R. STAHL 8530/1-MCB-STA101-B10-500-2 Line Protection Circuit Breaker
Article No. 293977
System Components for Technology
Product: Line Protection Circuit Breaker
Model: 8530/1-MCB-STA101-B10-500-2
Article No.: 293977
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation for short circuits and high switching capacities of 10, 15, or 25 kA. They are designed for minimal load on lines and high selectivity to upstream fuses. These components are modular and available in 1 to 4-pole versions with nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key Features:
- Function: Disconnection according to EN 60947-2
- Energy Limitation Class: 3
- Design: Easy replacement or system extension due to modular circuit breaker design. Simple plug-in mounting on a DIN rail in Ex e enclosures.
- Actuators: Fixed magneto-thermal releases.
- Operation: Ergonomic lever for safe switching on and off.
- Safety: Padlock protection (accessories) prevents re-operation during maintenance.
Technical Characteristics
Explosion Protection
Application Area (Zones) | 1, 2 |
Application Area (Zones) Note | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Protection Against Gas Explosion | Ex db eb IIC Gb |
ATEX Certificate Gas | FM19ATEX0191U |
ATEX Protection Against Gas Explosion | II 2G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX) |
Electrical Characteristics
Rated Operational Voltage AC | 230 V |
Rated Service Current | 10 A |
Frequency | 50/60 Hz |
Rated Switching Capacity | 10 kA |
Electrical Service Life | 2 x 104 |
Mechanical Service Life | 2 x 104 |
1st Auxiliary Function | Auxiliary contact 1 changeover contact + signal error contact 1 changeover contact |
Voltage 1st Auxiliary Function AC | 230 V |
Max. Current 1st Auxiliary Function | 2 A |
2nd Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | - |
Tripping Characteristic | B |
Number of Poles | 1 pole |
Ambient Conditions
Ambient Temperature | -40 °C ... 70 °C |
Ambient Temperature | -40 °F ... 158 °F |
Ambient Temperature Note | Ambient temperatures different from those specified are available upon request, based on current certificates. |
Mechanical Characteristics
Degree of Protection (IP) (IEC 60529) | IP2X |
Enclosure Material | Thermoplastic |
Connection Terminal Minimum Section | 1.5 mm² |
Connection Terminal Maximum Section | 25 mm² |
Connection Terminal AWG Minimum | 16 AWG |
Connection Terminal AWG Maximum | 4 AWG |
Connection Terminal 2 Minimum Section | 1.5 mm² |
Connection Terminal 2 Maximum Section | 10 mm² |
Connection Terminal 2 AWG Minimum | 16 AWG |
Connection Terminal 2 AWG Maximum | 8 AWG |
Connection Auxiliary Contact Minimum Section | 0.5 mm² |
Connection Auxiliary Contact Maximum Section | 4 mm² |
Connection Auxiliary Contact Minimum AWG | 18 (unece.unit.AWG) |
Connection Auxiliary Contact Maximum AWG | 14 (unece.unit.AWG) |
Minimum Tightening Torque | 2 N·m |
Maximum Tightening Torque | 3 N·m |
Connection Terminal Note | Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber maximum 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) Authorized combination possibilities for connection terminals are listed in the operating manual. |
Dimensions
Width | 65 mm (2.56 in) |
Length | 165 mm (6.5 in) |
Mounting Depth | 138.3 mm (5.44 in) |
Weight
Weight | 1 kg (2.205 lb) |
Mounting / Installation
Tightening Torque | 2-3 N·m |
Tightening Torque (lbf-in) | 17.7 ... 26.6 lbf-in |
Tightening Torque Auxiliary Contact | 0.4–0.6 Nm |
Tightening Torque Auxiliary Contact (lbf-in) | 3.5 ... 5.3 lbf-in |
Technical Drawings
Dimensions are in mm [inches] - subject to change.
Tripping Characteristic Curve
Characteristic curve limit from cold state.
Tripping Characteristic: B
1-pole, auxiliary contact: 1 changeover contact + 1 signal error contact changeover contact
Overall Dimensions
All dimensions are in mm [inches] - subject to change.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Quadruple locking/unlocking device for individual component locking with up to 4 cylinder locks. | Article No. | 227232 |
Mounting Kit
Description | A mounting kit for fixing the component to a mounting plate without a DIN rail. | Article No. | 276618 |
Cylinder Lock
Description | For locking (shackle Ø 3) | Article No. | 107115 |
Subject to change regarding technical characteristics, dimensions, weight, construction types, and delivery possibilities. Figures are for indicative purposes only.