Danfoss-LOGO

Sensori i hyrjes MCB 130 VLT Danfoss 1272B114

Danfoss-130B1272-Input-MCB-114-VLT-Sensor-PRODUCT

INFORMACION PËR PRODUKTIN

The VLT® Sensor Input MCB 114 can be used in the following cases:

  • Hyrja e sensorit për transmetuesit e temperaturës PT100 dhe PT1000 për monitorimin e temperaturave të kushinetave.
  • As general extension of analog inputs with 1 extra input (0/4–20 mA) for multi-zone control or differential pressure measurements.
  • Support extended PID controllers with I/Os for setpoint, transmitter/sensor inputs.
Seria FC Versioni i softuerit
VLT® HVAC Drive FC 102 1.00 dhe më vonë
VLT® AQUA Drive FC 202 1.41 dhe më vonë
VLT® Automation Drive FC 301/FC 302 6.02 dhe më vonë

Tabela 1.1 Software Versions Supporting the VLT® Sensor Input MCB 114

Artikujt e furnizuar

Artikujt e furnizuar varen nga numri i kodit të porositur dhe lloji i mbylljes së konvertuesit të frekuencës.

Numri i kodit Artikujt e furnizuar
130B1172 Uncoated version
130B1272 Versioni i veshur

Danfoss-130B1272-Input-MCB-114-VLT-Sensor-fig (1)

Informacioni i Sigurisë

PARALAJMËRIM

KOHA E SHKARKIMIT

Konvertuesi i frekuencës përmban kondensatorë me lidhje DC, të cilët mund të mbeten të ngarkuar edhe kur konverteri i frekuencës nuk është i ndezur. Vëllimi i lartëtage mund të jetë e pranishme edhe kur dritat treguese LED paralajmëruese janë o. Dështimi për të pritur kohën e specifikuar pasi të jetë hequr rryma elektrike përpara se të kryeni punë servisi ose riparimi mund të rezultojë në vdekje ose lëndim serioz.

  • Ndaloni motorin.
  • Shkëputni rrjetin elektrik AC dhe furnizimin me rrymë me lidhje DC në distancë, duke përfshirë bateritë rezervë, UPS dhe lidhjet me lidhje DC me konvertuesit e tjerë të frekuencës.
  • Shkëputni ose kyçni motorin PM.
  • Wait for the capacitors to discharge fully. The minimum duration of waiting time is specified in Tables 1.2 to Table 1.4.
  • Përpara se të kryeni ndonjë punë shërbimi ose riparimi, përdorni një vëllim të përshtatshëmtage pajisje matëse për t'u siguruar që kondensatorët janë shkarkuar plotësisht.

specifikim

Vëlltage [V] Koha minimale e pritjes (minuta)
4 7 15 20 30 40
200–240 1.1-3.7 kW

(1.50–5 kf)

5.5-45 kW

(7.5–60 kf)

380–480 1.1-7.5 kW

(1.50–10 kf)

11-90 kW

(15–121 kf)

315-1000 kW

(450–1350 kf)

400 90-315 kW

(121–450 kf)

500 110-355 kW

(150–500 kf)

525 75-315 kW

(100–450 kf)

525–600 1.1-7.5 kW

(1.50–10 kf)

11-90 kW

(15–121 kf)

690 90-315 kW

(100-350 kf)

525–690 1.1-7.5 kW

(1.50–10 kf)

11-90 kW

(15–121 kf)

400-1400 kW

(500–1550 kf)

450-1400 kW

(600–1550 kf)

Tabela 1.2 Discharge Time, VLT® HVAC Drive FC 102

Vëlltage [V] Koha minimale e pritjes (minuta)
4 7 15 20 30 40
200–240 0.25-3.7 kW

(0.34–5 kf)

5.5-45 kW

(7.5–60 kf)

380–480 0.37-7.5 kW

(0.5–10 kf)

11-90 kW

(15–121 kf)

110-315 kW

(150–450 kf)

315-1000 kW

(450–1350 kf)

355-560 kW

(500–750 kf)

525–600 0.75-7.5 kW

(1–10 kf)

11-90 kW

(15–121 kf)

400-1400 kW

(400–1550 kf)

525–690 1.1-7.5 kW

(1.5–10 kf)

11-90 kW

(10–100 kf)

75-400 kW

(75–400 kf)

450-800 kW

(450–950 kf)

Tabela 1.3 Discharge Time, VLT® AQUA Drive FC 202

Vëlltage [V] Koha minimale e pritjes (minuta)
  4 7 15 20 30 40
200–240 0.25-3.7 kW

(0.34–5 kf)

5.5-37 kW

(7.5–50 kf)

     
380–500 0.25-7.5 kW

(0.34–10 kf)

11-75 kW

(15–100 kf)

90-200 kW

(150–350 kf)

250-500 kW

(450–750 kf)

250-800 kW

(450–1350 kf)

315–500

(500–750 kf)

400 90-315 kW

(125–450 kf)

500 110-355 kW

(150–450 kf)

525 55-315 kW

(75–400 kf)

525–600 0.75-7.5 kW

(1–10 kf)

11-75 kW

(15–100 kf)

525–690 1.5-7.5 kW

(2–10 kf)

11-75 kW

(15–100 kf)

37-315 kW

(50–450 kf)

355-1200 kW

(450–1550 kf)

355-2000 kW

(450–2050 kf)

355-710 kW

(400–950 kf)

690 55-315 kW

(75–400 kf)

  • Tabela 1.4 Koha e shkarkimit, VLT® Automation Drive FC 301/FC 302

Montimi

Procedura e instalimit varet nga madhësia e mbylljes së konvertuesit të frekuencës.

Enclosure sizes A2, A3, and B3

  1. Remove the LCP (local control panel), the terminal cover, and the LCP frame from the frequency converter.
  2. Vendoseni opsionin në folenë B.
  3. Connect the control cables and relieve the cable. See Illustration 1.4 and Illustration 1.5 for details about wiring.
  4. Remove the knockout in the extended LCP frame (supplied).
  5. Fit the extended LCP frame and terminal cover on the frequency converter.
  6. Vendosni LCP ose mbulesën e verbër në kornizën e zgjeruar LCP.
  7. Lidhni energjinë me konvertuesin e frekuencës.
  8. Set up the input/output functions in the corresponding parameters.

INSTALIMI

Ilustrimi 1.2 Installation in Enclosure Sizes A2, A3, and B3

Danfoss-130B1272-Input-MCB-114-VLT-Sensor-fig (2)

1 LPK
2 Mbulesa e terminalit
3 Vendi B
4 Opsioni
5 Korniza LCP

Enclosure sizes A5, B1, B2, B4, C1, C2, C3, C4, D, E, and F

  1. Remove the LCP (local control panel) and the LCP cradle.
  2. Fit the option card into slot B.
  3. Connect the control cables and relieve the cable. See Illustration 1.4 and Illustration 1.5 for details about wiring.
  4. Fit the cradle on the frequency converter.
  5. Fit the LCP in the cradle.

Danfoss-130B1272-Input-MCB-114-VLT-Sensor-fig (3)

1 LPK
2 Djep LCP
3 Opsioni
4 Vendi B

Ilustrimi 1.3 Instalimi në përmasa të tjera mbyllëse (P.shample)

Izolimi galvanik

Izoloni në mënyrë galvanike sensorët nga voltage nivelit. Kërkesat e sigurisë: IEC 61800-5-1 dhe UL 508C.

Instalime elektrike

Lidhja elektrike e hyrjes së sensorit VLT® MCB 114.Danfoss-130B1272-Input-MCB-114-VLT-Sensor-fig (4) Danfoss-130B1272-Input-MCB-114-VLT-Sensor-fig (5)

Terminali Emri Funksioni
1 VDD 24 V DC to supply 0/4–20 mA sensor
2 Unë në 0/4–20 mA input
3 GND Analog input GND
4, 7, 10 Temp 1, 2, 3 Hyrja e temperaturës
5, 8, 11 Wire 1, 2, 3 3rd wire input if 3 wire sensors are used
6, 9, 12 GND Temperature input GND

rrjetë

Gjatësia maksimale e kabllit të sinjalit është 500 m (1640 ft).

Specifikimet elektrike dhe mekanike

Opsioni është në gjendje të furnizojë sensorin analog me 24 V DC (terminali 1).

Numri i hyrjeve analoge 1
Formati 0–20 mA or 4–20 mA
Telat 2 tela
Impedanca e hyrjes <200 Ω
Sample norma 1 kHz
3rd order filter 100 Hz at 3 dB

Tabela 1.6 Analog Input

Number of analog inputs supporting

PT100/1000

3
Lloji i sinjalit PT100/PT1000
Lidhja PT100 2 or 3 wire

PT1000 2 or 3 wire

Frequency PT100 and PT1000 input 1 Hz for each channel
Rezolucioni 10 bit
Gama e temperaturës -50 deri +204 °C

-58 deri +399 ° F

Tabela 1.7 Hyrja e sensorit të temperaturës

Konfigurimi

  • The 3 sensor inputs support 2 and 3 wire sensors and an auto detection of sensor type, PT100 or PT1000 takes places at power-up.
  • The analog input is capable of handling 0/4–20 mA.

For programming of the parameters, see the product-specific programming guide, parameter group 35-** Sensor Input Option and parameter group 18-3* Analog Readouts with data readouts in parameter 18-36 Analog Input X48/2 [mA] to
parameter 18-39 Temp. Input X48/10.

MË SHUMË INFORMACION

Danfoss nuk mund të pranojë asnjë përgjegjësi për gabime të mundshme në katalogë, broshura dhe materiale të tjera të shtypura. Danfoss rezervon të drejtën të ndryshojë produktet e saj pa paralajmërim. Kjo vlen edhe për produktet tashmë të porositura me kusht që këto ndryshime të mund të bëhen pa qenë të nevojshme ndryshime të mëvonshme në specifikimet e dakorduara tashmë. Të gjitha markat tregtare në këtë material janë pronë e kompanive përkatëse. Danfoss dhe logotipi i Danfoss janë marka tregtare të Danfoss A/S. Të gjitha të drejtat e rezervuara.

Pyetjet e shpeshta

  • Pyetje: Çfarë duhet të bëj nëse dritat treguese LED paralajmëruese janë të fikur, por mund të ketë ende volum të lartëtage pranishme?
    •  A: Always wait for the specified minimum waiting time after removing power before performing any service or repair work. Use an appropriate voltage measuring device to ensure capacitors are fully discharged.