R. STAHL Miniature Circuit Breaker
Model: 8530/1-MCB-STA101-B10-500-2
Art. No.: 293977
Product Overview
The R. STAHL 8530 series miniature circuit breakers (MCBs) are overcurrent devices designed for robust system solutions. They offer excellent current limiting for short circuits and a high switching capacity of 10, 15, or 25 kA, resulting in reduced stress on cables and enhanced selectivity for upstream fuses. These components feature a modular design, available in 1- to 4-pole configurations, with rated currents ranging from 0.5-63 A. The maximum installation capacity is 4.5 subunits.
Key features include:
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Simple replacement and expansion of existing systems due to modular design
- Easy installation with snap-on mounting onto the mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching operation
- Provision for padlocks (accessories) to prevent accidental switching during maintenance
Technical Data
Explosion Protection
- Application range (zones): 1, 2
- Application range (Zone) note: For use in Zone 21/22 when protected by Ex tb/tc enclosure
- IECEx gas certificate: IECEx FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certificate: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
- Declaration of conformity: Certificate of conformity (ATEX)
Electrical Data
Parameter | Value |
---|---|
Rated operational voltage AC | 230 V |
Rated operational current | 10 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact |
1st auxiliary function for AC rated voltage | 230 V |
1st auxiliary function for rated current max. | 2 A |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | B |
No. of poles | 1-pole |
Ambient Conditions
- Ambient temperature: -40 °C ... 70 °C
- Ambient temperature (Fahrenheit): -40 °F ... 158 °F
- Ambient temperature note: Deviating ambient temperatures based on current certificates available on request.
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP2X
- Enclosure material: Thermoplast
- Connection cross section min.: 1.5 mm²
- Connection cross-section max.: 25 mm²
- Connection cross-section AWG min.: 16 AWG
- Connection cross-section AWG max.: 4 AWG
- Connection cross-section 2 min.: 1.5 mm²
- Connection cross-section 2 max.: 10 mm²
- Connection cross-section 2 AWG min.: 16 AWG
- Connection cross-section 2 AWG max.: 8 AWG
- Min. aux. cont. con. cr.-sect.: 0.5 mm²
- Max. aux. cont. conn. cr.-sec.: 4 mm²
- Min. aux. co. con. cr.-se. AWG: 18 (unece.unit.AWG)
- Connection cross-section of auxiliary contact AWG max.: 14 (unece.unit.AWG)
- Min. tightening torque: 2 N·m
- Max. tightening torque: 3 N·m
- Connection cross-section note: 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16 / 10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) The permitted combinations of connection cross-sections can be found in the operating instructions.
- Width: 65 mm (2.56 in)
- Length: 165 mm (6.5 in)
- Mounting depth: 138.3 mm (5.44 in)
- Weight: 1 kg (2.205 lb)
Mounting / Installation
- Tightening torque: 2-3 N·m
- Tightening torque lbf in: 17.7 to 26.6 lbf-in
- Tightening torque auxiliary contact: 0.4–0.6 N·m
- Tightening torque auxiliary contact lbf in: 3.5 to 5.3 lbf in
Technical Drawings
Subject to Alterations
Tripping Characteristic B:
A diagram shows tripping time in minutes and seconds versus multiples of rated current for AC and DC, illustrating the tripping curve from a cold state.
Dimensional Drawings (All Dimensions in mm [inches]):
Diagrams show the front view, side view, and top view of the circuit breaker with key dimensions labeled.
1-pole, auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact
A diagram illustrates the configuration of the auxiliary contacts.
Accessories
- 4-way locking device: A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks. (Art. No. 227232)
- Cylinder lock: For closing (bracket Ø 3). (Art. No. 107115)
- Fastening set: A fastening set for securing the component on the mounting plate without a DIN rail. (Art. No. 276618)
R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs, and products available without notice. The illustrations cannot be considered binding.