INKBIRD IHC-200 Plug and Play Humidity Controller
Model: IHC-200
Manufacturer: Inkbird Tech.C.L
Contact: support@ink-bird.com | www.ink-bird.com | +86-755-25738050
Shenzhen, GD, 518000, China
1. Overview
What is IHC-200?
The IHC-200 is an easy-to-use, safe, and reliable dual relay output humidity controller. Its plug-and-play design and dual LED screens offer a more user-friendly experience. The IHC-200 can control any 100-265 volt humidifier, dehumidifier, or fan.
Main Features
- Switch between humidification and dehumidification modes automatically.
- Control humidity by setting value and differential value.
- Calibrate the humidity value.
- Delay protection for control output.
- Query current humidity.
- Alarm when humidity exceeds high/low humidity setting value.
- Alarm when sensor error or humidity exceeds limit.
2. Specification
Parameter | Value |
---|---|
Power Input | 100~240VAC, 50Hz/60Hz |
Power Output | Max. 10A, 100V~240V AC |
Power Consumption | <3W |
Humidity Measuring Range | 5%-99.99%RH |
Humidity Control Range | 5%-99%RH |
Resolution | 1%RH |
Accuracy | ±3%RH |
Sensor Model | HTG3535CH |
Sensor Stability | <0.5%RH/yr |
Sensor Length | 2m / 6.56ft |
Relay Contact Capacity | Humidification (12A, 100-240VAC), Dehumidification (12A, 100-240VAC) |
Input Power Cable Length | 1.5m (5ft) |
Output Power Cable Length | 30cm (1ft) |
Dimension | Main Body: 140x68x33mm (5.5x2.7x1.3 inch) Socket (US Version): 85x42x24mm (3.3x1.7x1.0 inch) Socket (EU Version): 135x54x40mm (5.3x2.1x1.6 inch) Socket (UK Version): 140x51x27mm (5.5x2.0x1.0 inch) |
Ambient Temperature | -30~75°C / -22~167°F |
Storage Temperature | -30~75°C / -22~167°F |
Storage Humidity | 20~85% RH (No Condensate) |
Warranty | 1 Year |
3. Keys Instruction
The controller features a display, SET button, UP arrow button, and DOWN arrow button. It connects to devices via humidification and dehumidification sockets. Different socket adapters (US, EU, AU, UK) are shown, each with two outlets.
Key Descriptions:
① PV: Process Value
- In running mode, displays current humidity.
- In setting mode, displays menu code.
- Pressing the decrease and increase keys simultaneously displays the current humidity.
② SV: Setting Value
- In running mode, displays setting humidity.
- In setting mode, displays setting value.
Humidification Indicator Lamp:
- On: Humidification Working.
- Off: Humidification Stop Working.
Dehumidification Indicator Lamp:
- On: Dehumidification Working.
- Off: Dehumidification Stop Working.
- Flicker: Dehumidification Delay.
⑤ SET Key:
- Press and hold for 3 seconds to enter the menu for function setting.
- During the setting process, press and hold for 3 seconds to quit and save changes.
⑥ DECREASE Key:
- In running mode, press to inquire DD value.
- In setting mode, press to decrease value.
⑦ INCREASE Key:
- In running mode, press to inquire HD value.
- In setting mode, press to increase value.
⑧ Humidification Device Socket:
Humidification output.⑨ Dehumidification Device Socket:
Dehumidification output.4. Key Operation Instruction
4.1 Power On/Off
When the controller is working normally, press and hold the [SET Key]
, [Up Arrow]
, and [Down Arrow]
keys simultaneously for 3 seconds to enter the power-off state. All displays and outputs will turn off. To turn on, press and hold the [SET Key]
, [Up Arrow]
, and [Down Arrow]
keys simultaneously for 1 second from the power-off state to enter normal measuring mode.
4.2 Enquiry Differential Value
When the controller is working normally, briefly press the [Up Arrow]
key once; the humidification differential (HD) will be displayed. Briefly press the [Down Arrow]
key once; the dehumidification differential (DD) will be displayed. After two seconds, the display will return to the normal humidity mode.
4.3 Enquiry Measuring Humidity
Press the [Up Arrow]
and [Down Arrow]
keys simultaneously. The current humidity value will be displayed on the PV screen. Release the keys after 2 seconds to return to the normal display mode.
4.4 How to Set Parameters
When the controller is working normally, press and hold the [SET Key]
for 3 seconds to enter parameter setting mode. The PV screen will display the first menu code "HS", and the SV screen will display the corresponding setting value. Press the [SET Key]
to page down through the menu. The code will be displayed, and then use the [Up Arrow]
or [Down Arrow]
keys to change the current parameter value. After finishing settings, press and hold the [SET Key]
for 3 seconds to save the parameter setting value and return to the normal humidity display mode. If there is no operation for 10 seconds during setting, the system will automatically quit the menu and return to normal display without saving modifications.
4.5 Setup Flow Chart
To enter parameter setup mode, press and hold the [SET Key]
for over 3 seconds.
- HS (Humidity Set Value): Default 50%RH. Press
[SET Key]
to proceed. - HD (Humidification Differential Value): Default 5%RH. Press
[SET Key]
to proceed. - DD (Dehumidification Differential Value): Default 5%RH. Press
[SET Key]
to proceed. - AH (Alarm High Humidity Set Value): Default 99%RH. Press
[SET Key]
to proceed. - AL (Alarm Low Humidity Set Value): Default 0%RH. Press
[SET Key]
to proceed. - PT (Delay Protection Value): Default 1 minute. Press
[SET Key]
to proceed. - CA (Humidity Calibration): Default 0%. Press and hold
[SET Key]
for 3 seconds to save and return to 'Working normally' mode.
5. Menu Instruction
Menu Code | Function | Setting Range | Default | Unit | Remarks |
---|---|---|---|---|---|
HS | Humidity Set Value | 5~99 | 50 | % RH | 5.1 |
HD | Humidification Differential Value | 1~20 | 5 | % RH | 5.1 |
DD | Dehumidification Differential Value | 1~20 | 5 | % RH | 5.1 |
AH | Alarm High Humidity Set Value | 50~99 | 99 | % RH | 5.2 |
AL | Alarm Low Humidity Set Value | 0~50 | 0 | % RH | 5.2 |
PT | Delay Protection Value | 0~10 | 1 | minute | 5.3 |
CA | Humidity Calibration | -10~10 | 0 | % | 5.4 |
5.1 Humidity Control Range Setting (HS, HD, DD)
When the controller is working normally, the LED displays the current measured humidity. It then automatically starts recognizing and translating humidifying and dehumidifying actions.
When measured humidity PV ≥ HS (Humidity Set Value) + DD (Dehumidification Differential Value), the controller enters dehumidification mode. The dehumidification indicator lamp turns on, and the dehumidification relay activates. If the dehumidification indicator light flickers, the equipment is in delay protection status. When the measured humidity PV ≤ HS (Humidity Set Value), the dehumidification indicator lamp turns off, and the dehumidification relay stops working.
When the measured humidity PV ≤ HS (Humidity Set Value) – HD (Humidification Differential Value), the controller enters humidification mode. The humidification indicator lamp turns on, and the humidification relay activates. When the measured humidity PV ≥ HS (Humidity Set Value), the humidification indicator lamp turns off, and the humidification relay stops working.
5.2 Alarm High/Low Limit Setting (AH, AL)
When the measured humidity PV ≥ AH (Alarm High Humidity Set Value) or PV ≤ AL (Alarm Low Humidity Set Value), an alarm sounds ("BI-BI-BIII"). The current value, AH, or AL will display on the PV screen. The alarm sound can be stopped by pressing any key, but the alarm status will not change until the measured humidity returns to the normal range.
5.3 Compressor Delay (PT)
In dehumidification mode, after power on, if the measured humidity PV ≥ HS (Humidity Set Value) + DD (Dehumidification Differential Value), the equipment will not start dehumidification immediately but will wait for a delay time.
If the time interval between two dehumidification operations (or from power on to dehumidify) is longer than the preset delay, the equipment starts dehumidification immediately. If the time interval is less than the preset delay, the equipment will not start dehumidification until the preset delay is satisfied.
The delay time is calculated right after the moment dehumidification stops.
5.4 Humidity Calibration (CA)
When there is a deviation between the measured humidity and the actual humidity, use the humidity calibration function to align them. The corrected humidity is equal to the humidity before calibration plus the corrected value (which can be positive, zero, or negative).
6. Error Description
Sensor fault alarm: If the humidity sensor is short-circuited or open-circuited, the controller will enter sensor fault mode and cancel all actions. The buzzer will sound, and the LED will display "ER". The buzzer alarm can be dismissed by pressing any key. After the fault is resolved, the system will return to normal working mode.
7. Technical Assistance and Warranty
7.1 Technical Assistance
If you encounter any problems installing or using this humidity controller, please carefully review the instruction manual. For assistance, write to cs@ink-bird.com. Emails will be replied to within 24 hours from Monday through Saturday.
You can also visit the website www.ink-bird.com for answers to common technical questions.
7.2 Warranty
INKBIRD TECH. C.L. warrants this humidity controller for one year from the date of purchase against defects caused by INKBIRD's workmanship or materials, provided it is operated under normal conditions by the original purchaser (non-transferable). This warranty is limited to the repair or replacement, at INKBIRD's discretion, of all or part of the thermostat. The original receipt is required for warranty claims.
INKBIRD is not liable for property damage or other consequential damages arising directly from the product's workmanship or materials. There are no other representations, warranties, or conditions, express or implied, statutory or otherwise, beyond those contained herein or implied by law.