NFA-T01CM Addressable Input Output Control Module
Product Information
Specifications
- Model: NFA-T01CM
- Compliance: EN54-18:2005
- Manufacturer: Norden Communication UK Ltd.
- Addressable Input/Output Control Module
Product Usage Instructions
Installation
Follow the steps below for proper installation:
Installation Preparation
Ensure all necessary tools and equipment are available before starting the installation process.
Installation and Wiring
Refer to the installation manual for detailed instructions on wiring the module correctly to ensure proper functionality.
Interface Module Configuration
Configure the interface module as per the following guidelines:
Preparation
Before configuration, make sure you have access to the necessary documentation and software.
Write: Addressing
Set the addressing parameters according to the requirements specified in the manual.
Feedback Mode
Enable feedback mode for receiving status updates from the connected devices.
Input Check Mode
Activate input check mode to monitor input signals effectively.
Output Check Mode
Utilize output check mode to verify the functionality of output signals.
Read Configuration
Review and verify the configured settings to ensure proper operation.
General Maintenance
Regularly inspect and clean the module to prevent dust accumulation and ensure optimal performance.
Troubleshooting Guide
Refer to the troubleshooting section in the manual for assistance in resolving any operational issues.
Product Safety
- To prevent severe injury and loss of life or property, read the instruction carefully before installing the module to ensure proper and safe operation of the system.
European Union directive :2012/19/EU (WEEE directive): Products marked with this symbol cannot be disposed of as unsorted municipal waste in the European Union. For prop-er recycling, return this product to your local supplier upon the purchase of equivalent new equipment, or dispose of it at designated collection points.
- For more information please visit the website at www.recyclethis.info
- EN54 Part 18 Compliance
- NFA-T01CM Addressable Input/Output Control Module complies with the requirements of EN 54-18:2005.
Introduction
Overview
- The Addressable Input Output Control Module serves as a versatile input/output relay and control unit. Typically, it is employed to override various equipment functions, including lift returns, door holders, smoke extract fans, air handling units, and auto-dialers to the fire brigade and building man-agement systems (BMS). Notably, this module features a built-in feedback signal mechanism. When a pre-configured interface module commands a fire scenario, the alarm controller sends a start com-mand to the relevant equipment. Upon receiving this command, the output module activates its relay, resulting in a change of state. Subsequently, once the module is under control and operational, a confirmation signal is transmitted back to the alarm controller.
- Additionally, the unit incorporates an intelligent processor that automatically monitors both open and short circuits in the input signal line. The unit is meticulously crafted to meet the requirements of the EN 54 Part 18 European Standard. Its design is not only aesthetically pleasing but also unobtrusive, seamlessly blending with modern build-ing architecture. The plug-in assembly simplifies installation and maintenance, providing convenience to installers. Importantly, this unit is fully compatible with the NFA-T04FP Analogue Intelligent Fire Alarm Control Panel and this compatibility ensures seamless addressable communication, eliminating any potential compatibility issues.
Feature and Benefits
- EN54-18 Compliance
- Built-in MCU processor and digital addressing
- 24VDC/2A Output relay contact and Control module
- Input Fire or Supervisory signal configuration
- LED status indicator
- Onsite Adjustable Parameter
- Loop or external power input
- Aesthetically pleasing design
- Surface mounting with fix base for simple installation
Technical Specification
- Listed LPCB Certification
- Compliance EN 54-18:2005
- Input Voltage Loop Power:24VDC [16V to 28V] External PSU: 20 to 28VDC
- Current Consumption Loop: Standby 0.6mA, Alarm: 1.6mA
- External PSU: Standby 0.6mA, Alarm: 45mA
- Control output voltage 24VDC / 2A rating
- Input Relay Normally Open dry contact
- Input Resistance 5.1Kohms/ ¼ W
- Protocol/Addressing Norden, Value ranges from 1 to 254
- Indicator Status Normal: Single blink/Active: Steady/Fault: Double Blink
- Material / Colour ABS / White Glossy finishing
- Dimension / LWH 108 mm x 86 mm x38 mm
- Weight 170g (with Base), 92g (without Base)
- Operating Temperature -10°C to +50°C
- Ingress Protection Rating IP30
- Humidity 0 to 95% Relative Humidity, Non condensing
Installation
Installation Preparation
- This interface module must be installed, commissioned and maintained by a qualified or factory trained service personnel. The installation must be installed in compliance with all local codes having a jurisdiction in your area or BS 5839 Part 1 and EN54.
Norden products has available range of interfaces, each interface module is designed for specific ap-plication, it is essential to consider the requirement of both sides of the interface to avoid malfunction and typical fault scenario. The main caution is to ensure that the voltage rating of the equipment and interface module are compatible.
Installation and Wiring
- Mount the interface module base on standard one [1] gang electrical back box. Follow the arrow mark for the correct position. Do not over-tighten the screws otherwise the base will twist. Use two M4 standard screws.
- Connect the wire in terminal according to the requirement as shown in Figure two [2] to five [5]. Verify the device address and other parameters then stick on the label before attaching the module. The sticker labels are available on the control panel. Align the interface module and tabs and gently pushing the device until it locks into place.
- Figure 1: I/O Control Module Structure
Terminal Description
- Z1 Signal In (+) :D1 External Power Supply In (+)
- Z1 Signal Out (+) :D2 External Power Supply In (-)
- Z2 Signal In (-) :D3 External Power Supply Out (+)
- Z2 Signal Out (-) :D4 External Power Supply Out (-)
- RET Input Cable :COM Output Cable
- G Input Cable :NO, NC Output Cable
- Figure 2: Input Wiring Details
- Note: Change the parameter Input Check into 3Y (Loop Powered)
- Figure 3: Relay Output Wiring Details (Loop Powered) mostly used
Signal | Monitoring | When Off(normal) | When On(active) |
Input | YES (Optional) | Normally Open | Normally Close |
Relay Output | YES | Normally Open | Normally Close |
Normally Close | Normally Open | ||
Power Limited Output | YES | +1.5-3Vdc | +24Vdc |
Input/output Parameters
Signal | Feedback | Input Check | Output Check |
Input |
– |
3Y (Yes)- Fit with resistor – 4N (No)- No resistor is re- quired -–Default setting |
– |
Relay Output |
1Y (Yes)- By the SELF
2N (No)- By the EXTERNAL – (Note: in relation with the Input signal) Default setting |
– |
– |
1Y (Yes)- By the SELF |
– |
5Y(Yes)-Supervise 24VDC |
|
Power Limited | 2N (No)- By the EXTERNAL – | continuity – Default setting | |
Output | (Note: in relation with the
Input signal) Default setting |
6N(No)- No supervision |
Interface Module Configuration
Preparation
- The NFA-T01PT Programming tool is used to configure interface module soft address and parameter. This tools is not included, must be purchased separately. The programming tool is packed with twin 1.5V AA battery and cable, ready for usage once received.
- It is mandatory for the commissioning personnel to have programming tool in order to adjust the module conferring to the site situation and environmental requirements.
- Program a unique address number for each device according to the project layout before placing from the Terminal Base.
- Warning: Disconnect the loop connection whilst connecting to the programming tool.
Write: Addressing
- Connect the programming cable to Z1 and Z2 terminals (Figure 6). Press “Power” to switch on the unit.
- Switch-on the programming tool, then press button “Write” or number “2” to enter Write Ad-dress mode (Figure 7).
- Input the desire device address value from 1 to 254, and then press “Write” to save the new address (Figure 8).
- Note: If display “Success”, means the entered address is confirmed. If display “Fail”, means failure to program the address (Figure 9).
- Press “Exit” key to go back Main Menu. Press “Power” key to switch-off the programming tool.
Feedback Mode
- Feedback mode has two types, SELF and EXTERNAL. Under SELF-feedback mode, once the inter-face module received active command from the panel, the module automatically send feedback signal to the control panel, alongside the Feedback LED indicator goes turn-on. While the Ex-ternal-feedback mode will do similar action when the interface module detects feedback signal from Input terminal. Default setting is External-feedback mode.
- Connect the programming cable to Z1 and Z2 terminals (Figure 6). Press “Power” to switch-on the unit.
- Switch-on the programming tool, then press button “3” to enter to Configuration mode (Figure 10).
- Input the “1” for Self-feedback mode or “2” for External-feedback mode then press “Write” to change the setting (Figure 11).
- Note: If display “Success”, means the entered mode is confirmed. If display “Fail”, means failure to program the mode.
- Press “Exit” key to go back Main Menu. Press “Power” to switch off the programming tool.
Input Check Mode
- Input Check mode is used to enable the input cable monitoring, this option is available when parameter is set to 3Y with fitted end of line resistor. The module monitor will report to the panel in the event of open or short circuit occurs in the wiring.
- To set to check mode. Connect the programming cable to Z1 and Z2 terminals (Figure 6). Press “Power” to switch-on the unit.
- Switch-on the programming tool, then press button “3” to enter to Configuration mode (Figure 12).
- Input the “3” key for Check mode then press “Write” to change the setting (Figure 13).
- Note:If display “Success”, means the entered mode is confirmed. If display “Fail”, means failure to program the mode.
- Press “Exit” key to go back Main Menu. Press “Power” to switch off the programming tool.
Output Check Mode
- Output Check mode is used to enable voltage monitoring. The module will report to the panel in the event of low voltage output caused by open and short circuit occur in the wiring.
- Connect the programming cable to Z1 and Z2 terminals (Figure 6). Press “Power” to switch-on the unit.
- Switch-on the programming tool, then press button “3” to enter to Configuration mode (Figure 14).
- Input the “5” for Check mode then press “Write” to change the setting (Figure 15).
- Note: If display “Success”, means the entered mode is confirmed. If display “Fail”, means failure to program the mode.
- Press “Exit” key to go back Main Menu. Press “Power” to switch off the programming tool.
Read Configuration
- Connect the programming cable to Z1 and Z2 terminals (Figure 6). Press “Power” to switch-on the unit.
- Switch-on the programming tool, then press button “Read” or “1” to enter to Read mode (Figure 16). The programming tool will display the configuration after few seconds. (Figure 17).
- Press “Exit” key to go back Main Menu. Press “Power” key to switch off the programming tool.
General Maintenance
- Inform the suitable personnel before conducting the maintenance.
- Disable the interface module on the control panel to prevent false alarm.
- Do not attempt to repair the circuitry of the interface module, it may affect the operation to respond to a fire condition and will void the manufacturer’s warranty.
- Use a damp cloth to clean the surface.
- Notify again proper personnel after conducting the maintenance and make sure to enable the interface module and confirm if up and running.
- Perform the maintenance on semi-annually or depending on the site conditions.
Troubleshooting Guide
What you notice | What it means | What to do |
Address not enrolling | The wiring is loose
The address is duplicate |
Conduct maintenance
Re-Commission the device |
Unable to commission | The damage of the electronic circuit | Replace the device |
Appendix
Limitation of Interface Module
- The Interface Module cannot last forever. To keep the interface module working in good condition, please maintain the equipment continuously according to recommendations from manufacturers and relative nation codes and laws. Take specific maintenance measures on the basis of different environ-ments.
- This interface module contains electronic parts. Even though it is made to last for a long period of time, any of these parts could fail at any time. Therefore, test your module at least every half-year ac-cording to national codes or laws. Any interface module, fire alarm devices or any other components of the system must be repaired and/or replaced immediately as they fail.
more info
- Norden Communication UK Ltd.
- Unit 10 Baker Close, Oakwood Business Park Clacton-On- Sea, Essex
- POST CODE:CO15 4BD
- Tel : +44 (0) 2045405070
- E-mail : salesuk@norden.co.uk
- www.nordencommunication.com
FAQs
- Q: Where can I find more information on product safety?
- A: Visit www.nordencommunication.com for detailed product safety information.