R. STAHL Circuit Breaker
Model: 8530/1-MCB-STA102-B16-000-2
Article Number: 293918
Product Description
The R. STAHL 8530/1-MCB-STA102-B16-000-2 circuit breaker is part of the system technology components. It features a modular design for easy installation and expansion, DIN rail mounting for Ex e enclosures, and fixed thermal and magnetic trip adjustments. The ergonomic operating lever ensures safe connection and disconnection, and it includes protection against reconnection during maintenance via padlocks (accessories).
These circuit breakers offer good current limitation in case of short circuits and high breaking capacities (10, 15, or 25 kA), leading to reduced electrical load on lines and improved selectivity with upstream fuses. They are available in 1 to 4-pole versions for nominal currents from 0.5–63 A. The maximum mounting capacity is 4.5 division units.
Technical Data
Explosion Protection
Applications (zones) | 1, 2 |
---|---|
Applications (zones) Note | Can be used in zones 21/22 with protection by Ex tb/tc enclosure |
IECEx gas certification | IECEX FMG 19.0029U |
IECEx Gas Explosion Protection | Ex db eb IIC Gb |
ATEX gas certification | FM19ATEX0191U |
ATEX Gas Explosion Protection | II 2 G Ex db eb IIC Gb |
Certifications | ATEX (FM), Brazil (ULB), China (CQST), IECEX (FM) |
Certificate of Conformity | Certificate of Conformity (ATEX) |
Electrical Data
Rated operational voltage AC | 230/400 V |
---|---|
Rated operational current | 16 A |
Frequency | 50/60 Hz |
Rated switching capacity | 10 kA |
Electrical service life | 2 x 10⁴ |
Mechanical service life | 2 x 10⁴ |
1st auxiliary function | none |
Rated voltage 1st auxiliary function AC | - |
Maximum current 1st auxiliary function | - |
2nd auxiliary function | none |
Maximum voltage 2nd auxiliary function DC | - |
Trip characteristic | B |
Number of poles | 2-pole |
Environmental Conditions
Ambient temperature | -40 °C ... 70 °C |
---|---|
Ambient temperature | -40 °C ... 70 °C |
Ambient temperature | -40 °F ... 158 °F |
Ambient temperature | -40°F ... +158°F |
Ambient temperature Note | Divergent ambient temperatures based on valid certificates upon request |
Mechanical Data
Degree of protection (IP) (IEC 60529) | IP2X |
---|---|
Enclosure material | Thermoplastic |
Connection terminal cross-section minimum | 1.5 mm² |
Connection terminal cross-section maximum | 25 mm² |
Connection terminal AWG min. | 16 AWG |
Connection terminal AWG max. | 4 AWG |
Connection terminal 2 minimum | 1.5 mm² |
Connection terminal 2 maximum | 10 mm² |
Connection terminal 2 AWG min. | 16 AWG |
Connection terminal 2 AWG max. | 8 AWG |
Tightening torque minimum | 2 N·m |
Tightening torque maximum | 3 N·m |
Connection terminal Note | 2 conductor connections (upper and lower chamber simultaneously): lower and upper chamber max. 16 / 10 mm² (only a difference in cross-section between the upper and lower chamber can be connected). Permitted connection cross-section combinations are shown in the user instructions. |
Width | 65 mm |
Mounting width in inches | 2.56 in |
Length | 165 mm |
Length inches | 6.5 in |
Installation depth | 138.3 mm |
Installation depth inches | 5.44 in |
Weight | 1 kg |
Weight | 2.205 lb |
Mounting / Installation | |
Tightening torque | 2-3 N·m |
Tightening torque lbf·in | 17.7 ... 26.6 lbf·in |
Tightening torque auxiliary contact | 0.4–0.6 Nm |
Tightening torque auxiliary contact lbf·in | 3.5 ... 5.3 lbf·in |
Technical Diagrams
Trip Curve: The document includes a graph illustrating the trip curve characteristic for the circuit breaker, showing the relationship between time and current for different trip characteristics (e.g., B curve for AC and DC). It details the time in seconds and minutes against current in Amperes.
Measurement Diagram: A dimensional drawing is provided, showing the overall dimensions of the circuit breaker in millimeters and inches. Key dimensions include width, length, installation depth, and mounting width.
Accessories
Accessory | Description | Article Number |
---|---|---|
Cylinder lock |
Cylinder lock for blocking (shackle Ø 3) | 107115 |
Quadruple immobilization device |
Locking/tagging pliers for individual component locking using up to 4 cylinder locks. | 227232 |
Fixing kit |
A fixing kit for mounting the component on the mounting plate without a top-hat rail. | 276618 |