R. STAHL 8530/1-MCB-STA102-B16-500-3 Circuit Breaker
Article Number: 272126
Product Overview
The R. STAHL 8530/1-MCB-STA102-B16-500-3 circuit breaker is a component for system technology. It features a modular design for easy installation and expansion, suitable for DIN mounting in Ex e enclosures. The device offers fixed thermal and magnetic tripping and an ergonomic operating lever for safe connection and disconnection. It also includes protection against reconnection during maintenance via padlocks (accessories).
These circuit breakers offer good current limitation in case of short circuits and high breaking capacities of 10, 15, or 25 kA, leading to reduced stress on electrical lines and improved selectivity with upstream fuses. They are available in 1 to 4-pole versions for nominal currents from 0.5–63 A, with a maximum mounting width of 4.5 division units.
Technical Data
Explosion Protection
Parameter | Value |
---|---|
Applications (zones) | 1, 2 |
Applications (zones) Note | Can be used in zones 21/22 with Ex tb/tc enclosure protection |
IECEX gas approval | IECEX FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX gas approval | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of conformity | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Parameter | Value |
---|---|
Rated operational voltage AC | 230/400 V |
Rated operational current | 16 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | Auxiliary contact 1 changeover + Signal contact 1 changeover |
Voltage 1st auxiliary function AC | 230 V |
Max. current 1st auxiliary function | 2 A |
2nd auxiliary function | None |
Max. voltage 2nd aux. function DC | 8 |
Number of poles | 2-pole |
Environmental Conditions
Parameter | Value |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Parameter | Value |
---|---|
Degree of protection (IP) (IEC 60529) | IP2X |
Enclosure material | Thermoplastic |
Connection terminal cross-section min. | 1.5 mm² |
Connection terminal cross-section max. | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 cross-section min. | 1.5 mm² |
Connection terminal 2 cross-section max. | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Connection terminal HIKO min. | 0.5 mm² |
Connection terminal HIKO max. | 4 mm² |
Connection terminal HIKO min AWG | 18 (unece.unit.AWG) |
Connection terminal HIKO max AWG | 14 (unece.unit.AWG) |
Tightening torque min. | 2 N·m |
Tightening torque max. | 3 N·m |
Connection terminal Note | 2 conductors (upper and lower chamber simultaneously): lower chamber and upper chamber max. 16 / 10 mm² (only one cross-section difference can be accommodated between the upper and lower chamber.) Permitted connection cross-section combinations are listed in the operating instructions. |
Dimensions
Parameter | Value |
---|---|
Width | 83 mm (3.27 in) |
Height | 165 mm (6.5 in) |
Installation depth | 138.3 mm (5.44 in) |
Weight | 1.3 kg (2.867 lb) |
Mounting / Installation
Parameter | Value |
---|---|
Tightening torque | 2–3 N·m |
Tightening torque lbf in | 17.7 ... 26.6 lbf-in |
Tightening torque auxiliary contact | 0.4–0.6 N·m |
Tightening torque auxiliary contact lbf in | 3.5 ... 5.3 lbf in |
Technical Diagrams
Tripping Characteristic Curve: The document includes a graph illustrating the tripping characteristic curve for the circuit breaker, showing the relationship between time and current for different tripping curves (e.g., B curve) under various conditions.
Dimensional Drawings: Schematics provide detailed measurements of the circuit breaker, including width, height, installation depth, and mounting dimensions, with values provided in both millimeters and inches.
Accessories
Cylinder Lock
Description: For locking (shackle Ø 3)
Article Number: 107115
Quadruple Immobilization Device
Description: Locking pliers / labeling for individual component locking using up to 4 cylinder locks.
Article Number: 227232
Fixing Kit
Description: A set of fasteners for mounting the component on a mounting plate without a top hat rail.
Article Number: 276618
General Information
R. STAHL Schaltgeräte GmbH reserves the right to modify technical data, dimensions, weights, constructions, and delivery options.
Contact Information:
R. STAHL Schaltgeräte GmbH
Am Bahnhof 30 | 74638 WALDENBURG
Tel. +49 7942 943 1700 | +49 7942 943 1777
Email: sales.de@r-stahl.com | r-stahl.com