R. STAHL 8530/1-MCB-STA101-C16-500-2 Circuit Breaker
Article No. 293997
System Components for Technology
The R. STAHL 8530 series circuit breakers offer excellent current limitation in short-circuit situations and high breaking capacities of 10, 15, or 25 kA. This results in reduced stress on electrical lines and improved selectivity with upstream fuses. The modules feature a modular design, available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Key Features:
- Disconnecting function according to EN 60947-2
- Energy limitation class 3
- Easy replacement or expansion of installations due to modular design
- Simple mounting via DIN rail snap-in in Ex e enclosures
- Fixed thermal and magnetic trip settings
- Ergonomic operating lever ensures safe connection and disconnection
- Protection against re-closing during maintenance using padlocks (Accessories)
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with enclosure protection Ex tb/tc |
IECEX gas certification | IECEx FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of Conformity | ATEX (FM) |
Electrical Data
Parameter | Value |
---|---|
Rated operating voltage AC | 230 V |
Rated operating current | 16 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical endurance | 2 x 10⁴ |
Mechanical endurance | 2 x 10⁴ |
1st auxiliary function | Auxiliary contact 1 changeover + Error signal contact 1 changeover |
Voltage 1st auxiliary function AC | 230 V |
Max. current 1st auxiliary function | 2 A |
2nd auxiliary function | None |
Max. voltage 2nd aux. function DC | - |
Tripping characteristic | C |
Number of poles | 1 pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C (-40 °F ... 158 °F) |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 cross-section min. | 1.5 mm² |
Connection terminal 2 cross-section max. | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Connection terminal HIKO min. | 0.5 mm² |
Connection terminal HIKO max. | 4 mm² |
Connection terminal HIKO min AWG | 18 (unece.unit.AWG) |
Connection terminal HIKO max AWG | 14 (unece.unit.AWG) |
Tightening torque min. | 2-3 N·m |
Tightening torque max. | 3 N·m |
Connection terminal Note | 2 conductors (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (only one cross-section difference between chambers is permitted.) Permitted connection cross-section combinations are listed in the operating instructions. |
Dimensions
Parameter | Value (mm) | Value (in) |
---|---|---|
Width | 65 | 2.56 |
Mounting width | - | 2.56 in |
Length | 165 | 6.50 |
Installation depth | 138.3 | 5.44 |
Weight | 1 kg | 2.205 lb |
Mounting / Installation
Parameter | Value (N·m) | Value (lbf·in) |
---|---|---|
Tightening torque | 2-3 | 17.7 ... 26.6 |
Tightening torque auxiliary contact | 0.4-0.6 | 3.5 ... 5.3 |
Technical Diagrams
Trip Time Curve: A graph illustrating the tripping characteristic curve for the circuit breaker, showing time in seconds versus multiples of the rated current (I/In). The curve is labeled 'Characteristic limit from cold state' and indicates tripping characteristics for AC and DC.
Measurement Diagram: A diagram showing the physical dimensions of the circuit breaker, with measurements provided in both millimeters and inches. Key dimensions include width, length, and installation depth.
Accessories
Cylinder Lock
Description: Padlockable hasp for individual component locking using up to 4 cylinder locks.
Article No.: 227232
Fixing Kit
Description: A set of fixings for mounting the component onto a mounting plate without a top hat rail.
Article No.: 276618
R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.