R. STAHL 8530/1-MCB-STA102-B25-500-3 Circuit Breaker

Article Number: 272128

Product Description

The R. STAHL 8530/1-MCB-STA102-B25-500-3 circuit breaker is a component for systems designed for explosion protection. It features a high current limitation in case of short circuits and a high breaking capacity of 10, 15, or 25 kA, resulting in reduced load on electrical lines and high selectivity with upstream fuses. The modular design allows for easy installation and expansion, with models available in 1 to 4 poles and nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.

Key Features:

Technical Data

Explosion Protection

Applications (zones) 1, 2
Applications (zones) Note Can be used in zones 21/22 with Ex tb/tc enclosure protection
IECEx gas homologation IECEX FMG 19.0029U
IECEx Gas Explosion Protection Ex db eb IIC Gb
ATEX gas homologation FM19ATEX0191U
ATEX Gas Explosion Protection II 2 G Ex db eb IIC Gb
Certifications ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM)
Certificate of conformity Certificate of conformity (ATEX), China (CCC)

Electrical Data

Rated operating voltage AC 230/400 V
Rated operating current 25 A
Frequency 50/60 Hz
Rated switching capacity 10 kA
Electrical service life 2 x 10⁴
Mechanical service life 2 x 10⁴
1st auxiliary function Auxiliary contact 1 changeover + Error signal contact 1 changeover
Voltage 1st auxiliary function AC 230 V
Max. current 1st auxiliary function 2 A
2nd auxiliary function None
Max. voltage 2nd aux. function DC 8
Tripping characteristic B
Number of poles 2-pole

Environmental Conditions

Ambient temperature -40 °C ... 70 °C
Ambient temperature (°F) -40 °F ... 158 °F
Ambient temperature Note Divergent ambient temperatures based on valid certificates upon request

Mechanical Data

Degree of protection (IP) (IEC 60529) IP2X
Enclosure material Thermoplastic
Minimum connection cross-section 1.5 mm²
Maximum connection cross-section 25 mm²
Minimum AWG connection cross-section 16 AWG
Maximum AWG connection cross-section 4 AWG
Minimum connection cross-section 2 1.5 mm²
Maximum connection cross-section 2 10 mm²
Minimum AWG connection cross-section 2 16 AWG
Maximum AWG connection cross-section 2 8 AWG
Minimum HIKO connection cross-section 0.5 mm²
Maximum HIKO connection cross-section 4 mm²
Minimum HIKO connection cross-section AWG 18 (unece.unit.AWG)
Maximum HIKO connection cross-section AWG 14 (unece.unit.AWG)
Minimum torque 2 N·m
Maximum torque 3 N·m
Connection cross-section Note 2 conductor connections (upper and lower chamber simultaneously): upper and lower chamber max. 16 / 10 mm² (only one cross-sectional difference can be accommodated in the upper and lower chamber.) Permitted connection cross-section combinations are listed in the operating instructions.

Dimensions

Width 83 mm
Width mounting inches 3.27 in
Length 165 mm
Length inches 6.5 in
Installation depth 138.3 mm
Installation depth inches 5.44 in
Weight 1.3 kg
Weight lbs 2.867 lb

Mounting / Installation

Torque 2-3 N·m
Torque lbf·in 17.7 ... 26.6 lbf·in
Torque auxiliary contact 0.4 - 0.6 N·m
Torque auxiliary contact lbf·in 3.5 ... 5.3 lbf·in

Accessories

Cylinder Lock

For locking (stirrup Ø 3) Article No.: 107115

Quadruple Immobilization Device

Locking/tagging pliers for individual component locking using up to 4 cylinder locks. Article No.: 227232

Fixing Kit

A fixing kit for mounting the component on the mounting plate without a top hat rail. Article No.: 276618

Technical Drawings and Diagrams

Tripping Characteristic Curve B: A graph illustrating the tripping characteristic for AC and DC, showing time versus current. The curve indicates the time it takes for the breaker to trip under various fault current conditions.

Measurement Diagram: Schematics showing the dimensions of the circuit breaker, including width, height, depth, and mounting dimensions. Measurements are provided in both millimeters and inches.

Exploded View Diagram: An illustration showing the different parts of the circuit breaker for assembly or maintenance reference.

PDF preview unavailable. Download the PDF instead.

ex-ficha-tecnica-individual-disyuntor-8530-1-mcb-sta102-b25-500-3-272128-es-es-rstahl Adobe PDF Library 17.0

Related Documents

Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker - Technical Data and Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for system solutions in hazardous environments.
Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker - Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B25-500-3 Line Protection Circuit Breaker
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-500-3 line protection circuit breaker, including explosion protection, electrical characteristics, mechanical specifications, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-B6-500-3 Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-B6-500-3 circuit breaker, including features, electrical data, mechanical data, environmental conditions, and accessories. This document provides comprehensive information for system integrators and engineers.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Circuit Breaker Technical Data
Technical specifications and features of the R. STAHL 8530/1-MCB-STA102-C1-500-3 circuit breaker, including explosion protection, electrical data, mechanical data, and accessories. Suitable for Ex zones.
Preview R. STAHL 8530/1-MCB-STA102-B25-000-2 Miniature Circuit Breaker Technical Data
Detailed technical specifications and features of the R. STAHL 8530/1-MCB-STA102-B25-000-2 miniature circuit breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker - Technical Data
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C1-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories.
Preview R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker - Technical Specifications
Detailed technical specifications for the R. STAHL 8530/1-MCB-STA102-C2-500-3 Miniature Circuit Breaker, including explosion protection, electrical data, mechanical data, and accessories. Features include high current limiting, modular design, and ATEX/IECEx certifications.