R. STAHL Circuit Breaker 8530/1-MCB-STA101-B10-500-2
Article No. 293977
Product Description
The R. STAHL 8530 series circuit breakers offer excellent short-circuit limitation and high breaking capacity (10, 15, or 25 kA). This results in reduced stress on electrical lines and improved selectivity with upstream fuses. The modules feature a modular design, are available in 1 to 4-pole versions, and support nominal currents from 0.5–63 A. The maximum mounting width is 4.5 division units.
Key features include:
- Circuit breaker function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of installations due to modular design
- Simple mounting via DIN rail snap-in in Ex e enclosures
- Fixed thermal and magnetic trip settings
- Ergonomic operating lever for secure connection and disconnection
- Protection against reconnection during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Application (Zones) | Application (Zones) Note | IECEx Gas Approval | IECEx Gas Explosion Protection | ATEX Gas Approval | ATEX Gas Explosion Protection |
---|---|---|---|---|---|
1, 2 | Can be used in zones 21/22 with Ex tb/tc enclosure protection | IECEx FMG 19.0029U | Ex db eb IIC Gb | FM19ATEX0191U | II 2 G Ex db eb IIC Gb |
Certifications
Certification | Certificate of Conformity |
---|---|
ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) | Certificate of Conformity (ATEX) |
Electrical Data
Parameter | Value |
---|---|
Rated operational voltage AC | 230 V |
Rated operational current | 10 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | Auxiliary contact 1 changeover + Error signal contact 1 changeover |
Voltage 1st auxiliary function AC | 230 V |
Max. current 1st auxiliary function | 2 A |
2nd auxiliary function | None |
Max. voltage 2nd aux. CC | 8 |
Trip characteristic | B |
Number of poles | 1 pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection cross-section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection AWG min. | 16 AWG |
Connection AWG max. | 4 AWG |
Connection 2 min. | 1.5 mm² |
Connection 2 max. | 10 mm² |
Connection 2 AWG min. | 16 AWG |
Connection 2 AWG max. | 8 AWG |
Connection HIKO min. | 0.5 mm² |
Connection HIKO max. | 4 mm² |
Connection HIKO min AWG | 18 (unece.unit.AWG) |
Connection HIKO max AWG | 14 (unece.unit.AWG) |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection Note | 2 conductors (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only one cross-sectional difference between the upper and lower chamber can be connected). Permitted connection cross-section combinations are listed in the operating instructions. |
Dimensions
Parameter | Value (mm) | Value (in) |
---|---|---|
Width | 65 | 2.56 |
Mounting width | - | - |
Length | 165 | 6.50 |
Installation depth | 138.3 | 5.44 |
Weight
Parameter | Value (kg) | Value (lb) |
---|---|---|
Weight | 1 | 2.205 |
Mounting / Installation
Parameter | Value (N·m) | Value (lbf·in) |
---|---|---|
Tightening torque | 2-3 | 17.7 ... 26.6 |
Tightening torque auxiliary contact | 0.4 - 0.6 | 3.5 - 5.3 |
Technical Diagrams
Trip Characteristic Curve B
A graph showing the trip time in seconds and minutes against current multiples for a Type B tripping characteristic. The curve indicates the time it takes for the circuit breaker to trip under various overcurrent conditions.
Measurement Diagram
Diagrams illustrating the dimensions of the circuit breaker in millimeters and inches. Key dimensions include width, length, and installation depth.
Accessories
Cylinder Lock
Padlock / labeling device for individual component locking using up to 4 cylinder locks.
Article No.: 227232
Fixing Kit
A set of fixings for mounting the component on a mounting plate without a top-hat rail.
Article No.: 276618