R. STAHL 8530/1-MCB-STA102-B6-500-3 Circuit Breaker
Article Number: 272123
[Image of R. STAHL circuit breaker]
System Technology Components - Circuit Breaker
The R. STAHL 8530 series circuit breakers offer excellent short-circuit current limitation and high breaking capacity (10, 15, or 25 kA). This results in reduced stress on electrical lines and improved selectivity with respect to upstream fuses. The modules feature a modular design, available in 1 to 4-pole versions and for nominal currents from 0.5–63 A. The maximum mounting width is 4.5 division units.
Key Features:
- Protective Separator Function: Complies with EN 60947-2.
- Energy Limitation Class: Class 3.
- Easy Installation: Simple replacement or expansion of installations due to modular design, suitable for DIN mounting rails in Ex e enclosures.
- Fixed Trip Settings: Thermal and magnetic trip adjusted.
- Ergonomic Lever: Ensures safe connection and disconnection.
- Reconnection Protection: Protection against reconnection during maintenance using padlocks (accessories).
Technical Data
Explosion Protection
Applications (zones) | Applications (zones) Note | IECEX gas homologation | IECEx gas explosion protection | ATEX gas homologation | ATEX gas explosion protection |
---|
1, 2 | Can be used in zones 21/22 with Ex tb/tc enclosure protection | IECEX FMG 19.0029U | Ex db eb IIC Gb | FM19ATEX0191U | II 2 G Ex db eb IIC Gb |
Certifications
Certifications | Certificate of conformity |
---|
ATEX (FM), Brasil (ULB), China (CQST), IECEX (FM) | Certificate of conformity (ATEX), China (CCC) |
Electrical Data
Operating voltage AC | Rated switching capacity | Frequency | Rated switching capacity | Electrical service life | Mechanical service life | 1st auxiliary function | Voltage 1st auxiliary function AC | Max. current 1st auxiliary function | 2nd auxiliary function | Max. voltage 2nd aux. CC | Trip characteristic | Number of poles |
---|
230/400 V | 6 A | 50/60 Hz | 10 kA | 2 x 10⁴ | 2 x 10⁴ | Auxiliary contact 1 changeover + Error signal contact 1 changeover | 230 V | 2 A | none | | B | 2-pole |
Environmental Conditions
Ambient temperature | Ambient temperature | Ambient temperature | Ambient temperature | Ambient temperature Note |
---|
-40 °C ... 70 °C | -40 °C ... 70 °C | -40 °F ... 158 °F | -40 °F ... 158 °F | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | Enclosure material | Minimum connection cross-section | Maximum connection cross-section | Minimum AWG connection cross-section | Maximum AWG connection cross-section | Minimum connection cross-section 2 | Maximum connection cross-section 2 | Minimum AWG connection cross-section 2 | Maximum AWG connection cross-section 2 | Minimum HIKO connection cross-section | Maximum HIKO connection cross-section | Minimum HIKO connection cross-section AWG | Maximum HIKO connection cross-section AWG | Minimum tightening torque | Maximum tightening torque | Connection cross-section Note |
---|
IP2X | Thermoplastic | 1.5 mm² | 25 mm² | 16 AWG | 4 AWG | 1.5 mm² | 10 mm² | 16 AWG | 8 AWG | 0.5 mm² | 4 mm² | 18 (unece.unit.AWG) | 14 (unece.unit.AWG) | 2 N·m | 3 N·m | 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only one cross-sectional difference between the upper and lower chamber can be wired). Permitted connection cross-section combinations are shown in the instructions for use. |
Dimensions
Width | Mounting width in inches | Length | Length in inches | Installation depth | Installation depth in inches | Weight | Weight in lb |
---|
83 mm | 3.27 in | 165 mm | 6.5 in | 138.3 mm | 5.44 in | 1.3 kg | 2.867 lb |
Mounting / Installation
Tightening torque | Tightening torque lbf in | Tightening torque auxiliary contact | Tightening torque auxiliary contact lbf in |
---|
2–3 N·m | 17.7 ... 26.6 lbf-in | 0.4–0.6 Nm | 3.5 ... 5.3 lbf in |
Accessories
Cylinder Lock
[Image of cylinder lock] | Cylinder lock / tagout device for individual component lockout using up to 4 cylinder locks. | Article No.: 107115 |
Quadruple Immobilization Device
[Image of lockout/tagout tool] | Lockout/tagout pliers for individual component lockout using up to 4 cylinder locks. | Article No.: 227232 |
Fixing Kit
[Image of fixing kit] | Set of fixings for mounting the component on the mounting plate without a top-hat rail. | Article No.: 276618 |
R. STAHL reserves the right to modify technical data, dimensions, weights, designs, and delivery options.
Document Version: V 0.106 ES
Date: 2025-06-27
Manufacturer: R. STAHL Schaltgeräte GmbH | Am Bahnhof 30 | 74638 WALDENBURG
Contact: Tel. +49 7942 943 1700 | +49 7942 943 1777 | Email: sales.de@r-stahl.com | r-stahl.com