Ndërfaqja e përdoruesit në distancë e kontrolluesit të njësisë 1005-7 MicroTech
“
Informacioni i produktit
Specifikimet
- Product Name: Remote User Interface for MicroTech Unit
Kontrollorët - Compatible with: MicroTech Applied Rooftops, Air and
Water-Cooled Chiller unit controllers - Supports: Rebel Packaged Rooftop, Self-Contained Systems, and
various other models - Designed for: Display, system configuration, set-up, and
management of unit controllers
Udhëzimet e përdorimit të produktit
Instalimi
- Refer to the installation manual specific to your unit
model. - Sigurohuni që furnizimi me energji elektrike të jetë shkëputur përpara instalimit.
- Mount the remote user interface in a convenient location for
akses.
Operacioni
- Power on the remote user interface by connecting it to a power
burimi. - Use the interface to display system information, configure
settings, and manage unit controllers. - Follow on-screen prompts for diagnostics and control
rregullimet.
Mirëmbajtja
- Regularly clean the interface display using a soft cloth.
- Avoid exposing the interface to liquids or extreme
temperaturat. - For technical support, refer to the contact information
të parashikuara në manual.
FAQ
Q: How many units can the remote user interface handle?
A: The remote user interface can handle up to eight units per
ndërfaqe.
Q: What should I do if I encounter a “DANGER” message on the
ndërfaqe?
A: A “DANGER” message indicates a hazardous situation that could
result in death or serious injury. Take immediate action to address
the situation and ensure safety.
Q: How do I access unit diagnostics using the remote user
ndërfaqe?
A: To access unit diagnostics, navigate through the menu options
on the interface. Look for diagnostic tools or status indicators to
monitor the unit’s performance.
“`
Manuali i instalimit dhe funksionimit
IM 1005-7
MicroTech® Unit Controller Remote User Interface
Grupi: Kontrollet Numri i Pjesës: IM 1005 Data: Korrik 2025
Packaged Rooftops, Applied Rooftop, Self-Contained, and Air Handler Systems
Air and Water-Cooled Chillers
Tabela e Përmbajtjes
Tabela e Përmbajtjes
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Product Information. . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Hazardous Information Messages . . . . . . . . . . . . . . . 3 Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . 3 Component Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Environmental Conditions . . . . . . . . . . . . . . . . . . . . 4
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Pre-Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Location Considerations . . . . . . . . . . . . . . . . . . . . . 5 Mounting Surfaces . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Parts. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Wiring the Remote User Interface. . . . . . . . . . . . . . . . 7 Daisy-Chain Connection . . . . . . . . . . . . . . . . . . . . . 7 Direct Connection . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tabela e Përmbajtjes
Operator’s Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Using the Remote User Interface . . . . . . . . . . . . . . . . 9 Hardware Features . . . . . . . . . . . . . . . . . . . . . . . . . 9 Keypad/Display Features. . . . . . . . . . . . . . . . . . . . . 9 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Passwords . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 Customize User Preferences . . . . . . . . . . . . . . . . . 10 Synchronize with MicroTech Unit Controller . . . . . 11 Firmware Upgrade Procedure . . . . . . . . . . . . . . . . 12
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Frequently Asked Questions . . . . . . . . . . . . . . . . . . 13 Helpful Tips . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Historia e Rishikimit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
©2025 Daikin Applied, Minneapolis, MN. All rights reserved throughout the world.This document contains the most current product information as of this printing. Daikin Applied Americas Inc. has the right to change the information, design, and construction of the product represented within the document without prior notice. For the most up-to-date product information, please go to www.DaikinApplied.com. TM® MicroTech, Rebel, Maverick II, Roofpak, Pathfinder, Trailblazer, Magnitude, Navigator, and Daikin Applied are trademarks or registered trademarks of Daikin Applied Americas Inc. The following are trademarks or registered trademarks of their respective companies: BACnet from American Society of Heating, Refrigeration and Air-Conditioning Engineers, Inc., and Windows from Microsoft Corporation
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
2
www.DaikinApplied.com
Hyrje
Hyrje
Informacione të Përgjithshme
This manual describes how to install and operate the remote user interface for use with MicroTech Applied Rooftops and also Air and Water-Cooled chiller unit controllers from Daikin Applied.
For technical support on rooftop or self-contained unit controllers, contact the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied. com).
For chiller unit controller support, contact the Daikin Applied Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).
For technical support on PreciseLine unit controllers, contact the Daikin Applied Air Technical Response Center at 800-4323928 (ATSTechSupport@daikinapplied.com)
Informacioni i produktit
The remote user interface is designed for display, system configuration, set-up, and management of MicroTech unit controllers:
MicroTech Unit Controller Models
Rebel® Packaged Rooftop
Të gjitha modelet
Rebel Packaged Rooftop
Të gjitha modelet
Self-Contained Systems
Models SWT and SWP
Maverick® II Commercial Rooftop Model MPS
Pathfinder® Air-Cooled Screw Chiller
Models AWS and AWV
Trailblazer® Air-Cooled Scroll Compressor Chiller
Models AGZ-D and AGZ-E
Magnitude® Water-Cooled Chiller Model WME, B Vintage
Navigator® Water-Cooled Screw Chiller
Model WWV/TWV
Trailblazer® Air-Cooled Chiller
Model AMZ
PreciseLine® Air Handler
Të gjitha modelet
In addition to the unit-mounted controller keypad/display, MicroTech unit control systems can be equipped with a remote user interface that handles up to eight units per interface. The remote user interface provides access to unit diagnostics and control adjustments similar to the unit-mounted controller.
Hyrje
Mesazhet e rrezikshme të informacionit
RREZIK Rreziku tregon një situatë të rrezikshme, e cila do të rezultojë në vdekje ose lëndime serioze nëse nuk shmanget.
PARALAJMËRIM Paralajmërimi tregon situata potencialisht të rrezikshme, të cilat mund të rezultojnë në dëmtime të pronës, lëndime personale ose vdekje nëse nuk shmangen.
KUJDES Kujdesi tregon situata potencialisht të rrezikshme, të cilat mund të rezultojnë në lëndime të lehta ose dëmtime të pajisjeve nëse nuk shmangen.
NJOFITIM Njoftimi tregon praktikat që nuk lidhen me lëndime fizike.
Dokumentet e referencës
Number IOM 1202 IOM 1206 IOM 1242
IOMM 1033
IOM 1264 IOM 1243 OM 1382 OM 1373 OM 1357
Company Daikin Applied Daikin Applied Daikin Applied
Aplikuar Daikin
Daikin Applied Daikin Applied Daikin Applied Daikin Applied Daikin Applied
Titulli
Pathfinder Chiller Model AWS Installation, Operation, and Maintenance Manual
Trailblazer Chiller Model AGZ Installation,Operation and Maintenance Manual
Pathfinder Model AWV Chiller Installation, Operation, and Maintenance Manual
Magnitude Model WME, B vintage Magnetic Bearing Centrifugal Chiller Installation, Operation, and Maintenance Manual
Navigator Model WWV/TWV Water-cooled Chiller Installation, Operation, and Maintenance Manual
Trailblazer Chiller Model AMZ
Rebel Commercial Packaged Rooftop Systems, Operation and Maintenance Manual
Rebel Applied Rooftop Systems, Operation and Maintenance Manual
PreciseLine Air Handler, Operation and Maintenance Manual
Burimi
www. DaikinApplied.
com
Veçoritë
· Push-and-roll navigation wheel with an 8-line by 30-character display format
· Operating conditions, system alarms, control parameters and schedules are monitored
· RS-485 or KNX interface for local or remote installation
· Power from controller, no additional power supply necessary
· Supports panel mounting and wall mounting
www.DaikinApplied.com
3
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
Hyrje
Të dhënat e komponentit
Gjeneral
Figure 1 shows the details of the remote user interface hardware design.
The overall physical layout includes:
· 5.7 × 3.8 × 1 in (144 × 96 × 26 mm) size · 9.1 oz (256.7 g) weight, excluding packaging · Plastic housing
Fuqia
· Supplied by the MicroTech unit controller for direct connection
· Separate 24V DAC power supply, optional for daisy chain connections, Max 85 mA
NOTE: Contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) if a separate power supply is desired.
Figura 1: Dimensionet fizike
Ekrani
· LCD type FSTN · Resolution dot-matrix 96 x 208 · Backlight blue or white, user selectable
Kushtet e Mjedisit
Operation Temperature Restriction LCD Restriction Process-Bus Humidity Air pressure
EC 721-3-3 -40…158°F (-40…+70°C) -4…140°F (-20…+60°C) -13…158°F (-25….+70°C) < 90% RH (no condensation) Min. 10.2 psi (700 hPa), corresponding to max. 9843 ft (3000 m) above sea level
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
4
www.DaikinApplied.com
Instalimi
Instalimi
Para-instalimi
Please be aware of the following before mounting and installing the remote user interface.
Konsideratat e vendndodhjes
Placement of the remote user interface is necessary to ensure proper operation. When selecting a location, avoid the following:
· Locations that are outside the operating temperature and humidity range (see Environmental Conditions.)
· Mounting on rooftop without a careful site evaluation and confirmation
· Walls that are subject to high vibration
· Areas with high humidity exterior walls and other walls that have a temperature differential between the two sides
· Areas that are close to heat sources such as sunlight, appliances, concealed pipes, chimneys, or other heatgenerating equipment
Sipërfaqet e montimit
For surface installation, mount the remote user interface to a flat surface such as sheet rock or plaster, control panel, or an electrical junction box.
· If mounting onto sheet rock or plaster, use anchors, if necessary
· For mounting in the unit controller panel, electrical junction box, or other metal enclosure, use the supplied magnets.
Pjesë
Përshkrimi
Numri i pjesës
MicroTech Remote User Interface
1934080031,2
Connectors (using CE+ CE- connection option) 193410302
1. Note that part number 193408001 is no longer available.
2. For daisy-chaining unit controllers together, a 2-pin connector (PN 193410302), is required for each unit controller. The 2-pin connector is not required for direct-connecting unit controllers.
Për të gjetur zyrën tuaj lokale të pjesëve, vizitoni www.DaikinApplied.com ose telefononi 800-37PARTS (800-377-2787).
Montimi dhe lidhja
The following section describes how to mount the remote user interface and connect it to one or more MicroTech unit controllers.
CAUTION Electrostatic discharge hazard. Can cause equipment damage.
Kjo pajisje përmban komponentë elektronikë të ndjeshëm që mund të dëmtohen nga shkarkimi elektrostatik nga duart tuaja. Përpara se të trajtoni një modul komunikimi, duhet të prekni një objekt të tokëzuar, siç është mbyllja metalike, në mënyrë që të shkarkojë potencialin elektrostatik nga trupi juaj.
WARNING Electric shock hazard. Can cause personal injury or equipment damage.
Kjo pajisje duhet të jetë e tokëzuar siç duhet. Vetëm personeli me njohuri në funksionimin e pajisjeve që kontrollohen duhet të kryejë lidhjet dhe shërbimin me kontrolluesin e njësisë.
1. Remove plastic cover (Figure 2).
2. Mount the remote user interface. The remote user interface can be either panel mounted or wall mounted as shown in Figure 3. See Figure 4 and Figure 5 for terminal connections for each of the mounting locations.
www.DaikinApplied.com
5
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
Figure 2: Removing the Cover of remote user interface Figure 3: Wall and Surface Wiring Connections
Instalimi
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
6
www.DaikinApplied.com
Instalimi
Wiring the Remote User Interface
Wiring the remote user interface to the MicroTech unit controller can be done in two different ways:
1. Daisy-chain connection to as many as eight units.
2. Direct connection to a single unit controller.
Connection and wiring instructions in each case are described in the following section. See Table 1 for wire sizing and distance limitations.
NOTE: Power is supplied by the MicroTech unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at (800) 4321342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com).
Lidhja Daisy-Zinxhiri
Establish a physical connection from the remote user interface to the MicroTech unit controller.
1. Connect a twisted pair wire to the CE + and CE pins of each unit controller and remote user interface (see Figure 4 and Figure 5).
2. Daisy-chain up to eight MicroTech unit controllers to a single remote user interface. See Figure 5 for wiring details. Note the wire size and distance limitations provided in Table 1.
3. Cycle power to each MicroTech unit controller once the wiring of the remote user interface is complete.
NOTE: Downloading and communication using the daisychain connection may be slower than for the RJ45 (Ethernet) direct connection.
Table 1: Wiring Specifications Bus connection Terminal Max. length Cable type Wiring distance up to 500 ft Wiring distance between 500 – 1000 ft
Wiring distance over 1000 ft
CE+, CE-, not interchangeable 2-screw connector 1000 ft (305 m)
Twisted pair, shielded cable 16 AWG Twisted pair, shielded cable 14 AWG Not currently supported. Contact the appropriate Daikin Applied Technical Response Center for assistance.
Figure 4: Interface Details for Daisy-Chain Connection
www.DaikinApplied.com
7
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
Figure 5: Daisy-Chain Connection Wiring Details
Instalimi
Lidhja direkte
The remote user interface can be wired directly to a single MicroTech unit controller over a standard RJ45 (Ethernet) connection.
Procedura
1. Locate the connector location as shown in Figure 6
2. Follow Figure 6 for connection details. Note the distance limitations provided.
3. Cycle power to the unit(s) once the wiring of the remote user interface is complete.
NOTE: Power is supplied by the unit controller. If a separate 24V power supply is desired, please contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied. com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied. com).
Figure 6: Interface Details for RJ45 Connector
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
8
www.DaikinApplied.com
Operacioni
Operacioni
Using the Remote User Interface
Karakteristikat e harduerit
The remote user interface keypad/display consists of an 8-line by 30 character display, a “push and roll” navigation wheel, and three buttons: Alarm, Menu, and Back (Figure 7).
· Turn the navigation wheel clockwise (right) or counterclockwise (left) to navigate between lines on a screen and also to increase and decrease changeable values when editing. Press down on the wheel to use it as an Enter button.
· Press the Back button to display the previous page. · Press the Home button to return to the main screen from
the current page. · Press the Alarm button to view the Alarm Lists menu.
Keypad/Display Features
The first line on each page includes the page title and the line
number to which the cursor is currently “pointing.” The line numbers are X/Y to indicate line number X of a total of Y lines for that page. The left most position of the title line includes an “up” arrow to indicate there are pages “above” the currently displayed items, a “down” arrow to indicate there are pages “below” the currently displayed items or an “up/down” arrow to indicate there are pages “above and below” the currently displayed page. Each line on a page can contain status-only information or include changeable data fields. When a line contains status-only information and the cursor is on that line, all but the value field of that line is highlighted meaning the text is white with a black box around it. When the line contains a changeable value and the cursor is at that line, the entire line is highlighted.
Each line on a page may also be defined as a “jump” line, meaning pushing the navigation wheel will cause a “jump” to a new page. An arrow is displayed to the far right of the line to indicate it is a “jump” line and the entire line is highlighted when the cursor is on that line.
NOTE: Only menus and items that are applicable to the specific unit configuration are displayed.
Figure 7: Remote User Interface Main Features
Butoni kryesor
Butoni i alarmit
Butoni prapa
Rrota e lundrimit
www.DaikinApplied.com
9
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
Alarmet
The Alarm Details Menu includes active alarm and alarm log information. See Figure 8 for an example of an active alarm. Also refer to the appropriate MicroTech unit controller Operation Manual (www.DaikinApplied.com) for available alarm options.
Figure 8: Alarm Details Menu
Figure 9: Main Password Page
Operacioni
Fjalëkalimet
Unit controller menu functions have different levels of accessibility. The ability to view and/or change settings depends on the access level of the user and the password entered. There are four levels of password access:
1. No password.
2. Level 2. The highest level of access. Without entering a password, the user has access only to basic status menu items. Entering the Level 2 password (6363) allows similar access as Level 4 with the addition of the Unit Configuration Menu.
3. Level 4. Entering the Level 4 password (2526) allows similar access as Level 6 with the addition of the Commission Unit Menu, Manual Control, and Service Menu groups.
4. Level 6. Entering the Level 6 password (5321) allows access to the Alarm Lists Menu, Quick Menu, and the View/Set Unit Menus group.
NOTE: Alarms can be acknowledged without entering a password.
Accessing The Password Page
The main password page is displayed when the remote user interface display (HMI) is first accessed.
1. Shtypni butonin Home.
2. Press the Back button multiple times, or if the keypad/ display has been idle longer than the Password Timeout (default 10 minutes).
The main password page provides access to enter a password, access the Quick Menu, view gjendjen aktuale të njësisë, hyni në listat e alarmit ose view information about the unit (Figure 9).
The MicroTech unit controller Operation Manual (www.DaikinApplied.com) provides additional information about passwords, including how to use the Navigation and Edit Mode settings to access and modify passwords.
Konfigurimi
The following section describes how to set up the HMI so that it can be used to display, configure, or change unit parameters. Refer to the applicable MicroTech unit controller Operation Manual for a detailed description of chiller or rooftop sequence of operation and keypad menu structure when configuring the unit via the remote user interface (www.DaikinApplied.com).
NOTE: To toggle between units, press the Back button for five seconds to return to the main screen.
Customize User Preferences
1. Turn power on to the unit controller(s). Power to the remote user interface is provided automatically from the MicroTech unit controller(s) through the RJ45 (Ethernet) direct connection.
2. The main screen with HMI Settings and Controller List appears (Figure 10).
Use the HMI Settings screen to change options for backlight color, backlight turn off time, contrast, and brightness.
NOTE: The main screen can be accessed at any time by pressing the Home button for five seconds.
3. Press the navigation wheel to select the HMI Settings menu, if desired.
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
10
www.DaikinApplied.com
Figure 10: Main Screen HMI Settings
Operacioni
NOTE: Refer to the Troubleshooting section if the remote user interface appears to “freeze” during the initial downloading sequence.
Figure 12: Information: Downloading Objects
Synchronize with MicroTech Unit Controller
1. Press the navigation wheel to select the Controller List screen (Figure 11).
· The Controller List automatically updates each time the remote user interface is powered up so that information is synchronized from the main unit controller.
· The Controller List screen displays the unit controller(s) connected to the remote user interface. This screen allows the user to select between units, if more than one unit is connected to the remote user interface
Figure 11: Controller List Details
3. Once the first unit has been downloaded, select the next unit controller, if applicable. The download process is required for each unit controller connected to the remote user interface.
4. Press the Home button for five seconds to return to the main screen.
NOTE: The Downloading the Objects sequence generally takes a minute or less when direct-connecting to a single unit. However, the downloading sequence takes longer when using the daisy-chain connection.
When the download sequence is complete, the Main screen of the unit controller appears on the remote user interface. At this point, the remote user interface and unit controller are synchronized.
5. Access and adjust the same parameters that are available via the unit controller keypad/display. Refer to the applicable MicroTech unit controller Operation Manual for the keypad menu structure and detailed description the unit controller sequence of operation (www.DaikinApplied.com).
NOTE: A single unit appears on the screen as a selection possibility if only one unit controller is connected to the remote user interface.
2. Turn the navigation wheel clockwise and then press down to select the desired unit.
· The Information screen appears as the remote user interface performs a download sequence to import the necessary information from the main unit controller. A status bar appears on the Downloading the Objects screen to indicate that the download is in process (Figure 12).
www.DaikinApplied.com
11
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
Procedura e përmirësimit të firmuerit
Follow these steps to update the remote user interface (HMI) firmware (.bin) file. NOTE: The upgrade procedure requires the use of an SD
memory card no larger than 8GB with a FAT32 file formati i sistemit.
NOTE: A field update is not possible on units with v1.07 firmware. Contact the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at (800) 4321342 (CHLTechSupport@daikinapplied.com) for assistance.
Upgrading from VVS10 to a newer version
1. Ngarko firmware-in file, POL12289.bin, on the SD-Card in the root directory with no other files.
2. Insert the SD Card into the MicroTech unit controller. The unit controller must be powered-up and running.
3. Connect the HMI DM to the unit controller.
4. Press the back button of the HMI DM until the “HMI Setting and Local Connection” page appears.
a. Choose the HMI Setting. Scroll to the end of this page and the “Firmware Update” option appears.
b. Push and roll to YES. Push the knob of the HMI DM again.
5. The “Now Firmware Updating” message appears on the user HMI display.
Do not remove power from the unit controller.
6. After successful upgrade of the firmware, the HMI DM goes back to the normal HMI page.
7. Follow steps 1-4 to upgrade firmware for each HMI on a daisy-chain network. Please be aware that each remote user interface must use the same firmware version.
Operacioni
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
12
www.DaikinApplied.com
Zgjidhja e problemeve
Zgjidhja e problemeve
This section contains helpful information, frequently asked questions, and other tips related to the remote user interface.
Tabela 2: Udhëzues për zgjidhjen e problemeve
Problem
Zgjidhje
During the initial download sequence, the keypad/display appears to freeze up and a “Loading……Lost Connection” message appears.
The remote user interface is stuck in the downloading sequence due to incompatibility with v1.07 application software. The remote user interface must be updated to v10.22 or newer application software. Contact Daikin Applied Air Technical Response at 800-432-1342 për udhëzime të mëtejshme.
The remote user interface has been connected to the MicroTech unit controller but the display remains blank after power-up.
Verify that the unit controller has power. Check wiring from the unit controller to the remote user interface. Note that inputs and outputs are polarity-sensitive.
The remote user interface is experiencing a loss of communication.
The site may have “dirty power” or electrical noise causing loss of communication. See below for further instruction.
1. Access the Power Bus menu on the MicroTech unit controller by the following keypad menu path: service menu/HMI setup/PBusPwrSply=ON (default). See Figure 13.
2. Set the default Power Bus supply.
a. For the first and last units on the daisy-chain trunk, leave the Power Bus supply at the default of ON.
b. For all other units within the daisy chain trunk, set the Power Bus supply to the OFF position.
Figure 13: Power Bus Menu
Pyetjet e bëra më shpesh
Zgjidhja e problemeve
1. Is a separate 24V power supply necessary for direct connection?
No, power is provided by the MicroTech unit controller.
2. What type of cable is recommended for daisy-chain connection?
Daikin Applied generally recommends using twisted pair, 16 AWG shielded cable up to 500 ft and 14 AWG from 500 to 1000 ft. Contact the appropriate Technical Response Center for applications requiring longer distances.
How do I know if or when I need to upgrade the remote user interface (HMI) firmware files?
If the remote user interface seems to freeze during initial download process
If wiring has been confirmed (inputs and outputs are polarity sensitive) and HMI is not responding
See Firmware Upgrade Procedure section for details.
What if I want to upgrade the MicroTech unit controller firmware?
Contact either the Daikin Applied Air Technical Response Center at 800-432-1342 (AAHTechSupport@daikinapplied.com) or the Chiller Technical Response Center at 800-432-1342 (CHLTechSupport@daikinapplied.com) for assistance.
Këshilla të dobishme
Service technicians often find it convenient to have two keypad/displays connected to a single unit controller. Using a split-screen setup makes it possible to view multiple menu items at the same time during start-up and also for diagnostic purposes.
Simply hook up the first remote user interface with an RJ45 direct connection, and then use a two-wire twisted pair cable to connect to the second keypad/display.
www.DaikinApplied.com
13
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
Historia e rishikimit
Historia e rishikimit
Revision IM 1005 IM 1005-1 IM 1005-2
IM 1005-3
IM 1005-4 IM 1005-5 IM 1005-6 IM 1005-7
Date January 2010 September 2010 March 2012
Nëntor 2016
January 2018 August 2019 June 2023 July 2025
Changes Initial release Added Daikin Trailblazer® chiller model AGZ-D Added Rebel® packaged rooftop model DPS. Updated Figure 3 with labels and connector cables. Added models AWV Pathfinder® chiller and AGZ-E Trailblazer® chiller, added RJ45 direct connection option, corrected bus wiring distance limitations, Troubleshooting section, Daikin branding and formatting updates Added WME & WWV chiller models.
Updated connections Branding and other formatting updates. Updated contact information, added Daikin Trailblazer® chiller model AMZ, and removed model lists from front cover.
IM 1005-7 · MICROTECH REMOTE USER INTERFACE
14
www.DaikinApplied.com
Trajnim dhe Zhvillim i Aplikuar i Daikin
Tani që keni bërë një investim në pajisje moderne dhe efikase Daikin Applied, kujdesi për to duhet të jetë një përparësi e lartë. Për informacion mbi trajnimin mbi të gjitha produktet Daikin Applied HVAC, ju lutemi na vizitoni në www.DaikinApplied.com dhe klikoni te Trajnimi, ose telefononi. 540-248-9646 dhe kërkoni për Departamentin e Trajnimit.
Garancia
Të gjitha pajisjet Daikin Applied shiten në përputhje me termat dhe kushtet standarde të shitjes, duke përfshirë Garancinë e Kufizuar të Produktit. Konsultohuni me përfaqësuesin tuaj lokal të aplikuar të Daikin për detajet e garancisë. Për të gjetur përfaqësuesin tuaj lokal të Daikin Applied, shkoni te www.DaikinApplied.com.
Shërbimet pas tregtimit
Për të gjetur zyrën tuaj lokale të pjesëve, vizitoni www.DaikinApplied.com ose telefononi 800-37PARTS (800-377-2787Për të gjetur zyrën tuaj lokale të shërbimit, vizitoni www.DaikinApplied.com ose telefononi 800-432-1342.
Ky dokument përmban informacionin më aktual të produktit që nga ky printim. Për informacionin më të përditësuar të produktit, ju lutemi shkoni te www.DaikinApplied.com.
Produkte të prodhuara në një objekt të certifikuar ISO.
IM 1005-7 (07/25)
©2025 Daikin Applied | (800) 432 | www.DaikinApplied.com