R. STAHL 8530/1-MCB-STA102-B16-500-3 Line Protection Circuit Breaker

Article Number: 272126

Product Overview

The R. STAHL 8530 series line protection circuit breakers offer excellent current limitation in case of short circuits and high switching capacity of 10, 15, or 25 kA. This ensures minimal load on lines and high selectivity to upstream fuses. The components are modular and available in 1 to 4 pole versions for nominal currents from 0.5–63 A. The maximum installation capacity is 4.5 partial units (UP).

Key features include:

Technical Characteristics

Explosion Protection

Characteristic Specification
Application Area (Zones) 1, 2
Application Area (Zones) Note Usable in Zone 21 / 22 with protection by Ex tb / tc enclosure
IECEx Certificate Gas IECEx FMG 19.0029U
IECEx Explosion Protection Gas Ex db eb IIC Gb
ATEX Certificate Gas FM19ATEX0191U
ATEX Explosion Protection Gas II 2 G Ex db eb IIC Gb
Certificates ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
Certificate of Conformity Certificate of Conformity (ATEX), China (CCC)

Electrical Characteristics

Characteristic Specification
Rated Operational Voltage AC 230/400 V
Rated Operational Current 16 A
Frequency 50/60 Hz
Rated Switching Capacity 10 kA
Electrical Service Life 2 x 104
Mechanical Service Life 2 x 104
1st Auxiliary Function Auxiliary contact 1 changeover contact + signal error contact 1 changeover contact
Voltage 1st Auxiliary Function AC 230 V
Max. Current 1st Auxiliary Function 2 A
2nd Auxiliary Function None
Max. Voltage 2nd Auxiliary Function DC B
Tripping Characteristic B
Number of Poles 2 poles

Mechanical Characteristics

Characteristic Specification
Ambient Temperature -40 °C ... 70 °C
Ambient Temperature -40 °C ... 70 °C
Ambient Temperature -40 °F ... 158 °F
Ambient Temperature -40°F ... +158°F
Ambient Temperature Note Ambient temperatures different from the base of the current certificates, on request
Degree of Protection (IP) (IEC 60529) IP2X
Enclosure Material Thermoplastic
Connection Terminal Minimum 1.5 mm²
Connection Terminal Maximum 25 mm²
Connection Terminal AWG min. 16 AWG
Connection Terminal AWG max. 4 AWG
Connection Terminal 2 min. 1.5 mm²
Connection Terminal 2 max. 10 mm²
Connection Terminal 2 AWG min. 16 AWG
Connection Terminal 2 AWG max. 8 AWG
Conn. Term. aux. min. 0.5 mm²
Conn. Term. aux. max. 4 mm²
Conn. Term. aux. min. AWG 18 (unece.unit.AWG)
Conn. Term. aux. max. AWG 14 (unece.unit.AWG)
Torque min. 2 N·m
Torque max. 3 N·m
Connection Terminal Note Connection of 2 conductors (upper and lower chamber simultaneously): Upper and lower chamber max. 16 / 10 mm² (Connection can be made with a maximum section difference between the upper and lower chamber.)
Width 83 mm
Width in inches 3.27 in
Length 165 mm
Length in inches 6.5 in
Mounting Depth 138.3 mm
Mounting Depth in inches 5.44 in
Weight 1.3 kg
Weight 2.867 lb

Mounting / Installation

Characteristic Specification
Torque 2-3 N·m
Torque in lbf in 17.7 ... 26.6 lbf-in
Torque Auxiliary Contact 0.4-0.6 Nm
Torque Auxiliary Contact lbf in 3.5 ... 5.3 lbf in

Technical Drawings

Tripping Characteristic Curve

The tripping characteristic curve shows the relationship between the multiple of the rated current (I/In) and the tripping time. The curve is a limit curve from the cold state.

Overall Dimensions (all dimensions in mm [inches])

Diagram showing the dimensions of the circuit breaker, including width, length, and mounting depth.

Accessories

Quadruple Locking Device

A locking/unlocking system that allows individual locking of the component using up to 4 cylinder locks.

Description Article Number
Quadruple locking device allowing individual locking of the component using up to 4 cylinder locks. 227232

Fixing Kit

A fixing kit for mounting the component onto a DIN rail without a mounting plate.

Description Article Number
A fixing kit for mounting the component onto a DIN rail without a mounting plate. 276618

Cylinder Lock

For locking (Ø 3 shackle).

Description Article Number
For locking (Ø 3 shackle) 107115

Subject to technical modifications, dimensions, weights, construction types, and delivery possibilities. Figures are for illustrative purposes only.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-b16-500-3-272126-fr-fr-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA102-B16-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B16-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C40-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C40-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C25-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C25-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B6-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B6-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA101-B16-500-2 Circuit Breaker for Line Protection
Technical specifications and features of the R. STAHL 8530/1-MCB-STA101-B16-500-2 circuit breaker for line protection, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B16-500-3 Circuit Breaker: Technical Specifications and Features
Detailed technical specifications, features, and accessories for the R. STAHL 8530/1-MCB-STA102-B16-500-3 circuit breaker, including explosion protection data, electrical characteristics, mechanical data, and dimensions.
Preview R. STAHL 8530/1-MCB-STA102-B16-000-2 Line Protection Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B16-000-2 line protection circuit breaker, including electrical characteristics, environmental conditions, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C1-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.