R. STAHL 8530/1-MCB-STA102-B16-500-3 Line Protection Circuit Breaker
Article Number: 272126
Product Overview
The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation in case of short circuits and high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4 pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).
Key features include:
- Disconnection according to EN 60947-2
- Energy limitation class 3
- Easy replacement or extension of your system thanks to the modular design
- Simple mounting by clipping onto a DIN rail in Ex e enclosures
- Fixed magneto-thermal releases
- Ergonomic operating lever for safe operation and shutdown
- Padlock protection (accessories) prevents restarting during maintenance
Technical Characteristics
Explosion Protection
Characteristic | Specification |
---|---|
Application Area (Zones) | 1, 2 |
Application Area (Zones) Note | Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure |
IECEx Certificate Gas | IECEx FMG 19.0029U |
IECEx Explosion Protection Gas | Ex db eb IIC Gb |
ATEX Certificate Gas | FM19ATEX0191U |
ATEX Explosion Protection Gas | II 2 G Ex db eb IIC Gb |
Certificates | ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX), China (CCC) |
Electrical Characteristics
Characteristic | Specification |
---|---|
Rated Operational Voltage AC | 230/400 V |
Rated Operational Current | 16 A |
Frequency | 50/60 Hz |
Rated Switching Capacity | 10 kA |
Electrical Service Life | 2 x 104 |
Mechanical Service Life | 2 x 104 |
1st Auxiliary Function | Auxiliary contact 1 changeover contact + signal error contact 1 changeover contact |
Voltage 1st Auxiliary Function AC | 230 V |
Max. Current 1st Auxiliary Function | 2 A |
2nd Auxiliary Function | None |
Max. Voltage 2nd Auxiliary Function DC | B |
Tripping Characteristic | B |
Number of Poles | 2 poles |
Mechanical Characteristics
Characteristic | Specification |
---|---|
Ambient Temperature | -40 °C ... 70 °C |
Ambient Temperature | -40 °C ... 70 °C |
Ambient Temperature | -40 °F ... 158 °F |
Ambient Temperature | -40°F ... +158°F |
Ambient Temperature Note | Ambient temperatures different from the base of the current certificates, on request |
Degree of Protection (IP) (IEC 60529) | IP2X |
Enclosure Material | Thermoplastic |
Connection Terminal Minimum | 1.5 mm² |
Connection Terminal Maximum | 25 mm² |
Connection Terminal AWG min. | 16 AWG |
Connection Terminal AWG max. | 4 AWG |
Connection Terminal 2 min. | 1.5 mm² |
Connection Terminal 2 max. | 10 mm² |
Connection Terminal 2 AWG min. | 16 AWG |
Connection Terminal 2 AWG max. | 8 AWG |
Conn. Term. aux. min. | 0.5 mm² |
Conn. Term. aux. max. | 4 mm² |
Conn. Term. aux. min. AWG | 18 (unece.unit.AWG) |
Conn. Term. aux. max. AWG | 14 (unece.unit.AWG) |
Torque min. | 2 N·m |
Torque max. | 3 N·m |
Connection Terminal Note | Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.) |
Width | 83 mm |
Width in inches | 3.27 in |
Length | 165 mm |
Length in inches | 6.5 in |
Mounting Depth | 138.3 mm |
Mounting Depth in inches | 5.44 in |
Weight | 1.3 kg |
Weight | 2.867 lb |
Mounting / Installation
Characteristic | Specification |
---|---|
Torque | 2-3 N·m |
Torque in lbf in | 17.7 ... 26.6 lbf-in |
Torque Auxiliary Contact | 0.4-0.6 Nm |
Torque Auxiliary Contact lbf in | 3.5 ... 5.3 lbf in |
Technical Drawings
Tripping Characteristic Curve
The tripping characteristic curve shows the relationship between the multiple of the rated current (I/In) and the tripping time. The curve is a limit curve from the cold state.
Overall Dimensions (all dimensions in mm [inches])
Diagram showing the dimensions of the circuit breaker, including width, length, and mounting depth.
Accessories
Quadruple Locking Device
A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.
Description | Article Number |
---|---|
Quadruple locking device allowing individual locking of the component using up to 4 cylinder locks. | 227232 |
Fixing Kit
A fixing kit for mounting the component onto a DIN rail without a mounting plate.
Description | Article Number |
---|---|
A fixing kit for mounting the component onto a DIN rail without a mounting plate. | 276618 |
Cylinder Lock
For locking (Ø 3 shackle).
Description | Article Number |
---|---|
For locking (Ø 3 shackle) | 107115 |
Subject to technical modifications, dimensions, weights, construction types, and delivery possibilities. Figures are for illustrative purposes only.