R. STAHL 8530/1-MCB-STA101-B16-500-2 Circuit Breaker
Article No.: 293980
System Components - Circuit Breaker
The R. STAHL 8530 series circuit breakers offer excellent short-circuit current limitation and high breaking capacities of 10, 15, or 25 kA. This results in reduced stress on electrical lines and high selectivity with respect to upstream fuses. The modules feature a modular design and are available in 1 to 4-pole versions with nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Key Features:
- Disconnector function according to EN 60947-2
- Energy limitation class 3
- Simple replacement or expansion of installations due to the modular design of the circuit breaker.
- Simple mounting by clipping onto a DIN mounting rail in Ex e enclosures.
- Thermally and magnetically tripped, with fixed settings.
- Ergonomic operating lever ensures safe connection and disconnection.
- Protection against reconnection during maintenance using padlocks (Accessories).
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEX gas certification | IECEx FMG 19.0029U |
IECEx gas explosion protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX gas explosion protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX) |
Electrical Data
Parameter | Value |
---|---|
Rated operating voltage AC | 230 V |
Rated operating current | 16 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | Changeover contact (1 changeover contact) + Error signal contact (1 changeover contact) |
Voltage 1st auxiliary function AC | 230 V |
Max. current 1st auxiliary function | 2 A |
2nd auxiliary function | None |
Max. voltage 2nd aux. function DC | 8 |
Characteristic curve of tripping | B |
Number of poles | 1-pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection cross-section min. | 1.5 mm² |
Connection cross-section max. | 25 mm² |
Connection cross-section AWG min. | 16 AWG |
Connection cross-section AWG max. | 4 AWG |
Connection cross-section 2 min. | 1.5 mm² |
Connection cross-section 2 max. | 10 mm² |
Connection cross-section 2 AWG min. | 16 AWG |
Connection cross-section 2 AWG max. | 8 AWG |
Connection HIKO cross-section min. | 0.5 mm² |
Connection HIKO cross-section max. | 4 mm² |
Connection HIKO cross-section AWG min. | 18 (unece.unit.AWG) |
Connection HIKO cross-section AWG max. | 14 (unece.unit.AWG) |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection cross-section Note | 2 conductor connections (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (only one cross-sectional difference between the upper and lower chamber can be connected.) Permitted connection cross-section combinations are listed in the operating instructions. |
Dimensions
Parameter | Value |
---|---|
Width | 65 mm |
Mounting width in inches | 2.56 in |
Length | 165 mm |
Length in inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth in inches | 5.44 in |
Weight | 1 kg |
Weight in lbs | 2.205 lb |
Mounting / Installation
Parameter | Value |
---|---|
Tightening torque | 2-3 N·m |
Tightening torque lbf·in | 17.7 ... 26.6 lbf·in |
Tightening torque auxiliary contact | 0.4 - 0.6 Nm |
Tightening torque auxiliary contact lbf·in | 3.5 ... 5.3 lbf·in |
Technical Diagrams
Technical Diagrams - Subject to change.
Measurement Diagram (all dimensions in [inches]) - Subject to change.
Diagram 1: Tripping characteristic curve B for AC and DC. Shows time to trip in seconds and minutes against current in Amperes.
Diagram 2: Shows the dimensions of the circuit breaker, including width, length, installation depth, and mounting points.
Accessories
Accessory | Article No. |
---|---|
Cylinder lock | 107115 |
Description: Cylinder lock for securing the component (stirrup Ø 3). | |
Quadruple immobilization device | 227232 |
Description: Locking/tagging pliers for individual component locking using up to 4 cylinder locks. | |
Fixing kit | 276618 |
Description: A set of fixings for mounting the component on the mounting plate without a top hat rail. |
R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.