9, if furnished.
The operating lever, at the rear of the switch operator, see Figure 1 on page 8, is in the Up position for an Alduti-Rupter Switch Closed position. Conversely, the operating lever is in the Down position for an Alduti-Rupter Switch Open position.
The blades on all three poles of the Alduti-Rupter Switch are fully open or fully closed (by visual verification).
Joale, tag and padlock the switch operator in accordance with standard system operating procedures. In all
cases, make sure the switch operator is padlocked before “walking away.”
Ts'ebetso ea Motlakase
Complete the following steps to open or close the interrupter switch electronically:
STEP 1 . Unlock and lift the external pushbutton protective cover.
STEP 2 . Press the appropriate pushbutton. See Figure 2 on page 9.
Alternatively, the switch operator may be activated by operating associated, remotely located control switches. (No instructions are included for activating the switch operator by means of remotely located control switches because control schemes vary with different installations. With any given installation, however, it may be possible and desirable to effect such operation. Instructions presented in this document cover operation at the switch operator only.)
For switch operators with an optional remote-control blocking switch (suffix “-Y”), opening the pushbutton protective cover prevents remote operation of the switch operator . OPEN/CLOSE pushbuttons are not included on switch operators specified with catalog number suffix “-J .”
10 S&C Leqephe la Taelo 769-511 .
Tshebetso
Ho Sebelisa Bukana ea Ts'ebetso
The manual operating handle is used during switch operator adjustment. Become familiar with the operation of the manual operating handle, as described on the switch operator nameplate on the right-hand side of the enclosure.
TLHOKOMELO
DO NOT manually open or close the switch operator while the Alduti-Rupter Switch is energized .
Operating the switch under reduced operating speed can cause excessive arcing, resulting in shortened interrupter life, damage to the interrupters, or personal injury .
Haeba switch opareitara taolo voltage is not available and emergency manual opening is absolutely necessary, crank the manual operating handle rapidly throughout its full travel . Do not stop or hesitate part way . Never close the switch manually .
MOHATO OA 1 . Hula konopo ea latch khubung ea letsoho la ho sebetsa 'me u suthisetse letsoho pele hanyane ho tloha sebakeng sa eona sa polokelo.
MOHATO 2 .
Release the latch knob while continuing to pivot the handle forward to lock it into the cranking position. See Figure 3. (As the handle is pivoted forward, the motor brake is mechanically released, both leads of the control source are automatically disconnected, and–except for 12-Vdc models–both the “opening” and “closing” motor contactors are mechanically blocked in the Open position.)
MOHATO 3 .
Crank the handle to the Open position.
If desired, during manual operation, the switch operator may also be disconnected from the control source by removing the motor-circuit two-pole pull-out fuse holder, located on the right-hand inside wall of the enclosure.
MOHATO 4 .
To return the manual operating handle to its Storage position: Pull the latch knob and pivot the handle approximately 90 degrees. The handle will then be disengaged from the switch operator and may be rotated freely in either direction to its Storage position.
Complete the handle storage by pivoting the operating handle backward approximately
Koto ea latch
Mokhoa oa ho sebetsa oa letsoho
Taba ea ho notlela
Sekhetho (se maemong a Kopanetsoeng)
Figure 3 . Using the manual operating handle .
. Leqephe la Litaelo tsa S&C 769-511 11
Tshebetso
90 degrees until it latches in the Storage position. Always padlock the handle in its Storage position.
Note: The manual operating handle may be disengaged from the switch operator mechanism at any position of the handle.
Ho sebelisa Sekhetho sa Sekhetho (Ho kopanya le ho kopanya)
The selector handle will be used during switch operator adjustment. The integral external selector handle, for operation of the built-in internal decoupling mechanism, is located on the right-hand side of the switch operator enclosure. Become familiar with the operation of the selector handle, as described on the switch operator nameplate on the right-hand side of the enclosure.
Ho hlakola opareitara ea switjha ho switch:
MOHATO 1 .
Tsamaisetsa setshwano sa sekhetho se otlolohile mme o se fetole butle ho ya ka di-degrees tse 50 ho ya sebakeng sa Decoupled. Sheba Setšoantšo sa 4. Sena se arola mochine oa ho fetola mochine ho tloha ho shaft ea tlhahiso ea opereishene.
MOHATO 2 .
Lower the selector handle to engage the locking tab. When decoupled, the switch operator may be operated either manually or electrically without operating the Alduti-Rupter Switch.
When the selector handle is in the Decoupled position, the output shaft is prevented from moving by a mechanical locking device located within the switch operator enclosure.
During the intermediate segment of the selector handle travel, which includes the position at which actual disengagement (or engagement) of the internal decoupling mechanism occurs, the motor circuit source leads are momentarily disconnected and (except for 12-Vdc models) both the “opening” and “closing” motor contactors are mechanically blocked in the Open position.
Visual inspection, through the observation window will verify whether the internal decoupling mechanism is in the Coupled or Decoupled position.
STEP 3 . Padlock the selector handle in either position.
Selector handle (being turned to Decoupled position)
Coupled 50
Hlakotsoe
Li-tab tsa ho notlela
Figure 4 . Using the selector handle .
12 S&C Leqephe la Taelo 769-511 .
Tshebetso
Ho kopanya opareitara ho switjha:
MOHATO 1 .
Manually operate the switch operator to bring it to the same Open or Closed position as the Alduti-Rupter Switch. The SWITCH OPERATOR POSITION indicator, seen through the observation window, will show when the approximate Open or Closed position has been attained. See Figure 5.
MOHATO 2 .
Turn the manual operating handle slowly until the position-indexing drums are numerically aligned to move the switch operator to the exact position for coupling.
STEP 3 . Swing the selector handle upright and rotate it counterclockwise to the Coupled position.
STEP 4 . Lower the handle to engage the locking tab. The selector handle is now in the Coupled position.
STEP 5 . Padlock the selector handle in either position.
Final Checks Before Walking Away
To ensure the switch operator is ready for normal power operation of the Alduti-Rupter Switch by remote automatic or supervisory control, make sure the following conditions exist:
The selector handle is in the Coupled position.
The manual operating handle is in its Storage position.
The two-pole pull-out fuse holders for the motor circuit and space-heater circuit are inserted.
The pushbutton protective cover is closed.
The switch operator is tagged and padlocked in accordance with standard system operating procedures.
Internal decoupling mechanism (in Decoupled position)
Position indexing drums
Fetola matšoao a boemo ba opareitara
Internal decoupling mechanism (in Coupled position)
Setšoantšo sa 5 . Views of switch operator through observation window .
. Leqephe la Litaelo tsa S&C 769-511 13
Tlhahlobo
To ensure continued proper performance of the Type AS-10 Switch Operator, it should be inspected every 5 years. De-energize the associated Alduti-Rupter Switch and perform the following switch operator inspection procedures:
STEP 1 . Check for evidence of water ingress, damage, and excessive corrosion or wear.
STEP 2 . Check ease of operation during slow, manual cranking using the switch operator manual operating handle.
STEP 3 . Check electrical operation, coupled and decoupled.
MOHATO 4 .
Check for loose wiring inside enclosure and proper functioning of POSITION INDICATING lamps, khaontara ea ts'ebetso, boiketlo lamp, joalo-joalo.
MOHATO 5 .
Check operation of brake and readjust if necessary. The procedure for doing this is as follows. All detail views can be found in Figure 6 on page 16.
(a) Place the selector handle in the Decoupled position.
(b) Remove the two-pole pull-out fuse holders for the motor circuit and space-heater circuit.
(c) Disconnect the linkage rod by removing the ¼20×1¼-inch hex-head screw, lockwasher, flat washer, and spacer-bushing from the end of the brake lever, as shown in Detail A. Be careful not to lose these parts.
(d) Raise the brake lever and measure the vertical free play, as shown in Detail B. This dimension should be 5/8 inch (16 mm) to ¾ inch (19 mm). Should the measurement be outside this range, brake-wear compensation is required; proceed to Step 5 (e). If the measurement is within this range, reattach the linkage rod and
tighten the ¼20×1¼-inch hex-head screw securely; proceed to Step 5 (j).
(e) Remove the four 5/1618×1¼-inch screws used to attach the motor, withdraw the motor, and carefully rest its shaft on the floor of the enclosure. Be careful not to lose the square key or tubular spacer (if furnished), which may remain on the motor shaft.
Note: 115-Volt ac and 230-Volt ac motors utilize a ¼-inch20 socket-head set screw on the side of the brake disc hub, as shown in Detail C. Loosen this set screw approximately one-half turn, using a 1/8-inch Allen wrench, before removing the motor.
(f) Using a 3/32-inch Allen wrench, loosen the pad assembly socket-head set screw on the side of the caliper assembly approximately one-half turn. See Detail A.
(g) Then, using a 5/16-inch Allen wrench, rotate the pad assembly clockwise until the free play at the end of the brake lever is 5/8 inch (16 mm) to ¾ inch (19 mm) as shown in Detail B. Now tighten the 3/32-inch pad assembly socket-head set screw.
(h) Insert the spacer-bushing through the angle bracket and brake lever, and reattach the linkage rod using the ¼20 × ¼-inch hex-head screw, lockwasher, and flat washer. Tighten the screw securely.
(i) Insert the square key in the keyway, as shown in Detail A. Slip the tubular spacer (if furnished) over the motor shaft and reinstall the motor. Position the motor such that the two weep holes on the side of the housing face downward. Replace the four 5/1618×1¼-inch screws used to attach the motor and tighten them securely.
On 115-Volt ac and 230-Volt ac motors: Retighten the ¼-inch20 sockethead set screw on the side of the brake disc hub.
14 S&C Leqephe la Taelo 769-511 .
(j) Pull the latch knob on the hub of the manual operating handle and slowly pivot the handle forward from its storage position toward its cranking position until the brake disc can be rotated by hand. Be careful not to get grease on the brake disc.
Now measure the distance that the end of the brake lever travels from the point of initial brake release to the bottom of its stroke (which occurs when the handle locks into the cranking position). This dimension should be 1/8 inch (3 mm) to ¼ inch (6 mm). See Detail D. Should the measurement be outside this range, refer to the nearest S&C Sales Office.
Since the Type AS-10 Switch Operator may be conveniently decoupled from the Alduti-Rupter Switch, elective exercising of the operator may be performed at any time without requiring an outage or switching to an alternate source.
Tlhahlobo
. Leqephe la Litaelo tsa S&C 769-511 15
Tlhahlobo
TSEBISO
Do not loosen this ¼-inch20 screw .
Motor shaft square key
Brake disc
-inch socket-head recess for adjusting pad assembly
Kopano ea pad
Pad assembly socket-head set screw ( -inch Allen wrench required)
Brake lever
Molamu oa khokahano
Borakete ea Angle
¼20 1¼-in . hex-head screw
Caliper assembly
Spacer-bushing
Hub
Brake disc ¼-inch20 socket-head set screw (-inch Allen wrench required) DETAIL C Location of motor shaft set screw (115- and 230-Vac operator only)
DETAIL A Brake assembly
Motor
18 1¼-inch screws Operating linkage disconnected to brake lever
¾-inch (16-19 mm) vertical free play
DETAIL B Measuring brake
lever free play
Brake lever
Operating linkage connected to brake lever
Point of initial manual brake release
DETAIL D Measuring brake
lever stroke
× 1¼-inch (3 x 32-mm) travel
Brake lever at bottom of its stroke (manual operating handle in Cranking position)
Figure 6 . Brake inspection procedure . 16 S&C Instruction Sheet 769-511 .
Litokomane / Lisebelisoa
![]() |
S and C AS-10 Switch Operator [pdf] Buka ea Taelo AS-10 Switch Operator, AS-10, Switch Operator, Operator |