General Information & Specifications
Product Name: Formula 65 LED CT
Manufacturer: Beghelli S.p.A.
Address: Via Mozzeghine 13/15, località Monteveglio 40053 Valsamoggia (BO), ITALY
Contact: Tel. +39 051 9660411, Fax +39 051 9660444, Toll-Free 800 626626
Website: www.beghelli.com
Operating Temperature: -10°C to 45°C
Power Supply: 230V - 50Hz
Ingress Protection: IP65
Certifications: UKCA, CE, ISO 14001, ISO 9001
WEEE Symbol: [Waste Electrical and Electronic Equipment symbol]
Dimensions
The fixture has the following approximate dimensions:
- Length: 354mm
- Width: 152mm
- Height/Depth: 48.5mm
- Housing Depth: 83mm
Installation and Wiring
Battery Connector Options
Various battery connector codes are available, including:
- cod. 19040
- cod. 19041
- cod. 19042
- cod. 19043
- cod. 19045
- cod. 19290, 19291, 19294 (for SA - Standard Autonomy)
- cod. 19292, 19293, 19295, 19296 (for SE - Emergency)
Cable Entry: Suitable for cables with a diameter of Ø 16-20mm.
Basic Autonomy Setting (1h-3h) without App
The autonomy can be set by connecting the battery AFTER cutting a specific wire. A 1-hour autonomy is achieved with the wire intact, and a 3-hour autonomy with the wire cut.
Important Note: The autonomy selection made via the App takes priority over circuit settings.
Wiring Diagrams
Wiring with Infinity Mode Deactivated
SA (Standard Autonomy): Wiring connections for Neutral (N), Live (L), L2, and N2 terminals.
SE (Emergency): Wiring connections for Neutral (N), Live (L), L2, and N2 terminals.
Optional Central Unit: Connections can be made to the optional Central unit cod. 20151 (for SA or SE modes).
General Wiring Precautions:
- Connect the battery AFTER cutting the wire for autonomy selection.
- Do NOT invert phase and neutral polarity.
- Maximum connectable lamps: 32.
- Do not connect other devices on the power cable/BUS L+ N-.
- For proper functioning, consult the manuals for the CableCom Connect Central unit (cod. 20151).
- Batteries must be sufficiently charged for Central configuration.
Wiring with Infinity Mode Activated
SA-SE (Standard Autonomy - Emergency): Wiring connections for N, L, L2, and N2 terminals.
Schema 2.1 (SA-SE): The fixture enters emergency mode due to: absence of general emergency power (CableCom network) OR absence of local lighting.
Schema 2.2 (SA-SE): The fixture enters emergency mode due to: absence of general emergency power (CableCom network).
Caution: SA luminaires can only be set to SE mode via the App (using smartphone flash on the lamp or Wi-Fi with Central CableCom Connect). When Infinity mode is active, terminals N2 and L2 must always be connected as shown in schemas 2.1 or 2.2.
Technical Specifications & Battery Options
The following table details available battery connector options and their specifications:
Battery Connector Code | Type | Voltage | Current | COS φ | LEDs | Battery Type | Autonomy Options |
---|---|---|---|---|---|---|---|
19290 | SE | 230V 50Hz | 180mA | 0.07 | 32 LED | Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
19291 | SE | 230V 50Hz | 180mA | 0.07 | 32 LED | Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
19292 | SE | 230V 50Hz | 180mA | 0.07 | 32 LED | 2x Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
19293 | SE | 230V 50Hz | 180mA | 0.07 | 32 LED | 2x Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
19294 | SA | 230V 50Hz | 180mA | 0.115 | 32 LED | Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
19295 | SA | 230V 50Hz | 180mA | 0.115 | 32 LED | 2x Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
19296 | SA | 230V 50Hz | 180mA | 0.115 | 32 LED | 2x Life 6.4V 1.5Ah | 1h, 1.5h, 2h, 3h, 8h |
Note: For autonomy management, refer to the table. With Infinity mode activated and wired as per scheme 2.1, autonomy is infinite when the CableCom network (N-L+) is present.
Expansion Modules
The fixture can be expanded with the following modules:
- LG Module (Cod. 15036)
- LG FM Module (Cod. 15037)
- DALI Module (Cod. 15038)
These modules are SELV (Safety Extra Low Voltage).
Configuration and Commands
Configuration Options
The fixture can be configured for various settings:
- Autonomy Duration: 1h, 1.5h, 2h, 3h, 8h
- SE/SA Setting (only on SA luminaires)
- AT Setting (even/odd)
- Test Duration: 1h or set autonomy
- Infinity Mode Setting
- Rest Mode
- Factory Reset
Commands
Available commands include:
- Start/Stop Functional Test
- Start/Stop Duration Test
- Sync Automatic Test
- Scheduling Automatic Test
- Failure Report from Remote Place
- Luminaire Tracking
- Type of Luminaire Identification
Configuration Methods
1. AT (without APP and without Central Unit)
Default Settings:
- Autonomy: 1h (wire intact)
- Test Duration: 1h
- Infinity Mode: Disabled by default
Jumper Settings: Can be used for some configurations.
QR Code ID: Preset by the QR code ID; not modifiable.
2. Use with B.connect App
Procedure:
- Open the B.connect App (available on the App Store and Google Play).
- Access lamp configuration via the "luminaire" menu.
Lamp Response:
- 1 high brightness flash: Function performed.
- 5 low light flashes: Function NOT enabled.
- No flashing: Command NOT received.
QR Code: Each device has a unique QR code for identification.
App Positioning: For optimal B.connect App coverage, position the lamp within a maximum distance of 50cm (e.g., ensuring good light signal).
3. Centralized Action (AT + CENTRALE CABLECOM CONNECT (cod. 20151) + APP
Features:
- Default settings apply.
- Configurable delayed start.
- Configurable periodicity.
- Remote error reporting: The Central unit's LED indicates errors, and the APP signals which lamp is in error.
Note: With the CableCom Connect control unit (cod. 20151), all configurations and commands can be sent remotely via the "nuBe" cloud.
Automatic Tests and LED Signals
Automatic Tests Periodicity
- Functional Test (30 sec): Every 28 days.
- Autonomy Test (1h): Every 26 weeks.
Even-numbered lamps perform the autonomy test one week after odd-numbered lamps. (Even: 0, 2, ..., 8, A, C, E; Odd: 1, 3, ..., 9, B, D, F).
LED Signals
- Fixed Green: Battery Charged.
- Flashing Green: Battery Charging.
- One Red Flash: Battery Error Duration.
- Two Red Flashes: Lighting LED Error.
- Three Red Flashes: Battery Disconnected.
App Communication and Warnings
Opening Communication from App
To open communication from the app, remove and reapply power for less than 3 seconds. The communication remains possible for 2 hours, and the LED flashes orange for 1 minute to signal this state.
Functional Test and STOP Functional Test can be controlled by the B.connect App at any time without needing to open communication with the device.
Warnings and Guarantee
This device is intended solely for its designed purpose. Any other use is considered improper and potentially dangerous.
The rechargeable battery and LED source are non-replaceable. For any repairs, contact an authorized technical service center and request the use of original spare parts.
Failure to adhere to these conditions may compromise the safety of the device.
Caution: Electric shock hazard.