R. STAHL LS Leitungsschutzschalter
Model: 8530/1-MCB-STA101-B10-500-2
Article No.: 293977
Product Overview
The R. STAHL 8530/1-MCB-STA101-B10-500-2 miniature circuit breakers offer excellent current limiting capabilities for short circuits, with high switching capacities of 10, 15, or 25 kA. This results in reduced stress on conductors and higher selectivity with upstream fuses. The devices are modularly designed, available in 1- to 4-pole versions, and rated for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 module units (TE).
Key features include:
- Trennerfunktion according to EN 60947-2
- Energy limitation class 3
- Easy installation and expansion due to modular design
- Simple mounting by snapping onto mounting rails in Ex e enclosures
- Fixed thermal and magnetic trip units
- Ergonomically shaped operating lever for secure switching
- Protection against re-switching during maintenance using padlocks (accessory)
Explosion Protection
Parameter | Details |
---|---|
Einsatzbereich (Zonen) | 1, 2 |
Einsatzbereich (Zonen) Hinweis | Usable in Zone 21 / 22 with protection by enclosure Ex tb / tc |
IECEx Bescheinigung Gas | IECEx FMG 19.0029U |
IECEx Gasexplosionsschutz | Ex db eb IIC Gb |
ATEX Bescheinigung Gas | FM19ATEX0191U |
ATEX Gasexplosionsschutz | II 2 G Ex db eb IIC Gb |
Bescheinigungen | ATEX (FM), Brasilien (ULB), IECEx (FM), Volksrepublik China (CQST) |
Konformitätserklärungen | Konformitätsbescheinigung (ATEX) |
Electrical Data
Parameter | Details |
---|---|
Bemessungsbetriebsspannung AC | 230 V |
Bemessungsbetriebsstrom | 10 A |
Frequenz | 50/60 Hz |
Bemessungsschaltvermögen | 10 kA |
Elektrische Lebensdauer | 2 x 10⁴ |
Mechanische Lebensdauer | 2 x 10⁵ |
1. Hilfsfunktion | Hilfskontakt 1 Wechsler + Fehlersignalkontakt 1 Wechsler |
Bemessungsspannung 1. Hilfsfunktion AC | 230 V |
Max. Bemessungsstrom 1. Hilfsfunktion | 2 A |
2. Hilfsfunktion | ohne |
Max. Spannung 2. Hilfsfunktion DC | - |
Auslösecharakteristik | B |
Polzahl | 1-polig |
Environmental Conditions
Parameter | Details |
---|---|
Umgebungstemperatur | -40 °C ... 70 °C (-40 °F ... 158 °F) |
Umgebungstemperatur Hinweis | Deviating ambient temperatures are available upon request based on current certificates. |
Mechanical Data
Parameter | Details |
---|---|
Schutzart (IP) (IEC 60529) | IP2X |
Gehäusematerial | Thermoplast |
Anschlussquerschnitt min. | 1.5 mm² |
Anschlussquerschnitt max. | 25 mm² |
Anschlussquerschnitt AWG min. | 16 AWG |
Anschlussquerschnitt AWG max. | 4 AWG |
Anschlussquerschnitt 2 min. | 1.5 mm² |
Anschlussquerschnitt 2 max. | 10 mm² |
Anschlussquerschnitt 2 AWG min. | 16 AWG |
Anschlussquerschnitt 2 AWG max. | 8 AWG |
Anschlussquerschnitt HIKO min. | 0.5 mm² |
Anschlussquerschnitt HIKO max. | 4 mm² |
Anschlussquerschnitt HIKO AWG min. | 18 AWG |
Anschlussquerschnitt HIKO AWG max. | 14 AWG |
Anzugsdrehmoment min. | 2 N·m |
Anzugsdrehmoment max. | 3 N·m |
Anschlussquerschnitt Hinweis | 2-conductor connection (upper and lower chamber simultaneously): upper and lower chamber max. 16/10 mm² (A maximum cross-section difference between the upper and lower chamber can be clamped.) The permitted combination possibilities of the connection cross-sections can be found in the operating manual. |
Breite | 65 mm [2.56 in] |
Länge | 165 mm [6.5 in] |
Einbautiefe | 138.3 mm [5.44 in] |
Gewicht | 1 kg [2.205 lb] |
Mounting / Installation
Parameter | Details |
---|---|
Anzugsdrehmoment | 2-3 N·m |
Anzugsdrehmoment Ibf in | 17.7 ... 26.6 lbf-in |
Anzugsdrehmoment Hilfskontakt | 0.4-0.6 Nm |
Anzugsdrehmoment Hilfskontakt Ibf in | 3.5 ... 5.3 lbf in |
Technical Drawings
Trip Time Characteristic B:
A graph shows the trip time in seconds versus multiples of the rated current (I/In) for AC and DC. The curve indicates the limit characteristic from a cold state. For AC, the trip times are shown for multiples of the rated current from 1 to 10. For DC, the trip times are shown from 1 to 5.
Dimensional Drawings:
Detailed drawings with dimensions in mm [inch] are provided for the device, showing width, height, and depth. The drawings indicate the device is 8530/1 with 2 module units.
Accessories
Befestigungsset (Mounting Set)
A mounting set for attaching the component to the mounting plate without a top hat rail.
Description | Art. Nr. |
---|---|
Ein Befestigungsset zum Befestigen der Komponente auf der Montageplatte ohne Hutschine. | 276618 |
Zylinderschloss (Cylinder Lock)
A lock-out / tag-out device for individually locking the component, usable with up to 4 cylinder locks.
Description | Art. Nr. |
---|---|
Zum Abschließen (Bügel Ø 3) | 107115 |