R. STAHL Miniature Circuit Breaker
Model: 8530/1-MCB-STA101-C10-500-2
Art. No.: 293995
Key Features
- Isolation function in accordance with EN60947-2
- Energy limitation class 3
- Modular design for simple replacement or expansion
- Easy installation: snaps onto the mounting rail in Ex e enclosures
- Non-adjustable thermal and magnetic releases
- Ergonomically shaped operating lever for safe switching
- Padlocks (Accessories) for protection against unauthorized switching during maintenance
Product Overview
R. STAHL 8530 series miniature circuit breakers are overcurrent devices offering excellent current limiting for short circuits and high switching capacity (10, 15, or 25 kA). They minimize load on cables and provide high selectivity for upstream fuses. Available in 1- to 4-pole versions and rated currents from 0.5-63 A, with a maximum installation capacity of 4.5 subunits.
Technical Data
Explosion Protection
- Application range (zones): 1, 2
- Application range (Zone) note: For use in Zone 21/22 when protected by Ex tb/tc enclosure
- IECEx gas certificate: IECEx FMG 19.0029U
- IECEx gas explosion protection: Ex db eb IIC Gb
- ATEX gas certificate: FM19ATEX0191U
- ATEX gas explosion protection: II 2 G Ex db eb IIC Gb
- Certificates: ATEX (FM), Brazil (ULB), China (CQST), IECEx (FM)
- Declaration of conformity: Certificate of conformity (ATEX)
Electrical Data
Parameter | Value |
---|---|
Rated operational voltage AC | 230 V |
Rated operational current | 10 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 104 |
Mechanical service life | 2 x 104 |
1st auxiliary function | Auxiliary contact 1 change-over contact + fault signal contact 1 change-over contact |
1st auxiliary function for AC rated voltage | 230 V |
1st auxiliary function for rated current max. | 2 A |
2nd auxiliary function | without |
2nd auxiliary function voltage max. DC | - |
Tripping characteristic | C |
No. of poles | 1-pole |
Ambient Conditions
- Ambient temperature: -40 °C ... 70 °C
- Ambient temperature (Fahrenheit): -40 °F ... 158 °F
- Ambient temperature note: Deviating ambient temperatures based on current certificates available on request
Mechanical Data
- Degree of protection (IP) (IEC 60529): IP2X
- Enclosure material: Thermoplast
- Connection cross section min.: 1.5 mm²
- Connection cross-section max.: 25 mm²
- Connection cross-section AWG min.: 16 AWG
- Connection cross-section AWG max.: 4 AWG
- Connection cross-section 2 min.: 1.5 mm²
- Connection cross-section 2 max.: 10 mm²
- Connection cross-section 2 AWG min.: 16 AWG
- Connection cross-section 2 AWG max.: 8 AWG
- Min. aux. cont. con. cr.-sect.: 0.5 mm²
- Max. aux. cont. conn. cr.-sec.: 4 mm²
- Min. aux. co. con. cr.-se. AWG: 18 (unece.unit.AWG)
- Connection cross-section of auxiliary contact AWG max.: 14 (unece.unit.AWG)
- Min. tightening torque: 2 N·m
- Max. tightening torque: 3 N·m
- Connection cross-section note: 2-conductor connection (upper and lower chamber at the same time): upper and lower chamber max. 16/10 mm² (A maximum difference of one cross section may be clamped between the upper and lower chamber.) Permitted combinations of connection cross-sections can be found in the operating instructions.
Dimensions
- Width: 65 mm (2.56 in)
- Length: 165 mm (6.5 in)
- Mounting depth: 138.3 mm (5.44 in)
Weight
- Weight: 1 kg (2.205 lb)
Mounting / Installation
- Tightening torque: 2-3 N·m (17.7 to 26.6 lbf·in)
- Tightening torque auxiliary contact: 0.4-0.6 N·m (3.5 to 5.3 lbf·in)
Technical Drawings
Tripping Characteristic C: A graph illustrates the tripping time in seconds and minutes against multiples of rated current for AC and DC, showing the characteristic curve for the circuit breaker.
Dimensional Drawings: Detailed diagrams show the dimensions of the circuit breaker in millimeters and inches, including width, length, mounting depth, and pitch for horizontal mounting.
Accessories
4-way locking device
A lock-out/tag-out hasp for individually locking the component using up to four cylinder locks.
Art. No.: 227232
Cylinder lock
For closing (bracket Ø 3)
Art. No.: 107115
Fastening set
A fastening set for securing the component on the mounting plate without a DIN rail.
Art. No.: 276618
R. STAHL reserves the right to make alterations to the technical data, dimensions, weights, designs, and products available without notice. The illustrations cannot be considered binding.